manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Controllers
  8. •
  9. Emerson dixell XR02CX Wiring diagram

Emerson dixell XR02CX Wiring diagram

Other Emerson Controllers manuals

Emerson Bettis Q series User manual

Emerson

Emerson Bettis Q series User manual

Emerson Fisher 67C Series User manual

Emerson

Emerson Fisher 67C Series User manual

Emerson CASH VALVE B-95 Manual

Emerson

Emerson CASH VALVE B-95 Manual

Emerson Fisher Y696 User manual

Emerson

Emerson Fisher Y696 User manual

Emerson Bettis RTS User manual

Emerson

Emerson Bettis RTS User manual

Emerson Unidrive M400 User manual

Emerson

Emerson Unidrive M400 User manual

Emerson Fisher 585C Series User manual

Emerson

Emerson Fisher 585C Series User manual

Emerson Fisher FIELDVUE DVC2000 User manual

Emerson

Emerson Fisher FIELDVUE DVC2000 User manual

Emerson unidrive m201 User manual

Emerson

Emerson unidrive m201 User manual

Emerson Tartarini OS/66 User manual

Emerson

Emerson Tartarini OS/66 User manual

Emerson Fisher 299H User manual

Emerson

Emerson Fisher 299H User manual

Emerson Unidrive M100 Use and maintenance manual

Emerson

Emerson Unidrive M100 Use and maintenance manual

Emerson Dixell XWi70K Wiring diagram

Emerson

Emerson Dixell XWi70K Wiring diagram

Emerson Dixell WING XW220L Wiring diagram

Emerson

Emerson Dixell WING XW220L Wiring diagram

Emerson Fisher LR125 Series User manual

Emerson

Emerson Fisher LR125 Series User manual

Emerson FISHER 912N Series User manual

Emerson

Emerson FISHER 912N Series User manual

Emerson Bettis G Series User manual

Emerson

Emerson Bettis G Series User manual

Emerson AMPGARD RVSS User manual

Emerson

Emerson AMPGARD RVSS User manual

Emerson dixell XW60LT Wiring diagram

Emerson

Emerson dixell XW60LT Wiring diagram

Emerson El-O-Matic E Series Instruction Manual

Emerson

Emerson El-O-Matic E Series Instruction Manual

Emerson Fisher 92S User manual

Emerson

Emerson Fisher 92S User manual

Emerson E2 User manual

Emerson

Emerson E2 User manual

Emerson Topworx D Series User manual

Emerson

Emerson Topworx D Series User manual

Emerson Fisher FIELDVUE DVC6200 SIS Configuration guide

Emerson

Emerson Fisher FIELDVUE DVC6200 SIS Configuration guide

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

Aprilaire 76 installation instructions

Aprilaire

Aprilaire 76 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

SZ 1598030250 XR02CX RWA GB r1.2 29.08.2013.doc XR02CX 1/2
DIGITAL CONTROLLER
XR02CX
1GENERAL WARNINGS................................................................................................................................... 1
2GENERAL DESCRIPTION.............................................................................................................................. 1
3REGULATION.................................................................................................................................................. 1
4DEFROST ........................................................................................................................................................ 1
5FRONT PANEL COMMANDS ......................................................................................................................... 1
6PARAMETERS ................................................................................................................................................ 1
7INSTALLATION AND MOUNTING.................................................................................................................. 2
8ELECTRICAL CONNECTIONS....................................................................................................................... 2
9HOW TO USE THE HOT KEY ........................................................................................................................ 2
10 ALARM SIGNALLING...................................................................................................................................... 2
11 TECHNICAL DATA.......................................................................................................................................... 2
12 CONNECTIONS............................................................................................................................................... 2
13 DEFAULT SETTING VALUES ........................................................................................................................ 2
1 GENERAL WARNINGS
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick
reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be
used as a safety device.
Check the application limits before proceeding.
1.2 SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see
address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each
other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel
with inductive loads could be useful.
Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring
the same and unchanged functionality.
2 GENERAL DESCRIPTION
Model XR02CX, format 32 x 74 x 50 mm, is a digital thermostat, with off cycle defrost, designed for
refrigeration applications at normal temperature. It provides a relay output to drive the compressor. It is also
provided with 2 NTC probe input. The instrument is fully configurable through special parameters that can be
easily programmed through the keyboard or the by HOT-KEY.
3 REGULATION
3.1 THE REGULATION OUTPUT
The regulation is performed according to
the temperature measured by the
thermostat probe with a positive differential
from the set point: if the temperature
increases and reaches set point plus
differential the compressor is started and
then turned off when the temperature
reaches the set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters CY
and Cn.
4 DEFROST
Defrost is performed through a simple stop of the compressor. Parameter id controls the interval
between defrost cycles, while its length is controlled by parameter Md.
5 FRONT PANEL COMMANDS
To display target set point, in programming mode it selects a parameter or confirm an
operation
(DEF) To start a manual defrost
(UP) In programming mode it browses the parameter codes or increases the displayed
value
AUX
(DOWN) In programming mode it browses the parameter codes or decreases the
displayed value
KEYS COMBINATION
+
To lock or unlock the keyboard
+
To enter in programming mode
+
To return to room temperature display
LED MODE MEANING
On Compressore enabled
Flashing Anti short cycle delay enabled (AC parameter)
On Defrost in progress
Flashing Dripping in progress
On Measurement unit
Flashing Programming mode
On Measurement unit
Flashing Programming mode
5.1 HOW TO SEE THE SET POINT
1. Push and immediately release the SET key, the set point will be showed;
2. Push and immediately release the SET key or wait about 5 sec to return to normal visualisation.
5.2 HOW TO CHANGE THE SETPOINT
1. Push the SET key for more than 2 sec to change the Set point value;
2. The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
3. To change the Set value, push the o or n arrows within 10 sec.
4. To memorise the new set point value push the SET key again or wait for 10 sec.
5.3 HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 sec and a manual defrost will start.
5.4 HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s, value operate as follows:
1. Enter the Programming mode by pressing the SET+DOWN keys for 3 sec (“°C” or “°F”LED starts
blinking).
2. Select the required parameter. Press the SET key to display its value
3. Use UP or DOWN to change its value.
4. Press SET to store the new value and move to the following parameter.
To exit: press SET+UP buttons or wait for 15 sec without pressing any key.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
5.5 TO LOCK THE KEYBOARD
1. Keep pressed for more than 3 sec the UP and DOWN keys.
2. The “OF” message will be displayed and the keyboard will be locked. If a key is pressed more
than 3 sec the “OF” message will be displayed.
5.6 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3 sec the UP and DOWN keys till the “on”message will be
displayed.
6 PARAMETERS
REGULATION
Hy Differential: (0.1 to 25°C; 1 to 45°F) differential for set point. Compressor Cut IN is SET POINT +
differential (Hy). Compressor Cut OUT is when the temperature reaches the set point.
LS Minimum SET POINT: (-55°C to SET; -67°F to SET) sets the minimum value for the set point.
US Maximum SET POINT: (SET to 99°C; SET to 99°F) set the maximum value for set point.
ot First probe calibration: (-9.9 to 9.9°C; -17 to 17°F) allows to adjust possible offset of the first probe.
P2 Evaporator probe presence: n= not present; y= the defrost stops by temperature.
oE Second probe calibration: (-9.9 to 9.9°C; -17 to 17°F) allows to adjust possible offset of the second
probe.
F5 Filter probe enabling: (nu; AL; do) set the field of action of the internal measurement filter. nu=not
used; AL=the filter will always works on all probes; do=the filter will only works on all probes for 30
sec after opening of the door.
od Outputs activation delay at start up: (0 to 99min) this function is enabled at the initial start up of the
instrument and inhibits any output activation for the period of time set in the parameter.
AC Anti-short cycle delay: (0 to 50 min) minimum interval between the compressor stop and the
following restart.
Cy Compressor ON time with faulty probe: (0 to 99min) time during which the compressor is active in
case of faulty thermostat probe. With Cy=0 compressor is always OFF.
Cn Compressor OFF time with faulty probe: (0 to 99min) time during which the compressor is OFF in
case of faulty thermostat probe. With Cn=0 compressor is always active.
DISPLAY
CF Measurement unit: (°C; °F) °C =Celsius; °F =Fahrenheit. WARNING: When the
measurement unit is changed the SET point and the values of the parameters Hy, LS, US, oE,
o1, AU, AL have to be checked and modified if necessary.
rE Resolution (only for °C): (dE; in) dE= decimal between -9.9 and 9.9°C; in= integer.
Ld Default display: (P1; P2) P1= thermostat probe; P2= evaporator probe.
dy Display delay: (0 to 15min) when the temperature increases, the display is updated of 1°C or
1°F after this time.
DEFROST
dE Defrost termination temperature: (-55 to 50°C; -67 to 99°F) if P2=Y it sets the temperature
measured by the evaporator probe, which causes the end of defrost.
id Interval between defrost cycles: (0 to 99min) Determines the time intervals between two
consecutives cycles of defrost.
Md Maximum length for defrost: (0 to 99min, 0 means no defrost) when P2=n, (not evaporator
probe: timed defrost) it sets the defrost duration, when P2 = y (defrost end based on
temperature) it sets the maximum length for defrost.
dF Display during defrost: (rt; it; SP; dF) rt= real temperature; it= start defrost temperature;
SP= SET-POINT; dF= label dF.
ALARMS
AU Maximum temperature alarm: (AL to 99°C; AL to 99°F) when this temperature is reached
the alarm is enabled, after the “Ad” delay time.
AL Minimum temperature alarm: (-55°C to AU; -67°F to AU) when this temperature is reached
the alarm is enabled, after the Ad delay time.
Ad Temperature alarm delay: (0 to 99min) time interval between the detection of an alarm
condition and alarm signalling.
SZ 1598030250 XR02CX RWA GB r1.2 29.08.2013.doc XR02CX 2/2
dA Exclusion of temperature alarm at startup: (0 to 99min) time interval between the detection
of the temperature alarm condition after instrument power on and alarm signalling.
OTHER
d1 Room probe instant value (read only)
d2 Evaporator probe instant value (read only)
rS Real Set Poin value (read only)
Pt Parameter code table (read only)
rL Software release (read only)
7 INSTALLATION AND MOUNTING
Instrument XR02CX shall be mounted on vertical panel, in a
29x71 mm hole, and fixed using the special bracket supplied.
The temperature range allowed for correct operation is 0 to 60°C.
Avoid places subject to strong vibrations, corrosive gases,
excessive dirt or humidity. The same recommendations apply to
probes. Let air circulate by the cooling holes.
8 ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to
2.5mm2. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier
loads use a suitable external relay.
8.1 PROBES
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature. Place the defrost termination probe among the evaporator
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during
defrost, to prevent premature defrost termination.
9 HOW TO USE THE HOT KEY
9.1 HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT
(UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “Hot-key” and push UP key; the "uP" message appears followed
a by flashing “En”
3. Push “SET” key and the “En” will stop flashing.
4. Turn OFF the instrument and then remove the “Hot-key”. After that turn it ON again.
NOTE: the “Er” message is displayed for failed programming. In this case push again o key if you want to
restart the upload again or remove the “Hot-key” to abort the operation.
9.2 HOW TO PROGRAM AN INSTRUMENT USING HOT KEY
(DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key”into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the parameter list of the “Hot-key” is downloaded into the Controller memory, the “do”
message is blinking followed a by flashing “En”.
4. After 10 sec the instrument will restart working with the new parameters.
5. Remove the “Hot-key”.
NOTE: the “Er” message is displayed for failed programming. In this case push again o key if you want to
restart the upload again or remove the “Hot-key” to abort the operation.
10 ALARM SIGNALLING
Mess. Cause Outputs
P1 Room probe failure Compressor output according to Cy e Cn
P2 Evaporator probe failure Defrost end is timed
HA Maximum temperature alarm Outputs unchanged
LA Minimum temperature alarm Outputs unchanged
5.1 ALARM RECOVERY
Probe alarms “P1” and “P2” start some seconds after the fault in the related probe; they automatically
stop some seconds after the probe restarts normal operation. Check connections before replacing the
probe. Temperature alarms “HA” and “LA” automatically stop as soon as the temperature returns to
normal values.
11 TECHNICAL DATA
Housing: self extinguishing ABS
Case: frontal 32x74 mm; depth 60mm
Mounting: panel mounting in a 71x29mm panel cut-out
Protection: IP20
Frontal protection: IP65
Connections: disconnectable terminal block 2.5 mm2wiring and 6.3mm fast-on
Power supply: according to the model ±10%; 230Vac 10%, 50/60Hz, 110Vac 10%, 50/60Hz
Power absorption: 3.5 VA max
Display: 2 digits, red LED, 14.2 mm high; Inputs: 2 NTC
Relay outputs: compressor SPST 8(3) A, 250Vac; 20(8)A 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B
Pollution degree: 2
Software class: A
Rated impulsive voltage: 2500V
Overvoltage Category: II
Operating temperature: 0 to 60°C (32 to 140°F)
Storage temperature: -30 to 85°C (-22 to 185°F)
Relative humidity: 20 to 85% (not condensing)
Measuring and regulation range: NTC -40 to 110°C (-40 to 230°F).
Resolution: 0.1°C or 1°C or 1°F (selectable)
Accuracy (ambient temp. 25°C): ±0.7°C ±1 digit
12 CONNECTIONS
12.1 20A COMPRESSOR RELAY
NOTE: in case of 110Vac model, connect power supply to terminals 6-7.
13 DEFAULT SETTING VALUES
LABEL DESCRIPTION RANGE
REGULATION
Hy Differential 0.1 to 25°C; 1 to 45°F
LS Minimum Set Point -55°C to SET; -67°F to SET
US Maximum Set Point SET to 99°C; SET to 210°F
ot First probe calibration -9.9 to 9.9°C; -17 to 17°F
P2 Second probe presence n; Y
oE Second probe calibration -9.9 to 9.9°C; -17 to 17°F
F5 Filter probe enabling nu; AL; do
od Outputs activation delay at start up 0 to 99 min
AC Anti-short cycle delay 0 to 50 min
Cy Compressor ON time faulty probe 0 to 99 min
Cn Compressor OFF time faulty probe 0 to 99 min
DISPLAY
CF Measurement units °C; °F
rE Resolution (only for °C) dE; in
Ld Default Display P1; P2
dy Display delay 0 to 15 min
DEFROST
dE Defrost termination temperature -50 to 50°C; -58 to 122°F
id Interval between defrost cycles 0 to 99 hours
Md Maximum length for defrost 0 to 99 min.
dF Display during defrost rt; in; dE
ALARMS
AU Maximum temperature alarm ALL to 99°C; ALL to 210°F
AL Minimum temperature alarm -55°C to ALU; -67°F to ALU
Ad Temperature alarm delay 0 to 99 min
dA Exclusion of temperature alarm at
startup 0 to 99 min
OTHER
d1 Room probe display Read Only
d2 Evaporator probe display Read Only
rS Real set point Read Only
Pt Parameter code table Read Only
rL Firmware release Read Only