manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Rinnai
  6. •
  7. Water Heater
  8. •
  9. Rinnai R85i User manual

Rinnai R85i User manual

* For clearances not specified in ANSI Z223.1 / NFPA 54 or CAN/CGA-
B149, please use clearances in accordance with local installation codes
and the requirement of the gas supplier.
** 4 feet for units other than Direct-Vent Appliance.
1
10) Thread the cable through the access hole at the base of the unit and
connect the wires to the controller terminals on the right hand side
bottom of the PCB.
11) Secure the controller cable using the clamp provided.
12) Replace plastic cover over PCB and then replace the front cover of the
Rinnai Water Heater.
Suggested temperatures are:
Kitchen 120°F - 130°F, Shower 98°F - 110°F, Bath fill 102°F - 114°F
These temperatures are suggestions only. You may find higher or lower
temperatures more comfortable. Maintaining lower temperatures helps
save energy. To obtain water temperatures lower than 98°F, simply add
cold water.
Deluxe Controllers are an optional extra. ‘Controller’ and ‘Deluxe’
Controllers can be installed together. Controllers allow temperature
selection only. ‘Deluxe’Controllers have temperature selection, bath fill and
clock functions.
Controllers allow the water temperature to be set from the various
locations where they are installed. The temperature selected will be
available to all outlets. Below are the combination of Controllers that are
offered by Rinnai:
Controllers Combination Pattern
**See controller manual in controller carton box for more infomation detail.
Water Smart / Bath FillTemperature Table
2
□The vent pipe has a negative slope/grade to the outside of three
degrees (3°) or 5/8" per foot of vent pipe.If the vent pipe is sloped back
towards the appliance as some code may require, provisions SHALL
be made to collect all condensation to drain off and away from the
appliance to a proper drain source.See local code for details.

□You have no more than three bends in your vent system and the length
does not exceed Rinnai specifications.
Thesettingsbelowarefactorydefaultsettings.Pleaseensurethemodel
numberandgastypeoftheunityouhave,matchesthemodelnumber
and gas type listed below; before settings any switches. If you need
assistance,contactRinnaiat(800)621-9419beforeproceeding.
WARNING
In appropriate Dip Switch setting can damage the Rinnai water heater and
may void the warranty of this unit
9. Set the Infinity to‘Forced Low’combustion by setting No.7 dip switch of
the (SW1) set of dip switches to‘ON’.(Fig.3).
10. Check the burner test point pressure.
11. Remove rubber access plug and adjust the regulator screw on the
modulating valve (Fig.4) as required inTable 1.Replace rubber access
plug.
12. Set the RinnaiWater Heater to ‘Forced High’combustion by setting
both No.7 and No. 8 dip switches of the bottom (SW1) set to‘ON’.
(Fig.5). Ensure maximum water flow !
13. Check the burner test point pressure.
14. Adjust the high pressure Potentiometer (POT) on the Printed Circuit
Board (PCB) as required to the pressure shown in Table 1.
IMPORTANT: Set dip switches 7 and 8 on the bottom (SW1) to‘OFF’
to return the appliance to 'Normal' combustion. (Fig.6).
15. Close hot water tap.
16.Turn ‘OFF’the gas supply and 120V power supply.
17. Remove pressure gauge & replacing sealing screw.
18.Turn ‘ON’the gas supply and 120V power supply.
19. Operate unit and check for gas leaks at test point.
20. Replace the front cover of the appliance.
34
Top of Heater
Back of Heater
Front of Heater
Sides of Heater
Floor
Vent/Air Intake
6 inches
0 inch
6 inches
2 inches
12 inches
0 inch
INSTALLER'S INSTALLATION INSTRUCTIONS
Remote Controllers- General
The remote controls for the Rinnai Water Heater allow the customer to
control the functions of the water heater and to diagnose certain fault
conditions.
Before installing the remote controllers, determine the most convenient
location(s).
When deciding on the best location for the remote controllers, please
consider the
following items:
1) Place the controllers out of reach of small children.
2) Avoid locations where the controller(s) will become hot.(over the stove,
near the oven or a radiant heater.
3) Avoid direct sunlight.(The digital monitor can be difficult to read in
direct sunlight)
4) Avoid areas where the remote can be splashed with cooking water, oil
or sauce.
5) The remote controller cables carry low voltage, 12VDC digital.
The controllers can be wired in series or in parallel depending on the
distance from the Rinnai Water Heater to the controllers.
Every installation is different
REMOTE CONTROLLER OPERATION
GENERAL CONTROLLER INFORMATION
DIAGNOSTIC USE OF CONTROLLER
1. To Display Maintenance Codes: Press ‘On/Off’ button. To sequence
through stored maintenance codes, press‘On/Off’ followed by the
thermostat button.
2. To DisplayWater Flow through water heater: Press thermostat
button, hold for 2 seconds and simultaneously press‘On/Off’button.
3. To display OutletWaterTemperature: Press ‘thermostat button’,
hold for 2 seconds and simultaneously press‘On/Off’ button.
TO CHANGETEMPERATURES FROM °F to °C
1. Press and hold‘On/Off’button for 5 seconds while water heater is OFF.
2.To change back from °C to °F, please repeat step 1.
MUTE
To eliminate the beeping sound, press and hold and button
simultaneously until a‘beep’is heard (approximately 5 seconds).
Temperature controllers allows precise temperature control by the user.
When used correctly, the hot water unit will deliver the selected
temperature, even when the water flow is varied, or more than one tap is in
use. Each Temperature Controller can be individually programmed,
however the water heater unit can only deliver one set temperature at any
time.The available temperatures (°F) are as follows:
TemperatureTable by Models
□▲
□▲
□▼
□▲ □▼
GAS PRESSURE SETTING AND DIAGNOSTICS
INFORMATION
NOTE:For additional installation and commissioning
information refer to Operation / Installation Manual
APPLIANCE OPERATING PRESSURES
COMMISSIONING
With all gas appliances in operation at maximum gas rate, the flowing
inlet pressure at the incoming test point on the Rinnai Water Heater
should read 6"W.C. - 10.5"W.C.on Natural Gas and 10"W.C. - 13.5"W.C.
on Propane Gas. If the pressure is lower, the gas supply is inadequate
and the appliance unit will not operate to specification. Check gas meter,
regulator and pipework for correct operation/sizing and rectify as
required.
GAS PRESSURE SETTING
(Ensure gas pressure check under Commissioning above has been
completed first !)
The regulator is electronically controlled and factory pre-set. Under
normal circumstances it does not require adjustment during
installation. Make adjustments only if the unit is not operating
correctly and all other possible causes for incorrect operation have
been eliminated.
1.Turn ‘OFF’the gas supply.
2.Turn ‘OFF’120V power supply.
3. Remove the front cover from the appliance.
4. Check gas type switches (Fig.1) are in the correct position
(dip switch 1 of SW2‘ON’= NG,‘OFF’= LPG)
Note:‘ON’towards front,‘OFF’towards rear.
5. Attach pressure gauge to burner test point, located on the gas control.
(Fig.2).
6.Turn ‘ON’the gas supply.
7.Turn ‘ON’120V power supply.
8. If remote controllers are fitted, turn the unit‘ON’at the kitchen controller,
select the maximum delivery temperature and open all available hot
water taps full including the shower.
(CAUTION: Ensure building occupants do not have access to hot water
outlets during this procedure).
THIS APPLIANCE MUST BE INSTALLED, SERVICED
AND REMOVED BY ANAUTHORISED PERSON
DURING PRESSURE TESTING OF THE CONSUMER PIPING
ENSURE GAS COCK SITUATED BEFORE UNIT IS SHUT-OFF.
FAILURE TO DO SO MAY RESULT IN SERIOUS
DAMAGE TO THE APPLIANCEAND POSSIBLE INJURY.
WARNING
Nat.G Prop.G Nat.G Prop.G Nat.G Prop.G
REU-V2532FFUD
REU-V2532FFUCD
REU-V2520FFUD
REU-V2520FFUCD
150PSI
6"W.C.
10.5"W.C. 10"W.C.
13.5"W.C. 0.77"W.C. 0.93"W.C.
3.7"W.C. 4.2"W.C.
Table 1.
Water
Inlet Min.
Gas Inlet
Min./ Max. Forced Low Forced High
No code or
blank
display Nothing happens when water
flows through water heater.
Clean inlet filter screen and ensure you have at least the
minimum flow rate required to fire unit. Check for pipe dope
inside water flow control turbine.
On new installations, ensure hot and cold water lines are not
crossed.
Check for bleed over.Isolate unit from building by turning off
hot water line to building.Then open your pressure relief
valve, if unit fires, thereís a bleed over in your plumbing.
If a circulating system is in use, it must be isolated also.
Remote control does not light up but you have 12VDC at the
terminals for controls:
Disconnect water flow control motor, then turn on hot water,
if unit fires replace water flow control assembly.
Code
Displayed
00
Fault
When checking maintenance code history,
“00” is substituted for“LC” Build up of lime scale in heat exchanger - needs to be
flushed.
03
Power interruption during Water Smart/Bath Fill
(Hot water will not flow when power returns)
Turn off all hot water taps.Press ON/OFF twice.
33 Heat exchanger outlet water temperature
faulty Check H.E.outlet sensor or wiring. Measure resistance of
sensor.Clean sensor of scale build-up
34
52 Modulating Solenoid Valve signal abnormal Check gas control wiring harness and measure resistance of
valve coil in ohms.
61 Combustion Fan Failure Combustion fan or wiring harness faulty. Make sure
motor/fan turns freely. Measure resistance of motor winding.
71 SV0, SV1, SV2 or SV3
Solenoid Valve Circuit Faulty Check all gas solenoid wiring harness and connections.
Measure resistance of each solenoid valve coil.
LC Scale build-up in Heat Exchanger Build up of lime scale in heat exchanger ñ needs to be
flushed.
02 No burner operation during freeze
protection mode
Verify that gas supply is turned on to the water heater and
valve at meter or tank is open.Verify proper gas type and
supply pressure. Bleed air from gas line.Verify all ignition
component/wires are connected.
10 Air intake supply or exhaust blockage Check for a restriction in exhaust or intake vent, verify proper
dip switch settings.Ensure only Rinnai approved venting
components are used.
14 Thermal Fuse Ensure high and low fire manifold gas pressures are properly
set.Verify dip switch settings are correct.Measure
resistance in ohms of safety circuit.
11 No Ignition Verify that gas supply is turned on to the water heater and at
meter or tank.Verify proper gas type and supply pressure.
Bleed air from gas line.Verify all ignition component/wires
are connected.
32 Outlet water temperature sensor reading
out of expected range Check outlet temperature sensor or wiring for damage.
Measure resistance of sensor.Clean sensor of scale build -
up.
65 Water Flow Servo Faulty
(Does not stop flow properly) Water Flow Servo or wiring faulty. Check Water Flow Servo
wiring harness conection.
Measure resistance of Water Flow Servo wiring.
16 Over Temperature Warning Verify dip switch settings, check manifold pressure and verify
gas type for water heater. Check for clogged heat
exchanger.Check for low water flow in a circulating system
causing short-cycling.
72 Flame Sensing Device Faulty Check flame rod and wiring harness connections. Measure
micro amp output of sensor circuit with flame present. Clean
flame sensor of any build-up.Check for debris in burner
chamber that may block flame from sensor.
12 Flame Failure, poor ground connection Make sure gas is turned on at the water heater; check for
obstructions in exhaust vent.Ensure only Rinnai approved
venting components are used.Verify proper grounding.
Check for debris or moisture in burner area.
Items to Inspect
INSTALLER'S INSTALLATION INSTRUCTIONS
-Warnings-
This manual must be followed exactly.
The Rinnai Water Heater is not suitable for use in pool or spa applications.
Installer must install a Pressure relief valve. Pipe pressure relief discharge to
a drain or outside environment.
Maintain proper space around the unit for proper servicing and operation.
Minimum clearances from combustible materials are listed below.
RECOMMENDEDVENT/AIR INTAKE TERMINAL POSITION
Terminals should be so positioned as to avoid products of combustion
entering openings into buildings or other flues or vents.
REF U.S. Installations Candadian
Installations
DESCRIPTION
K 3 feet 6 feetClearance to a forced air inlet into a building
N 2 feet 2 feetVent FIue from wall (FIat or Pitched Roof)
P 1 foot 1 footClearance between two vertical flue on the same pIane
Q 1 foot 1 footHorizontal between two terminals on the same wall
S 4 feet 4 feetClearance from terminal facing a terminal
R 5 feet 5 feet
Clearance between two Vertical flue on pitched roof above
each other
O 5 feet 5 feet
Vertical between two terminals on the same wall above each
other
M3 feet 3 feetClearance under deck, veranda, porch, or balcony
(open on 3 sides)
L * 7 feet
Clearance above paved sidewalk or paved driveway located on
public property
J **1 foot 1 foot
Clearance to nonmechanical air supply inlet to building or the
combustion air inlet to any other appliance
INSTALLER'S INSTALLATION INSTRUCTIONS
Locating the vent terminal
REF U.S. Installations Canadian
Installations
DESCRIPTION
A 1 foot 1 footClearance above grade, veranda, porch, deck, or balcony
B **1 foot 1 foot
**
Clearance to window or door that may be opened
C Clearance to permanently closed window
D 3 feet 3 feetVertical clearance to ventilated soffit, eaves or overhang
E 3 feet 3 feetClearance to unventilated soffit, eaves or overhang
F 1 foot 1 footClearance to outside corner
G 2 feet 2 feetCIearance to inside corner
I * 3 feetClearance to service regulator vent outlet
H*
3 feet within a height
15 feet.above the
meter/reguIator
assembly
Clearance to each side of center line extended above
meter/regulator assembly
INSTALLER'S INSTALLATION INSTRUCTIONS
Remote Controllers - Installation
1) Determine a suitable location for the
controller.
2) Make three holes on the wall as
shown.
3) Run the cable between the controller
and the Rinnai Water Heater or the
controller and the other controller.
4) Remove the face plate from the remote controller.
5) Connect the cable to the remote controller.
6) Mount the controller to the wall using the holes drilled in step 2.
7) Disconnect the power from the Rinnai Water Heater.
8) Remove the cover of the Rinnai Water Heater.
9) Remove the plastic cover from the PCB and electrical connections.
DO NOT ATTEMPT TO CONNECT THE REMOTE CONTROLLERS WITH
THE POWER ON, THERE'S 120 VOLT POTENTIAL, NEXT TO THE
REMOTE CONTROLLER CONNECTIONS INSIDE THE UNIT. All service
and wiring should be performed by a certified installer.
111
32"
35
16"
model
REU-V2532FFUD
REU-V2520FFUD(°F)
REU-V2520FFUCD(°F)
REU-V2532FFUCD(°F) 98
98
100
100
102
102
104
104
106
106
108
108
110
110
115
115
120
120
120
125
125
125
130
130
130
135
135
135
140
140
140
150
150
160
160
185
Approx.
temperature(°C) 37 38 39 40 41 42 43 46 49 52 54 57 60 66 71 85
185
temperature
water smart/
bath fill temperature (°F)
Approx.
temperature (°C) 49
120
48
118
47
116
46
114
44
112
43
110
42
108
41
106
40
104
39
102
38
100
37
98
temperature
1+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
MC-91-1US
MC-91-1US
MC-91-1US
MC-91-1US
MC-91-1US
MC-91-1US MC-91-1US BC-100V MC-100V
MC-100V
MC-91-1US **MC-91-1US
MC-91-1US
BC-100V
MC-91-1US
MC-91-1US
MC-91-1US2
3
4
5
6
Remote and Deluxe Controllers
(M)Water Flow Control Device Servo or Geared Motor:
NOTE:The grey wire listed above turns to black at B connector on the PCB,the orange wire turns to red.
(QS)Water Flow Sensor:
By-pass Flow Control: (REU-V2532FFU/FFUC ONLY)
(IG) Ignition System:
(FM) Combustion Fan Motor:
Set your meter to the hertz scale. Reading across the red and yellow wires at terminals 2 and 3
you should read between 60 and 350 hertz.
Thermal Fuse:
Overheat Switch:
Flame Rod:
Place one lead of your meter to the flame rod and the other to earth or ground. With the unit
running you should read between 5 ~ 150 VAC. Set your meter to the µamp scale, series your
meter in line with the flame rod. You should read 1µor greater for proper flame circuit. In the
event of low flame circuit remove the flame rod and check for carbon and/or damage.
Heat Exchanger, AirTemperature, and Outgoing WaterTemperature Thermistors:
Check all thermistors by inserting meter leads into each end of the thermistor plug. Set your
meter to the 20K scale and read resistance.You should be able to apply heat to the thermistor
bulb and see the resistance decrease.Then apply some ice to the thermistor and the resistance
should increase. See below for examples of temperatures and resistance reading at those
temperatures.
Example: 59°F = 11.4 ~ 14K
86°F = 6.4 ~ 7.8K
113°F = 3.6 ~ 4.5K
140°F = 2.2 ~ 2.7K
221°F = 0.6 ~ 0.8K
OutgoingWaterThermistor:
Heat ExchangerTemperatureThermistor:
Surge Protector:
With the power off you can check the continuity through the surge protector. Place one meter
lead on the top pin #1 of the surge protector and pin #2 on the bottom of the surge protector.
Then check across top pin #3 and bottom pin #1, if you read continuity across these two points
the surge protector is good. If you do not get continuity, replace the surge protector.
Remote Controls:
Frost Protection:
This unit has four frost protection heaters mounted at different points inside the unit, to protect
the water heater from freeze ups. There are two heaters located on the outlet hot water line
next to the thermistor.
Using a voltage meter set on the 200 ohm scale, you should have a resistance reading of 26 ~
30 ohms through each of these heaters. The heater located on the heat exchanger piping
should have a resistance reading of 81 ~ 86 ohms and the one located in the water flow sensor
valve has a resistance reading of 16 ~ 19 ohms.Voltage throughout this circuit should be 120
VAC.
Amp Fuses:
This unit has two inline (3) amp glass fuses. Remove the fuse and check continuity through it.If
you have Continuity through the fuse, it is good. If you can not read continuity, the fuse is blown
and must be replaced.
SERVICEMAN'STROUBLESHOOTING INFORMATION
for the RINNAIWATER HEATERS
IMPORTANT SAFETY NOTES:
There are a number of (live) tests that are required when fault finding this
product. Extreme care should be used at all times to avoid contact with
energized components inside the water heater. Only trained and qualified
service agencies should attempt to repair this product. Remember,
before checking for resistance readings, you should disconnect the power
source to the unit and isolate the item to be checked from the circuit (unplug it).
(TR)Transformer:
(SV1, SV2,SV3 and POV) Gas valve and Modulating solenoids: (Set meter above 2K)
Wire color
Black ~ White
Blue ~ Brown
Voltage
90 ~ 100 VAC
108 ~ 132 VAC
Resistance
51 ~ 63 ohms
51 ~ 63 ohms
Connector #
F9
F7
Pin #'s
1 ~ 2
1 ~ 3
Red ~ Black
White ~ Black
Yellow ~ Black
6 ~ 45 VDC
5 ~ 10 VDC
11 ~ 13 VDC
N/A
9.2K ~ 9.4K
3.5K ~ 3.9K
A1
A1
A1
1 ~ 2
2 ~ 4
2 ~ 3
(Main) Pink ~ Black
(SV1) Black ~Yellow
(SV2) Black ~ Blue
80 ~ 100 VDC
80 ~ 100 VDC
80 ~ 100 VDC
1.7K ~ 2K ohms
1.7K ~ 2K ohms
1.7K ~ 2K ohms
E1
E2
E3
1 ~ 2
2 ~ 3
2 ~ 4
(SV3) Black ~ Brown 80 ~ 100 VDC 1.7K ~ 2K ohms E4 2 ~ 5
(POV) Pink ~ Pink 2 ~ 15 VDC 67 ~ 81 ohms C2 3 ~ 4
Grey ~ Grey 90 ~ 100 VAC N/A A1 1 ~ 2
Red ~ Red 12 VDC Below 1 ohm B ~ C B6 ~ C1
Red ~ Red 12 VDC Below 1 ohm B ~ C B6 ~ C1
White ~ White N/A See example above B B3 ~ B4
White ~ White N/A See example above B B3 ~ B12
Terminals D1, D210 ~ 13 VDC digital 1.5K ~ 1.9K ohms H 1 ~ 3
Black ~ White
Blue ~ Brown 108 ~ 132 VAC
108 ~ 132 VAC N/A
N/A
Surge Protector D1
Surge Protector D2
1 ~ 3
1 ~ 2
Brown ~ White
Orange ~ White
Yellow ~ White
Red ~ White/ Ground
2 ~ 6 VDC
Unit in operating
mode
15 ~ 35K
G4 ~ G5
G2 ~ G5 4 ~ 5
2 ~ 5
G1 ~ G5
G3 ~ G5 1 ~ 5
3 ~ 5
Red ~ Blue
Grey ~ Brown
Grey ~Yellow
11 ~ 13 VDC
4 ~ 6 VDC
N / A
22 ~ 26 ohms
N / A
N / A
B2
B2
B2
9 ~ 10
5 ~ 7
Black ~ Red
Yellow ~ Black 11 ~ 13VDC
4 ~ 7 VDC 5.5K ~ 6.2K
1 meg ~ 1.4 meg B4
B4 5 ~ 6
1 ~ 5
5 ~ 8
Grey ~ Orange 11 ~ 14VDC N / A B2 5 ~ 6
REU-V2532FFUD-US
REU-V2532FFUCD-US
REU-V2520FFUD-US
REU-V2520FFUCD-US
U245-3245(00)
In Use Indicator
Indicates that a hot water tap
is open and that control of the
temperature has been taken at
another controller.
Digital Monitor
Indicates the selected
water temperature.
Error messages flash
in the event of a failure.
Thermostat
Increases or decreases
the desired water
temperature.
Priority Indicator
Indicates whether this
controller has priority
control over the water
temperature
Priority
Pressing takes control
of the water temperature
by this controller.
ON/OFF
Used to switch the
water heater on and off
Attention Installer! - HaveYou Checked Everything?
For full details - Always Refer to Rinnai Installation Instructions
□HOT (outlet) and COLD (inlet) water lines are not crossed to the unit
and are leak free.

□You have installed isolating valves, unions, and drain down vales on the
cold water inlet line and hot water outlet lines.(These components are
used for servicing and/or removing the appliance quickly).

□COLD water inlet filter was cleaned after installation.(The filter MUST
be cleaned after installing the unit)

□A pressure relief valve is installed and is rated for 200,000 Btu's at 150
PSI per local code.

□120 VOLTS A.C. is connected to the unit, it is properly GROUNDED
and circuit is turned on.

□Gas supply system is properly sized. All gas meters, regulators, gas
line types, tanks, etc.have a BTU value.Please confirm that all
components meet the gas requirements at this location.Verify the
system is functioning correctly by connecting your manometer to the
gas pressure test port on the Rinnai unit. Operate all gas appliances in
the facility.The inlet gas pressure must not drop below that listed in the
ownerís manual specification sheet or appliance rating plate.
□Proper gas type and pressure is supplied to the unit. (See owner's
manual for correct inlet gas pressures in the specification section.
Normal inlet gas pressures are 7" to 10" of water column for natural
gas, and 11" to 13" of water column for propane gas).
□Gas supply pipe is purged of foreign material before connection.

□Proper model controllers are used, connected and functioning.

□Instructed the customer how to operate the Controllers.

□Verify proper clearances around the unit and all vents and air intakes.
(See owner's manual for all clearance requirements.)

□Explained to the customer to never store anything around the vent
terminals or block the air and/or exhaust ports to the unit.

For Internal models only

□Ensure you used the proper venting materials for the unit you have
installed.
RinnaiWater Heaters
Dip Switch Default Settings
Fig. 3
Fig. 5 Fig. 6
ON
ON
SW1
ON
SW1
Fig. 2Fig. 1
Fig. 4
Regulator adjustment
screw access plug
Burner test point
GAS
COLD water inlet filter
inlet GAS test port
WATER INLET
(COLD)
WATER OUTLET
(HOT)
CLAMP
REMOTE
CONTROL CABLE
REMOTE CONTROL
CONNECTION TERMINALS
Water Smart / Bath Fill temperature cannot exceed 120°F for the following
commercial models with no by-pass :REU-V2520FFUCD
◆REU−V2532FFUD
◆REU−V2532FFUCD
NAT.GLPG LPG NAT.G NAT.GLPG LPG NAT.G
◆REU−V2520FFUD
◆REU−V2520FFUCD
Residential Units Commercial Units
Dip Switch Settings Dip Switch Settings
Residential Units
Dip Switch Settings
Commercial Units
Dip Switch Settings
1
O
F
F
2
3
4
5
6
7
8
ON
→
O
F
F
2
3
4
1
→
ON
1
O
F
F
2
3
4
5
6
7
8
→
ON
O
F
F
2
3
4
1
→
ON
1
O
F
F
2
3
4
5
6
7
8
→
ON
O
F
F
2
3
4
1
→
ON
1
O
F
F
2
3
4
5
6
7
8
→
ON
O
F
F
2
3
4
1
→
ON
1
O
F
F
2
3
4
5
6
7
8
ON
→
O
F
F
2
3
4
1
→
ON
1
O
F
F
2
3
4
5
6
7
8
→
ON
O
F
F
2
3
4
1
→
ON
1
O
F
F
2
3
4
5
6
7
8
→
ON
O
F
F
2
3
4
1
→
ON
1
O
F
F
2
3
4
5
6
7
8
→
ON
O
F
F
2
3
4
1
→
ON
Sensor or wiring faulty.Verify fan blade is mounted securely
to shaft. Check for airflow restrictions in venting system.
(Indoor Units Only) Combustion air sensor
reading out of expected range
OFF/ON
Vent/air intake
piping length
See Owner's manual for more in informd detail.
12345678
070 00012 31445 7
PARTS LIST
Part Number
U245-3150-1
U245-3150-2
U242-111-11
U242-111-9
CF79-41020-A
U245-3160
U245-107
U245-3110-3
U245-3110-4
U245-3118-2
U245-3118-1
MC-91-1US-S-FL
U245-3134
U245-3121
U245-3122
AH59-772
AU169-126
AH59-772
C36E-41-S
AU39-965
CU195-1866
H73-110
CH51-209
H73-112
BH51-218
B3A7-1
CH51-221
H73-115
U245-200-A
U245-200-B
AU155-207-2
H73-214
C10D-5
U245-260
U245-261
H73-120
AH41-216
AH66-398
AH66-393
U245-262
U242-312
AU161-665-C
U245-550
U245-555
BH29-606
AU183-562
U245-560
Quantity
V2532FFUD/FFUCD
1
1
1
1
1
1
1
1
1
1
2
1
1
2
4
1
1
1
1
2
1
1
1
1
1
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V2520FFUD/FFUCD
1
1
1
1
1
1
1
1
1
1
2
1
1
2
4
1
1
1
1
2
1
1
1
1
1
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V2520FFUD/FFUCD
1
1
1
1
1
1
1
1
1
2
1
-
1
1
-
1
1
-
-
1
1
1
1
1
1
1
1
1
-
1
1
1
1
1
1
1
1
1
2
1
5
1
1
1
1
2
1
1
V2520FFUD/FFUCD
1
1
1
1
1
1
1
1
1
1
1
8
4
4
3
1
2
2
1
1
1
2
1
1
1
2
1
1
1
1
1
1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Description
Casing Assembly (Residential model)
Casing Assembly (Commercial model)
Wall Fitting Bracket-8 (Residential model)
Wall Fitting Bracket-9 (Commercial model)
Rubber Bushing
Connection Reinforcement Panel
Heat Protection Plate
Front Panel (Residential model)
Front Panel (commercial model)
Front Panel Packing
Front Panel Packing Side
Remote Controller
Remote Controller Support Plate
Side Panel
Side Panel Cap
Quick Controller Connection
Cable Seal Packing
Connection Support Clip
Gas Control Assembly
Screw
Gas Connection (3/4""NPT)
Burner Unit Assembly
Burner Case Front
Burner Case Bottom Panel
Packing
Lean and Rich
Bunsen Burner Assembly
Burner Case Back Panel
Damper
Manifold Assembly -A (LPG)
Manifold Assembly -B (Nat.G)
Paking of Combustion Chamber
Lower Packing of Combustion Chamber
Screw
Combustion Chamber Front Plate Assembly
Combustion Chamber Front Plate
Electrode
Flame Rod
Electrode Packing
Electrode Holder
Upper Packing of Combustion Chamber
Tube Joint
Pressure Tube
Blower Motor All Assembly
Fan casing Assembly
Fan Connecting Bracket
Fan Connecting Packing
Blower Motor
Number
001
001
002
002
003
004
005
006
006
007
008
009
010
011
012
013
014
015
100
101
102
103
104
105
106
107
108
109
110
110
111
112
113
114
115
116
117
118
119
120
121
122
125
126
127
128
129
Quantity
V2532FFUD/FFUCD
1
1
1
1
1
1
1
1
1
2
1
1
-
1
1
-
1
1
2
-
1
1
1
1
1
1
1
1
1
-
1
1
1
1
1
1
1
1
1
1
5
1
1
1
1
2
1
1
Part Number
U245-558
U245-566
U245-255
U245-400
U245-408
U245-409
U245-567
U245-410
U245-434
U245-435
U245-419
U245-690
U245-2240
H73-501-2
M8E-15
M8E-14
M8D1-15
M6J-1-3
AH69-310
AU195-321
H73-512
H98-511
H98-510
U245-865-3
AU162-1876
AU103-413
AU142-444
H98-510-S
U245-500
U245-2260
BBF9-630
U245-774
BU168-707
ET-281
U245-257
El-189
BH38-710-240
AU206-218
BH45-650
CP-90172
U217-676
U242-511
U245-620
U245-621
U245-622
CF29-742
AU111-653
AU100-721
Number
130
131
132
135
136
137
138
139
140
141
142
145
145
400
401
401
402
403
404
404
405
406
407
408
409
410
411
412
700
700
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
717
718
Description
Bell Mouth
Bellows Connecting Bracket/Intake Duct
Combustion Chamber Bracket
Air Inlet Box Assembly
Bellows Connecting Bracket/Fan
Bellows
Bellows Clamping Ring
Air Inlet Box Assembly
Exhaust Bracket
Exhaust Bracket Holder
Air Inlet Box Cover
Heat Exchanger Complete Assembly
Heat Exchanger Complete Assembly
Water Inlet (3/4""NPT)
Water Flow Servo & Sensor Assembly
Water Flow Servo & Sensor Assembly
Rectifier
By-pass Servo Assembly
Stop Bracket
Stop Bracket
Plug Band
Water Filter Assembly
Filter Plug
Hot Water Outlet (3/4""NPT)
Stop Bracket
Plug Band Small
Drain Valve
Water Filter All Assembly
PCB
PCB
Surge Protector
PCB Cover-Side
PCB Cover-Front
Transformer Assembly
PCB Bracket
Ignitor
High Tension Cord
Electrode Sleeve
Thermistor
Thermistor Clip Large
Thermal Fuse Clip
Frost Sensing Switch
120V Anti-Frost Heater Assembly
Heater Connecting Harness
120V Valve Heater Assembly
Anti-Frost Heater Clip
Anti-Frost Heater Clip A
Anti-Frost Heater Clip
Part Number
BH50-730-2
BU195-1630
U245-601
U245-602
U245-603-6
U245-603-9
U245-3190
BU129-821-2
U245-3173
U242-780
ZIHD0510UK
CP-30580
CF83-41430
CP-21478-412
U217-449
ZAA0408UK
M10B-2-4
M10B-2-3
M10B-13-4
M10B-2-18
M10B-2-16
M10B-2-14
M10B-2-7
M10B-1-24
C36E1-6
U245-2602
PWB-261
BU195-1865
MC-91-1US
MC-100V-1US
BC-100V-1US
50710327
50223098B
224064
184118
224069
146141
50171948
50171960
50171953
224051
224052
224053
224063
224050
169044
Quantity
V2532FFUD/FFUCD
1
1
1
1
1
1
1
1
1
1
1
8
4
4
3
1
3
2
1
1
2
2
2
1
1
2
1
1
1
1
1
1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Description
Inlet Air Thermistor
Fuse Harness
100V Harness
Solenoid Valve Harness
Sensor Harness
Sensor Harness
Thermal Fuse Harness
Mold-Type Over Heat Switch
Remote Controller Harness
Power Surprise Cable
Remote Controller Cable
Screw
Screw
Washer
Screw
Screw
Screw
O-ring
O-ring
O-ring
O-ring
O-ring
O-ring
O-ring
O-ring
Packing
Owner's Manual
Package Spec Sheet
Manual 3/4"" gas control valve
Remote Controller (include)
Deluxe Controller (optional)
Deluxe Bathroom Controller (optional)
Horizontal Discharge Adapter
Wall Discharge Terminal
(for wall thicknesses from 4"" to 20"")
Vertical Discharge Adapter
Roof Discharge Terminal
Condensate Collector
Roof Flashing - Flat Roof
Roof Flashing - 1/12 to 6/12 Pitch
Roof Flashing - 6/12 to 12/12 Pitch
Roof Flashing - 12/12 to 16/12 Pitch
10"" Pipe Extension
19.5"" Pipe Extension
39"" Pipe Extension
90 Degree Vent Pipe Elbow
45 Degree Vent Pipe Elbow
Vent Pipe Clamp
Number
719
721
722
723
724
724
725
726
727
728
729
800
801
802
803
804
805
810
811
812
813
814
815
816
817
818
888
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
801 802
012
011
007
005
009
010
001  002
800
003
006
800
004
008
006
MC-91-1US(include)
MC-100V-1US(optional)
BC-100V-1US(optional)
131
116
118
803 110
115
708
707
113 812
120
117
105 108 121
122
705
706
125
811 719
103
139
141
716
710135
709
810
138
132
726
718
717
136
712
137
142 140
141
143
104
106
112
111 109
107
119
130
126
128 127
129
711 
100
401
101818
818
701
727
813
403
815
815
704
817
402
813
406
407
412
013
014 015
102
101
400
405814
700
805
804
814
409
709 810 715 408 410 816 411
702
703
404
805
725
724
709
719
709
726
713
712
715
715
727
723
722
729
727
728
721
714
724
EXPLODEDVIEW - CABINET EXPLODEDVIEW - INTERNALS
EXPLODEDVIEW - ELECTRICALEXPLODEDVIEW - INTERNALS

Other Rinnai Water Heater manuals

Rinnai Infinity EF24 User manual

Rinnai

Rinnai Infinity EF24 User manual

Rinnai RH180 User manual

Rinnai

Rinnai RH180 User manual

Rinnai REU-VA3237FFU Specification sheet

Rinnai

Rinnai REU-VA3237FFU Specification sheet

Rinnai C42e User manual

Rinnai

Rinnai C42e User manual

Rinnai QRESS80L336 User manual

Rinnai

Rinnai QRESS80L336 User manual

Rinnai PEARL 350 User manual

Rinnai

Rinnai PEARL 350 User manual

Rinnai Ai 350 Guide

Rinnai

Rinnai Ai 350 Guide

Rinnai HJ Cooper User manual

Rinnai

Rinnai HJ Cooper User manual

Rinnai HOTFLO EHFA Series User manual

Rinnai

Rinnai HOTFLO EHFA Series User manual

Rinnai Infinity XR16 User manual

Rinnai

Rinnai Infinity XR16 User manual

Rinnai INFINITY REU-3203W User manual

Rinnai

Rinnai INFINITY REU-3203W User manual

Rinnai RH180 Specification sheet

Rinnai

Rinnai RH180 Specification sheet

Rinnai c199i User manual

Rinnai

Rinnai c199i User manual

Rinnai Sensei RU130i User manual

Rinnai

Rinnai Sensei RU130i User manual

Rinnai INFINITY 32 User manual

Rinnai

Rinnai INFINITY 32 User manual

Rinnai Circ-Logic RU98i User manual

Rinnai

Rinnai Circ-Logic RU98i User manual

Rinnai REU-V3237WC User manual

Rinnai

Rinnai REU-V3237WC User manual

Rinnai RES-EB015 User manual

Rinnai

Rinnai RES-EB015 User manual

Rinnai Demand Duo 80 User manual

Rinnai

Rinnai Demand Duo 80 User manual

Rinnai HD210E User manual

Rinnai

Rinnai HD210E User manual

Rinnai C53i User manual

Rinnai

Rinnai C53i User manual

Rinnai Infinity XR26ia User manual

Rinnai

Rinnai Infinity XR26ia User manual

Rinnai R50LSI User manual

Rinnai

Rinnai R50LSI User manual

Rinnai REU-1110FFU-E User manual

Rinnai

Rinnai REU-1110FFU-E User manual

Popular Water Heater manuals by other brands

Heatstore HS65VT-Eco Installation instructions manual

Heatstore

Heatstore HS65VT-Eco Installation instructions manual

TTulpe Outdoor HD-6 Instructions for use, installation and maintenance

TTulpe

TTulpe Outdoor HD-6 Instructions for use, installation and maintenance

Quick B3 user manual

Quick

Quick B3 user manual

PVI Industries 750P900A-TPGO Specifications

PVI Industries

PVI Industries 750P900A-TPGO Specifications

CTC Union CTC Accumulator Tank 1. 500/50 Installation and maintenance manual

CTC Union

CTC Union CTC Accumulator Tank 1. 500/50 Installation and maintenance manual

TESY GCV9SL 1204720 C21 TSRCP Instructions for use and maintenance

TESY

TESY GCV9SL 1204720 C21 TSRCP Instructions for use and maintenance

Quantum IOT Series Installation and user instructions

Quantum

Quantum IOT Series Installation and user instructions

STIEBEL ELTRON DHC-E 12 Operating and installation

STIEBEL ELTRON

STIEBEL ELTRON DHC-E 12 Operating and installation

Leslie E-1500L INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS PARTS LIST

Leslie

Leslie E-1500L INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS PARTS LIST

Webasto thermo top evo Installation documentation

Webasto

Webasto thermo top evo Installation documentation

Benchmark Green Storage WB Series Installation & maintenance instructions

Benchmark

Benchmark Green Storage WB Series Installation & maintenance instructions

Zip Water InLine DCX Next Installation instructions & user manual

Zip Water

Zip Water InLine DCX Next Installation instructions & user manual

WIKORA WBO 405 UNO Installation manual operating instructions

WIKORA

WIKORA WBO 405 UNO Installation manual operating instructions

Bradford White 238-45917-OON Installation and operating instruction manual

Bradford White

Bradford White 238-45917-OON Installation and operating instruction manual

Kenmore Elite 153.331010 Use & care guide

Kenmore

Kenmore Elite 153.331010 Use & care guide

VEVOR WT-0240 user manual

VEVOR

VEVOR WT-0240 user manual

Aqua-Hot 375-LP owner's manual

Aqua-Hot

Aqua-Hot 375-LP owner's manual

Bradford White ASME Operating instructions manual

Bradford White

Bradford White ASME Operating instructions manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.