Rotex HPU ground User manual

Installation manual
ROTEX HPU ground English
Installation manual
ROTEX HPU ground
RGSQH10S18AA9W

3P351751-2
CE - DECLARATION-OF-CONFORMITY CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - IZJAVA-O-USKLAĐENOSTI CE - IZJAVA O SKLADNOSTI CE - ATITIKTIES-DEKLARACIJA
CE - KONFORMITÄTSERKLÄRUNG CE - DICHIARAZIONE-DI-CONFORMITA CE - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ CE - ILMOITUS-YHDENMUKAISUUDESTA CE - MEGFELELŐSÉGI-NYILATKOZAT CE - VASTAVUSDEKLARATSIOON CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - DECLARATION-DE-CONFORMITE CE - ΔHΛΩΣΗ ΣΥΜΜΟΡΦΩΣΗΣ CE - OVERENSSTEMMELSESERKLÆRING CE - PROHLÁŠENÍ-O-SHODĚ CE - DEKLARACJA-ZGODNOŚCI CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ CE - VYHLÁSENIE-ZHODY
CE - CONFORMITEITSVERKLARING CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE CE - DECLARAŢIE-DE-CONFORMITATE CE - UYGUNLUK-BEYANI
ROTEX
01
02
03
04
05
06
07
08
declares under its sole responsibility that the equipment to which this declaration relates:
erklärt auf seine alleinige Verantwortung daß die Ausrüstung für die diese Erklärung bestimmt ist:
déclare sous sa seule responsabilité que l'équipement visé par la présente déclaration:
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de apparatuur waarop deze verklaring betrekking heeft:
declara bajo su única responsabilidad que el equipo al que hace referencia la declaración:
dichiara sotto la propria responsabilità che gli apparecchi a cui è riferita questa dichiarazione:
δηλώνει με αποκλειστική της ευθύνη ότι ο εξοπλισμός στον οποίο αναφέρεται η παρούσα δήλωση:
declara sob sua exclusiva responsabilidade que os equipamentos a que esta declaração se refere:
09
10
11
12
13
14
15
16
заявляет, исключительно под свою ответственность, что оборудование, к которому относится настоящее заявление:
erklærer under eneansvarlig, at udstyret, som er omfattet af denne erklæring:
deklarerar i egenskap av huvudansvarig, att utrustningen som berörs av denna deklaration innebär att:
erklærer et fullstendig ansvar for at det utstyr som berøres av denne deklarasjon innebærer at:
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat laitteet:
prohlašuje ve své plné odpovědnosti, že zařízení, k němuž se toto prohlášení vztahuje:
izjavljuje pod isključivo vlastitom odgovornošću da oprema na koju se ova izjava odnosi:
teljes felelőssége tudatában kijelenti, hogy a berendezések, melyekre e nyilatkozat vonatkozik:
17
18
19
20
21
22
23
24
25
deklaruje na własną i wyłączną odpowiedzialność, że urządzenia, których ta deklaracja dotyczy:
declară pe proprie răspundere că echipamentele la care se referă această declaraţie:
z vso odgovornostjo izjavlja, da je oprema naprav, na katero se izjava nanaša:
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluv varustus:
декларира на своя отговорност, че оборудването, за коeто се отнася тази декларация:
visiška savo atsakomybe skelbia, kad įranga, kuriai taikoma ši deklaracija:
ar pilnu atbildību apliecina, ka tālāk aprakstītās iekārtas, uz kurām attiecas šī deklarācija:
vyhlasuje na vlastnú zodpovednosť, že zariadenie, na ktoré sa vzťahuje toto vyhlásenie:
tamamen kendi sorumluluǧunda olmak üzere bu bildirinin ilgili olduǧu donanımının aşaǧıdaki gibi olduǧunu beyan eder:
RGSQH10S18AA9W,
01
02
03
04
05
06
07
are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our instructions:
der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung, daß sie gemäß
unseren Anweisungen eingesetzt werden:
sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions:
conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig onze
instructies:
están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con nuestras
instrucciones:
sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle nostre istruzioni:
είναι σύμφωνα με το(α) ακόλουθο(α) πρότυπο(α) ή άλλο έγγραφο(α) κανονισμών, υπό την προϋπόθεση ότι χρησιμοποιούνται
σύμφωνα με τις οδηγίες μας:
08
09
10
11
12
13
14
15
estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
acordo com as nossas instruções:
соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим инструкциям:
overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore instrukser:
respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under förutsättning att
användning sker i överensstämmelse med våra instruktioner:
respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at disse brukes i
henhold til våre instrukser:
vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme mukaisesti:
za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům:
u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
16
17
18
19
20
21
22
23
24
25
megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi instrukcjami:
sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în conformitate cu
instrucţiunile noastre:
skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите инструкции:
atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade snašim
návodom:
ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
EN60335-2-40,
01
02
03
04
05
06
07
08
09
following the provisions of:
gemäß den Vorschriften der:
conformément aux stipulations des:
overeenkomstig de bepalingen van:
siguiendo las disposiciones de:
secondo le prescrizioni per:
με τήρηση των διατάξεων των:
de acordo com o previsto em:
в соответствии с положениями:
10
11
12
13
14
15
16
17
under iagttagelse af bestemmelserne i:
enligt villkoren i:
gitt i henhold til bestemmelsene i:
noudattaen määräyksiä:
za dodržení ustanovení předpisu:
prema odredbama:
követi a(z):
zgodnie z postanowieniami Dyrektyw:
18
19
20
21
22
23
24
25
în urma prevederilor:
ob upoštevanju določb:
vastavalt nõuetele:
следвайки клаузите на:
laikantis nuostatų, pateikiamų:
ievērojot prasības, kas noteiktas:
održiavajúc ustanovenia:
bunun koşullarına uygun olarak:
Low Voltage 2006/95/EC
Electromagnetic Compatibility 2004/108/EC *
01
02
03
04
05
06
07
08
09
Directives, as amended.
Direktiven, gemäß Änderung.
Directives, telles que modifiées.
Richtlijnen, zoals geamendeerd.
Directivas, según lo enmendado.
Direttive, come da modifica.
Οδηγιών, όπως έχουν τροποποιηθεί.
Directivas, conforme alteração em.
Директив со всеми поправками.
10
11
12
13
14
15
16
17
Direktiver, med senere ændringer.
Direktiv, med företagna ändringar.
Direktiver, med foretatte endringer.
Direktiivejä, sellaisina kuin ne ovat muutettuina.
v platném znění.
Smjernice, kako je izmijenjeno.
irányelv(ek) és módosításaik rendelkezéseit.
z późniejszymi poprawkami.
18
19
20
21
22
23
24
25
Directivelor, cu amendamentele respective.
Direktive z vsemi spremembami.
Direktiivid koos muudatustega.
Директиви, с техните изменения.
Direktyvose su papildymais.
Direktīvās un to papildinājumos.
Smernice, v platnom znení.
Değiştirilmiş halleriyle Yönetmelikler.
01Note*
02Hinweis*
03Remarque*
04Bemerk*
05Nota*
as set out in <A> and judged positively by <B>
according to the Certificate<C>.
wie in <A> aufgeführt und von <B> positiv
beurteilt gemäß Zertifikat<C>.
tel que défini dans <A> et évalué positivement par <B>
conformément au Certificat<C>.
zoals vermeld in <A> en positief beoordeeld door <B>
overeenkomstig Certificaat<C>.
como se establece en <A> y es valorado
positivamente por <B> de acuerdo con el
Certificado<C>.
06Nota*
07Σημείωση*
08Nota*
09Примечание*
10Bemærk*
delineato nel <A> e giudicato positivamente da<B>
secondo il Certificato<C>.
όπως καθορίζεται στο <A> και κρίνεται θετικά
από το <B> σύμφωνα με το Πιστοποιητικό<C>.
tal como estabelecido em <A> e com o parecer positivo
de <B> de acordo com o Certificado<C>.
как указано в <A> и в соответствии сположительным
решением <B> согласно Свидетельству<C>.
som anført i <A> og positivt vurderet af <B> ihenhold til
Certifikat<C>.
11Information*
12Merk*
13Huom*
14Poznámka*
15Napomena*
enligt <A> och godkänts av <B> enligt
Certifikatet<C>.
som det fremkommer i <A> og gjennom positiv
bedømmelse av <B> ifølge Sertifikat<C>.
jotka on esitetty asiakirjassa <A> ja jotka <B>
on hyväksynyt Sertifikaatin<C> mukaisesti.
jak bylo uvedeno v <A> a pozitivně zjištěno
<B> vsouladu sosvědčením<C>.
kako je izloženo u <A> i pozitivno ocijenjeno odstrane
<B> prema Certifikatu<C>.
16Megjegyzés*
17Uwaga*
18Notă*
19Opomba*
20Märkus*
a(z) <A> alapján, a(z) <B> igazolta a megfelelést, a(z)
<C>tanúsítvány szerint.
zgodnie z dokumentacją <A>, pozytywną
opinią <B> i Świadectwem<C>.
aşa cum este stabilit în <A> şi apreciat pozitiv de<B>
în conformitate cu Certificatul<C>.
kot je določeno v <A> in odobreno s strani <B>
vskladu scertifikatom<C>.
nagu on näidatud dokumendis <A> ja heaks kiidetud
<B> järgi vastavalt sertifikaadile<C>.
21Забележка*
22Pastaba*
23Piezīmes*
24Poznámka*
25Not*
както е изложено в <A> и оценено положително от <B>
съгласно Сертификата<C>.
kaip nustatyta <A> ir kaip teigiamai nuspręsta <B> pagal
Sertifikatą<C>.
kā norādīts <A> un atbilstoši <B> pozitīvajam vērtējumam
saskaņā ar sertifikātu<C>.
ako bolo uvedené v <A> a pozitívne zistené <B> vsúlade
s osvedčením<C>.
<A>’da belirtildiği gibi ve <C>Sertifikasına göre <B>
tarafından olumlu olarak değerlendirildiği gibi.
<A>
<B>
<C>
DEKRA (NB0344)
2082543.0551-QUA/EMC
TCF.025E19/07-2013
Dr.-Ing. Franz Grammling
Managing Director
1st of March 2014

Table of Contents
Installation manual
3
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
Table of Contents
1 About the documentation 3
1.1 About this document.................................................................. 3
2 About the box 3
2.1 Indoor unit ................................................................................. 3
2.1.1 To remove the accessories from the indoor unit......... 3
3 Preparation 4
3.1 Preparing installation site .......................................................... 4
3.1.1 Installation site requirements of the indoor unit .......... 4
3.2 Preparing piping ........................................................................ 4
3.2.1 To check the water volume and flow rate of the
space heating circuit and brine circuit......................... 4
3.3 Preparing electrical wiring ......................................................... 4
3.3.1 Overview of electrical connections for external and
internal actuators ........................................................ 4
4 Installation 5
4.1 Opening the units ...................................................................... 5
4.1.1 To open the indoor unit............................................... 5
4.1.2 To open the switch box cover of the indoor unit ......... 5
4.2 Mounting the indoor unit............................................................ 5
4.2.1 To install the indoor unit.............................................. 5
4.3 Connecting the brine piping....................................................... 7
4.3.1 To connect the brine piping......................................... 7
4.3.2 To fill the brine circuit.................................................. 7
4.3.3 To insulate the brine piping......................................... 7
4.4 Connecting the water piping...................................................... 8
4.4.1 To connect the water piping........................................ 8
4.4.2 To connect the recirculation piping ............................. 8
4.4.3 To connect the drain hose .......................................... 8
4.4.4 To fill the space heating circuit.................................... 8
4.4.5 To fill the domestic hot water tank .............................. 8
4.4.6 To insulate the water piping........................................ 9
4.5 Connecting the electrical wiring................................................. 9
4.5.1 About electrical compliance ........................................ 9
4.5.2 To connect the electrical wiring on the indoor unit...... 9
4.5.3 To connect the main power supply ............................. 10
4.5.4 To connect the remote outdoor sensor....................... 11
4.5.5 To connect the user interface ..................................... 11
4.5.6 To connect the shut-off valve...................................... 12
4.5.7 To connect the electrical meters................................. 12
4.5.8 To connect the domestic hot water pump................... 12
4.5.9 To connect the alarm output ....................................... 12
4.5.10 To connect the space heating ON/OFF output ........... 13
4.5.11 To connect the changeover to external heat source... 13
4.5.12 To connect the power consumption digital inputs ....... 13
4.6 Finishing the indoor unit installation .......................................... 13
4.6.1 To fix the user interface cover to the indoor unit......... 13
4.6.2 To close the indoor unit............................................... 13
5 Configuration 13
5.1 Overview: Configuration ............................................................ 13
5.1.1 To access the most used commands ......................... 14
5.2 Basic configuration .................................................................... 15
5.2.1 Quick wizard: Language / time and date..................... 15
5.2.2 Quick wizard: Standard............................................... 15
5.2.3 Quick wizard: Options................................................. 15
5.2.4 Quick wizard: Capacities (energy metering) ............... 16
5.2.5 Space heating control ................................................. 16
5.2.6 Domestic hot water control ......................................... 17
5.2.7 Contact/helpdesk number........................................... 17
5.3 Advanced configuration/optimization......................................... 18
5.3.1 Space heating operation: advanced ........................... 18
5.3.2 Heat source settings ................................................... 18
5.3.3 System settings........................................................... 18
5.4 Menu structure: Overview installer settings................................ 19
6 Commissioning 20
6.1 Checklist before commissioning................................................. 20
6.2 Checklist during commissioning ................................................. 20
6.2.1 To check the minimum flow rate .................................. 20
6.2.2 To perform an air purge ............................................... 20
6.2.3 Air purge function on the brine circuit .......................... 20
6.2.4 To perform a test run ................................................... 21
6.2.5 To perform an actuator test run ................................... 21
6.2.6 To perform an underfloor heating screed dryout.......... 22
7 Hand-over to the user 22
7.1 To fix the applicable language on the unit name plate ............... 22
8 Technical data 23
8.1 Wiring diagram ........................................................................... 23
8.1.1 Wiring diagram: Indoor unit.......................................... 23
1 About the documentation
1.1 About this document
Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set
consists of:
▪General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
▪Indoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
▪Installer reference guide:
▪ Preparation of the installation, technical specifications, good
practices, reference data,…
▪ Format: Digital files on the ROTEX homepage
▪Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the indoor unit) + Digital files on
the ROTEX homepage
Latest revisions of the supplied documentation may be available on
the regional ROTEX website or via your dealer.
The original documentation is written in English. All other languages
are translations.
2 About the box
2.1 Indoor unit
2.1.1 To remove the accessories from the
indoor unit
1Remove the screws at the top of the unit.
2Remove the top panel.

3 Preparation
Installation manual
4
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
4×
3Remove the accessories.
a1× b1× c1× d1×
f1×
e1× g1× h1×
aGeneral safety precautions
bAddendum book for optional equipment
cInstallation manual
dOperation manual
eRemote outdoor sensor
fUser interface kit cover
gMultilingual fluorinated greenhouse gases label
hCable for brine pressure switch connection
4Reinstall the top panel.
3 Preparation
3.1 Preparing installation site
3.1.1 Installation site requirements of the
indoor unit
▪ Mind the following spacing installation guidelines:
>500
≥50≥50
(mm)
▪ The indoor unit is designed for indoor installation only and for
ambient temperatures ranging from 5~30°C.
3.2 Preparing piping
3.2.1 To check the water volume and flow rate
of the space heating circuit and brine
circuit
Minimum water volume
Check that the total water volume per circuit in the installation is
minimum 20litre, the internal water volume of the indoor unit NOT
included.
INFORMATION
If a minimum heating load of 1kW can be guaranteed and
setting [9‑04] is changed by the installer from 1 to 4°C, the
minimum water volume can be lowered to 10litre.
INFORMATION
In critical processes, or in rooms with a high heat load,
extra water might be required.
NOTICE
When circulation in each space heating loop is controlled
by remotely controlled valves, it is important that the
minimum water volume is guaranteed, even if all of the
valves are closed.
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup
heater operation) in the installation is guaranteed in all conditions.
NOTICE
When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating/operation).
See the installer reference guide for more information.
Minimum required flow rate during backup heater operation
12l/min
See the recommended procedure as described in "6.2 Checklist
during commissioning"on page20.
3.3 Preparing electrical wiring
3.3.1 Overview of electrical connections for
external and internal actuators
Item Description Wires Maximum
running
current
Indoor unit power supply
1 Power supply for E1
and E3
3+N + GND (a)
2 Power supply for E2 2 (c)
4 Preferential kWh rate
power supply (voltage
free contact)
2(d)
5 Normal kWh rate power
supply
2 6.3A
User interface
6 User interface 2 (e)
Optional equipment
12 Room thermostat 3 or 4 100mA(b)

4 Installation
Installation manual
5
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
Item Description Wires Maximum
running
current
13 Outdoor ambient
temperature sensor
2(b)
14 Indoor ambient
temperature sensor
2(b)
15 Heat pump convector 4 100mA(b)
Field supplied components
16 Shut-off valve 2 100mA(b)
17 Electricity meter 2 (per meter) (b)
18 Domestic hot water
pump
2(b)
19 Alarm output 2 (b)
20 Changeover to external
heat source control
2(b)
22 Power consumption
digital inputs
2 (per input
signal)
(b)
(a) Refer to name plate on unit.
(b) Minimum cable section 0.75mm².
(c) Cable section 2.5mm².
(d) Cable section 0.75mm² till 1.25mm²; maximum length:
50m. Voltage-free contact shall ensure the minimum
applicable load of 15VDC, 10mA.
(e) Cable section 0.75mm² till 1.25mm²; maximum length:
500m. Applicable for both single user interface and dual
use interface connection.
NOTICE
More technical specifications of the different connections
are indicated on the inside of the indoor unit.
4 Installation
4.1 Opening the units
4.1.1 To open the indoor unit
1Loosen and remove the screws at the bottom of the unit.
2Push on the button at the bottom of the front plate.
WARNING: Sharp edges
Take the front plate on the upper part instead of the lower
part. Watch your fingers, there are sharp edges on the
lower part of the front plate.
3Slide the front panel of the unit downwards and remove it.
CAUTION
The front panel is heavy. Be careful NOT to jam your
fingers when opening or closing the unit.
4Loosen and remove the 4 screws that fix the top panel.
5Remove the top panel from the unit.
4×
2×
3
2
4
5
1
2
4.1.2 To open the switch box cover of the
indoor unit
7×
4.2 Mounting the indoor unit
4.2.1 To install the indoor unit
1Bring the unit on the pallet as close as possible to its installation
place.
2Lift the indoor unit from the pallet and place it on the floor.

4 Installation
Installation manual
6
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
210kg
4×
12
3Slide the indoor unit into position. Make sure that the side
support bolts are present when handling the unit.
4Unlink the heat pump module from the outer frame. ONLY
remove the side support bolts!
2×
NOTICE
Do NOT throw away any bolts. They need to be re-inserted
when transport or heavy manipulation is required.
5Open the front plate of the unit. If needed, the nylon bands for
lifting can be used.
6Adjust the height of the 4 leveling feet of the outer frame to
compensate for floor irregularities. The maximum allowed
deviation is 1°.
≤1°
NOTICE
To avoid structural damage on unit, ONLY move the unit
when levelling feet are at their lowest position.
NOTICE
For optimum sound reduction, carefully check if there is no
gap between the bottom frame and the floor.
7Adjust the height of the 2 front leveling feet of the inner frame to
compensate for irregularities.
CAUTION
Check that the heat pump module does NOT touch the
outer casing.

4 Installation
Installation manual
7
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
NOTICE
Check if the front support bolts remain levelled and are
NOT stressed. The support feet from outer (b) and inner
frame (c) MUST be adjusted so that those front bolts
remain level. Do NOT adjust support foot (a)!
Bottom view:
a
b
c
Side view:
INFORMATION
To check if the front support bolts are not stressed, loosen
them partly and fix them again afterwards.
4.3 Connecting the brine piping
4.3.1 To connect the brine piping
a b
aBrine out
bBrine in
NOTICE
To facilitate service and maintenance, it is recommended
to install shut-off valves as close as possible to the inlet
and outlet of the unit.
4.3.2 To fill the brine circuit
WARNING
Before, during and after filling carefully check the brine
circuit for leakage.
WARNING
Temperature of the fluid running through the evaporator
can become negative. It MUST be protected against
freezing. Refer to setting [A‑04] in "5.2.2 Quick wizard:
Standard"on page15.
INFORMATION
The materials used in the units brine circuit are chemically
resistant to the following anti-freeze fluids:
▪ 40 mass% propylene glycol
▪ 29 mass% ethanol
1Connect the unit to the field supplied brine filling system.
2Position the 3‑way valve correctly.
3Fill the circuit with brine until the manometer indicates a
pressure of ±2.0bar.
a
aBrine manometer
4Purge as much air as possible from the brine circuit. For
instructions, see "6Commissioning"on page20.
5Return the 3‑way valve to its original position.
4.3.3 To insulate the brine piping
The piping in the complete brine circuit MUST be insulated to
prevent reduction of the heating capacity.

4 Installation
Installation manual
8
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
Consider that the brine circuit piping inside the house can/will
condensate. Foresee adequate insulation for these pipes.
4.4 Connecting the water piping
4.4.1 To connect the water piping
NOTICE
Do NOT use excessive force when connecting the piping.
Deformation of the piping can cause malfunctioning of the
unit.
1Connect the domestic hot water in and out pipes to the indoor
unit.
a c bd
aSpace heating water out
bSpace heating water in
cDomestic hot water out
dDomestic cold water in (cold water supply)
NOTICE
It is recommended to install shut-off valves to cold water in
and hot water out connections. Shut-off valves are field
supplied.
2Connect the space heating in and out pipes to the indoor unit.
4.4.2 To connect the recirculation piping
Prerequisite: Only required if you need recirculation in your system.
1Loosen and remove the screws at the bottom of the unit.
2Slide the front panel of the unit downwards and remove it.
3Loosen and remove the 4 screws that fix the top panel.
4Remove the top panel from the unit.
a
b
aKnock-out hole
bConnection for recirculation piping
5Remove the knock-out hole at the backside of the unit.
6Connect the recirculation piping to the recirculation connection
and route the piping through the knock-out hole at the backside
of the unit.
7Re-attach the insulation and casing.
4.4.3 To connect the drain hose
Condensate can form on the brine components inside the
compressor department of the unit. The unit contains a drain pan.
Depending on room ambient temperature, room humidity and
operation condition, the drain pan can overflow. A drain hose is
supplied with the unit.
The drain hose is routed to the backside on the left, close to the
bottom of the unit. A field supplied drain pump might be needed to
pump the water away to the field drain.
4.4.4 To fill the space heating circuit
1Connect the water supply hose to the fill valve (field supply).
2Open the fill valve.
3Make sure that the automatic air purge valve is open (at least 2
turns).
INFORMATION
For location of the air purge valve, see "Dimensions and
service space: Indoor unit" in chapter "8Technical data"on
page23.
INFORMATION
For location of the air purge valve, see "Dimensions and
service space: Indoor unit" in the installer reference guide.
4Fill the circuit with water until the manometer indicates a
pressure of ±2.0bar.
a
aWater manometer
5Purge as much air as possible from the water circuit.
NOTICE
▪ Air in the water circuit can cause malfunctioning of the
backup heater. During filling, it may not be possible to
remove all the air from the circuit. Remaining air will be
removed through the automatic air purge valves during
the initial operating hours of the system. Additional
filling with water afterwards may be required.
▪ To purge the system, use the special function as
described in the chapter "6 Commissioning" on
page 20. This function should be used to purge the
heat exchanger coil of the domestic hot water tank.
6Close the fill valve.
7Disconnect the water supply hose from the fill valve.
4.4.5 To fill the domestic hot water tank
1Open every hot water tap in turn to purge air from the system
pipe work.

4 Installation
Installation manual
9
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
2Open the cold water supply valve.
3Close all water taps after all air is purged.
4Check for water leaks.
5Manually operate the field-installed pressure relief valve to
ensure a free water flow through the discharge pipe.
4.4.6 To insulate the water piping
The piping in the complete water circuit MUST be insulated to
prevent reduction of the heating capacity.
4.5 Connecting the electrical wiring
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
4.5.1 About electrical compliance
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16A and ≤75A per phase.).
4.5.2 To connect the electrical wiring on the
indoor unit
INFORMATION
Foresee additional cable length of 35cm for all wires which
should be connected to X2M and X5M on sheet metal
support above the hydro PCB. Additional wire length
should be tie wrapped at the back side of the unit. Reason
is to guarantee serviceability of, for example, the hydro
PCB.
1To open the indoor unit, see "4.1.1To open the indoor unit"on
page5 and "4.1.2 To open the switch box cover of the indoor
unit"on page5.
2Wiring should enter the unit from the top:
a c b
3Routing of the wiring inside the unit should be as follows:
1× 1×
a c b
a c
≥50 mm
≥50 mm
1× 1×
c
a
≥50 mm

4 Installation
Installation manual
10
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
X5M X2M
X1 X2 X3 X4
YC Y1 Y2 Y3 Y4
11 12
1×
1×
a c
NOTICE
▪ Make sure that 50mm is guaranteed between the low
voltage (a) and high voltage (c) cables.
▪ Make sure that the cables (a) and (c) are routed
between the wire guide and the backside of the switch
box to prevent water ingress.
4Fix the cable with cable ties to the cable tie mountings to
ensure strain relief and to make sure that it does NOT come in
contact with the piping and sharp edges.
Routing Possible cables (depending on unit type and installed options)
a
Low voltage
▪ Preferential power supply contact
▪ User interface
▪ Power consumption digital inputs (field supply)
▪ Outdoor ambient temperature sensor
▪ Indoor ambient temperature sensor (option)
▪ Electrical meters (field supply)
b
High voltage power supply
▪ Normal kWh rate power supply (power supply for unit)
c
High voltage control signal
▪ Preferential kWh rate power supply
▪ Heat pump convector (option)
▪ Room thermostat (option)
▪ Shut-off valve (field supply)
▪ Domestic hot water pump (field supply)
▪ Alarm output
▪ Changeover to external heat source control
CAUTION
Do NOT push or place redundant cable length in the unit.
4.5.3 To connect the main power supply
1Connect the main power supply.
In case of normal kWh rate power supply
X1M
N
L3
L2
L1
X2M
30
X6YB
X6Y X6YA
31
X5M
a
X19AX1A
Legend: see illustration below.
In case of preferential kWh rate power supply
Connect X6Y to X6YB.
X1M
N
L3
L2
L1
X2M
29 34
X6YB
X6YA
X6Y
X5M
a
X19AX1A
S1S LN
b
c
3 4
30 31
aMain power supply
bNormal kWh rate power supply
cPreferential power supply contact
2Fix the cable with cable ties to the cable tie mountings.

4 Installation
Installation manual
11
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
INFORMATION
In case of preferential kWh rate power supply, connect
X6Y to X6YB. The necessity of separate normal kWh rate
power supply to indoor unit (b) X2M30/31 depends on the
type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
4.5.4 To connect the remote outdoor sensor
The remote outdoor sensor (delivered as accessory) measures the
outdoor ambient temperature.
INFORMATION
If the desired leaving water temperature is weather
dependent, the full time outdoor temperature measurement
is important.
1Connect the external temperature sensor cable to the indoor
unit.
X2M
X5M
11
10
12
2Fix the cable with cable ties to the cable tie mountings.
3Install the remote outdoor sensor outside as described in the
installation manual of the sensor (delivered as accessory).
4.5.5 To connect the user interface
▪ If you use 1 user interface, you can install it at the indoor unit (for
control close to the indoor unit), or in the room (when used as
room thermostat).
▪ If you use 2 user interfaces, you can install 1 user interface at the
indoor unit (for control close to the indoor unit) + 1 user interface
in the room (used as room thermostat).
The procedure differs slightly depending on where you install the
user interface.
# At the indoor unit In the room
1 Connect the user interface cable to the indoor unit.
Fix the cable with cable ties to the cable tie mountings.
X2M
X5M
a b
12
a Main user interface(a)
b Optional user interface
2 Insert a screwdriver into the slots underneath the user
interface and carefully separate the faceplate from the
wallplate.
The PCB is mounted in the faceplate of the user interface.
Be careful NOT to damage it.
3 Fix the wallplate of the user interface
to the sheet metal of the unit.
Be careful NOT to distort the shape
of the backside of the user interface
by overtightening the mounting
screws.
Fix the wallplate of
the user interface to
the wall.
4 Connect as shown in 4A. Connect as shown
in 4A, 4B, 4C or 4D.
5 Reinstall the faceplate onto the wallplate.
Be careful NOT to pinch the wiring when attaching the
frontplate to the unit.
(a) The main user interface is required for operation, but has to
be ordered separately (mandatory option).
4A From the rear
ba
PCB
1×
4B From the left
a
PCB
b
1×

4 Installation
Installation manual
12
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
4C From the top
a
b
PCB
b
1×
4D From the top centre
a
PCB
b
b
1×
aNotch this part for the wiring to pass through with nippers
etc.
bSecure the wiring to the front part of the casing using the
wiring retainer and clamp.
4.5.6 To connect the shut-off valve
1Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normal closed) valve and a NO
(normal open) valve.
NO NC
X2M
X5M
5
67 5
6
7
X2M
X5M
M2SM2S
2Fix the cable with cable ties to the cable tie mountings.
4.5.7 To connect the electrical meters
INFORMATION
In case of an electrical meter with transistor output, check
the polarity. The positive polarity MUST be connected to
X5M/7 and X5M/9; the negative polarity to X5M/8 and
X5M/10.
1Connect the electrical meters cable to the appropriate terminals
as shown in the illustration below.
X2M
X5M
689
10
7
S2S S3S
2Fix the cable with cable ties to the cable tie mountings.
4.5.8 To connect the domestic hot water pump
1Connect the domestic hot water pump cable to the appropriate
terminals as shown in the illustration below.
X2M
X5M
3534
1~
MM2P
2Fix the cable with cable ties to the cable tie mountings.
4.5.9 To connect the alarm output
1Connect the alarm output cable to the appropriate terminals as
shown in the illustration below.
X2M
X5M
A4P
29
a
aInstallation of EKRP1HB is required.
2Fix the cable with cable ties to the cable tie mountings.

5 Configuration
Installation manual
13
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
4.5.10 To connect the space heating ON/OFF
output
1Connect the space heating ON/OFF output cable to the
appropriate terminals as shown in the illustration below.
X2M
X5M
A4P
29
a
aInstallation of EKRP1HB is required.
2Fix the cable with cable ties to the cable tie mountings.
4.5.11 To connect the changeover to external
heat source
1Connect the changeover to external heat source cable to the
appropriate terminals as shown in the illustration below.
X2M
X5M
A4P
LN
a
aInstallation of EKRP1HB is required.
2Fix the cable with cable ties to the cable tie mountings.
4.5.12 To connect the power consumption digital
inputs
1Connect the power consumption digital inputs cable to the
appropriate terminals as shown in the illustration below.
X2M
X5M
A8P
S6S
S7S
S8S
S9S
1 2 3 4 5
a
aInstallation of EKRP1AHTA is required.
2Fix the cable with cable ties to the cable tie mountings.
4.6 Finishing the indoor unit
installation
4.6.1 To fix the user interface cover to the
indoor unit
1Make sure that the front panel is removed from the indoor unit.
See "4.1.1To open the indoor unit"on page5.
2Plug the user interface cover into the hinges.
3Mount the front panel to the indoor unit.
4.6.2 To close the indoor unit
1Close the switch box cover.
2Reinstall the top plate.
3Reinstall the front panel.
NOTICE
When closing the indoor unit cover, make sure that the
tightening torque does NOT exceed 4.1N•m.
5 Configuration
5.1 Overview: Configuration
This chapter describes what you have to do and know to configure
the system after it is installed.

5 Configuration
Installation manual
14
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
NOTICE
The explanation about the configuration in this chapter
gives you ONLY basic explanations. For more detailed
explanation and background information, see the installer
reference guide.
Why
If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:
▪ The calculations of the software
▪ What you can see on and do with the user interface
How
You can configure the system via the user interface.
▪First time – Quick wizard. When you turn ON the user interface
for the first time (via the indoor unit), a quick wizard starts to help
you configure the system.
▪Afterwards. If necessary, you can make changes to the
configuration afterwards.
INFORMATION
When the installer settings are changed, the user interface
will request to confirm. When confirmed, the screen will
shortly turn OFF and "busy" will be displayed for several
seconds.
Accessing settings – Legend for tables
You can access the installer settings using two different methods.
However, NOT all settings are accessible via both methods. If so,
the corresponding table columns in this chapter are set to N/A (not
applicable).
Method Column in tables
Accessing settings via the breadcrumb in the
menu structure.
#
Accessing settings via the code in the
overview settings.
Code
See also:
▪"To access the installer settings"on page14
▪"5.4Menu structure: Overview installer settings"on page19
5.1.1 To access the most used commands
To access the installer settings
1Set the user permission level to Installer.
2Go to [A]: > Installer settings.
To access the overview settings
1Set the user permission level to Installer.
2Go to [A.8]: > Installer settings > Overview settings.
To set the user permission level to Installer
1Set the user permission level to Adv. end user.
2Go to [6.4]: > Information > User permission level.
3Press for more than 4seconds.
Result: is displayed on the home pages.
4If you do NOT press any button for more than 1hour or press
again for more than 4seconds, the installer permission level
switches back to End user.
To set the user permission level to Advanced end user
1Go to the main menu or any of its submenus: .
2Press for more than 4seconds.
Result: The user permission level switches to Adv. end user.
Additional information is displayed and "+" is added to the menu title.
The user permission level will stay in Adv. end user until set
otherwise.
To set the user permission level to End user
1Press for more than 4 seconds.
Result: The user permission level switches to End user. The user
interface will return to the default home screen.
To modify an overview setting
Example: Modify [1‑01] from 15 to 20.
1Go to [A.8]: > Installer settings > Overview settings.
2Go to the corresponding screen of the first part of the setting by
using the and button.
INFORMATION
An additional 0-digit is added to the first part of the setting
when you access the codes in the overview settings.
Example: [1‑01]: "1" will result in "01".
01
02
06
0a
0e
00 03
07
0b
0f
0000
04
08
0c
00 01
05
09
0d
15
Overview settings
Confirm Adjust Scroll
3Go to the corresponding second part of the setting by using the
and button.
01
02
06
0a
0e
00 03
07
0b
0f
0000
04
08
0c
00 01
05
09
0d
15
Overview settings
Confirm Adjust Scroll
Result: The value to be modified is now highlighted.
4Modify the value by using the and button.
01
02
06
0a
0e
00 03
07
0b
0f
0000
04
08
0c
00 01
05
09
0d
20
Overview settings
Confirm Adjust Scroll
5Repeat previous steps if you have to modify other settings.
6Push to confirm the modification of the parameter.
7At installer settings menu, press to confirm the settings.
Installer settings
The system will restart.
Confirm Adjust
Cancel
OK
Result: The system will restart.

5 Configuration
Installation manual
15
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
5.2 Basic configuration
5.2.1 Quick wizard: Language / time and date
# Code Description
[A.1] N/A Language
[1] N/A Time and date
5.2.2 Quick wizard: Standard
Space heating settings
# Code Description
[A.2.1.7] [C-07] Unit temperature control:
▪ 0 (LWT control)(default): Unit
operation is decided based on the
leaving water temperature.
▪ 1 (Ext RT control): Unit operation is
decided by the external thermostat.
▪ 2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
[A.2.1.B] N/A Only if there are 2user interfaces:
User interface location:
▪ 0 (At unit)
▪ 1 (In room)(default)
[A.2.1.8] [7-02] Number of water temperature zones:
▪ 0 (1 LWT zone): Main
▪ 1 (2 LWT zones): Main + additional
[A.2.1.9] [F-0D] Pump operation:
▪ 0 (Continuous): Continuous pump
operation, regardless of thermo ON or
OFF condition.
▪ 1 (Sample)(default): When thermo
OFF condition occurs, the pump runs
every 5 minutes and the water
temperature is checked. If the water
temperature is below target, unit
operation can start.
▪ 2 (Request): Pump operation based
on request. Example: Using a room
thermostat and thermostat creates
thermo ON/OFF condition.
Brine freezing temperature
# Code Description
[A.6.9] [A‑04] Brine freezeup temp
▪ 0: 0°C
▪ 1: –2°C
▪ 2: –4°C
▪ 3: –6°C
▪ 4: –8°C
▪ 5: –10°C
▪ 6: –12°C
▪ 7 (default): –14°C
NOTICE
The setting brine freezing temperature can be modified
and the read out is correct in [A.6.9] Brine freezeup temp
ONLY after having accessed menu [A.8] Overview
settings.
This setting can ONLY be modified and/or saved and the
read out is ONLY correct if the communication between
hydro module and compressor module is present. The
communication between hydro module and compressor
module is NOT guaranteed and/or applicable if:
▪ error "U4" appears on the user interface,
▪ the heat pump module is connected to preferential kWh
rate power supply where power supply is interrupted
and preferential kWh rate power supply is activated.
Capacity boost
# Code Description
N/A [A‑03] Compressor frequency
▪ 0 (default): normal
▪ 1: boost
5.2.3 Quick wizard: Options
Domestic hot water settings
# Code Description
N/A [E-05] DHW operation:
▪ 0: N/A
▪ 1 (Yes): Installed
[A.2.2.A] [D-02] DHW pump:
▪ 0 (No)(default): NOT installed
▪ 1 (Secondary rtrn): Installed for instant
hot water
▪ 2 (Disinf. shunt): Installed for
disinfection
See also illustrations below.
Domestic hot water pump installed for…
Instant hot water Disinfection
c
f
b
a
g
c
b
ad f
e g
aIndoor unit
bTank
cDomestic hot water pump
dHeater element
eNon‑return valve
fShower
gCold water
Thermostats and external sensors
NOTICE
If an external room thermostat is used, the external room
thermostat will control the room frost protection. However,
the room frost protection is only possible if the leaving
water temperature control on the unit's user interface is
turned ON.

5 Configuration
Installation manual
16
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
# Code Description
[A.2.2.4] [C-05] External room thermostat for the main
zone:
▪ 1 (Thermo ON/OFF): When the used
external room thermostat or
heatpump convector can only send a
thermo ON/OFF condition.
[A.2.2.5] [C-06] External room thermostat for the
additional zone:
▪ 1 (Thermo ON/OFF): When the used
external room thermostat or
heatpump convector can only send a
thermo ON/OFF condition.
[A.2.2.B] [C-08] External sensor:
▪ 0 (No)(default): NOT installed.
▪ 2 (Room sensor): Connected to PCB
measuring the indoor temperature.
Digital I/O PCB
# Code Description
[A.2.2.6.1] [C-02] External backup heater source:
▪ 0 (No)(default): None
▪ 1 (Bivalent): Gas, oil boiler
[A.2.2.6.3] [C-09] Alarm output on optional EKRP1HB
PCB:
▪ 0 (Normally open)(default): The
alarm output will be powered when
an alarm occurs.
▪ 1 (Normally closed): The alarm
output will NOT be powered when an
alarm occurs. This installer setting
allows distinction between detection
of an alarm and detection of a power
failure to the unit.
See also table below (Alarm output
logic).
Alarm output logic
[C-09] Alarm No alarm No power
supply to unit
0 (default) Closed output Open output Open output
1 Open output Closed output
Demand PCB
# Code Description
[A.2.2.7] [D-04] Demand PCB
Indicates if the optional demand PCB is
installed.
▪ 0 (No)
▪ 1 (Pwr consmp ctrl)
Energy metering
# Code Description
[A.2.2.8] [D‑08] Optional external kWh meter1:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1pulse/kWh)
▪ 2: Installed (1pulse/kWh)
▪ 3: Installed (10pulse/kWh)
▪ 4: Installed (100pulse/kWh)
▪ 5: Installed (1000pulse/kWh)
# Code Description
[A.2.2.9] [D‑09] Optional external kWh meter2:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1pulse/kWh)
▪ 2: Installed (1pulse/kWh)
▪ 3: Installed (10pulse/kWh)
▪ 4: Installed (100pulse/kWh)
▪ 5: Installed (1000pulse/kWh)
5.2.4 Quick wizard: Capacities (energy
metering)
# Code Description
[A.2.3.2] [6‑03] Capacity of the first step of the backup
heater at nominal voltage [kW]
[A.2.3.3] [6‑04] Capacity difference between the second
and first step of the backup heater [kW]
5.2.5 Space heating control
Leaving water temperature: Main zone
# Code Description
[A.3.1.1.1] N/A Setpoint mode:
▪ 0 (Fixed): Absolute
▪ 1 (Weather dep.): Weather-
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3 (WD/scheduled): Weather-
dependent + scheduled (only for
leaving water temperature control)
[7.7.1.1] [1-00]
[1-01]
[1-02]
[1-03]
Weather‑dependent curve (heating):
[1-03]
[1-02]
Ta
Tt
[1-00] [1-01]
▪ Tt: Target leaving water temperature
(main)
▪ Ta: Outdoor temperature
Leaving water temperature: Additional zone
# Code Description
[A.3.1.2.1] N/A Setpoint mode:
▪ 0 (Fixed): Absolute
▪ 1 (Weather dep.): Weather-
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3 (WD/scheduled): Weather-
dependent + scheduled (only for
leaving water temperature control)

5 Configuration
Installation manual
17
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
# Code Description
[7.7.2.1] [0-00]
[0-01]
[0-02]
[0-03]
Weather‑dependent curve (heating):
[0-00]
[0-01]
Ta
Tt
[0-03] [0-02]
▪ Tt: Target leaving water temperature
(additional)
▪ Ta: Outdoor temperature
Leaving water temperature: Delta T source
# Code Description
[A.3.1.3.1] [9-09] Heating: required temperature
difference between entering and
leaving water.
In case a minimum temperature
difference is required for the good
operation of the heat emitters in heating
mode.
Leaving water temperature: Modulation
# Code Description
[A.3.1.1.5] [8-05] Leaving water temperature modulation:
▪ 0 (No): Disabled
▪ 1 (Yes): Enabled. The leaving water
temperature is calculated according
to the difference between desired
and actual room temperature.
This allows better matching of the
heat pump capacity to actual
required capacity and results in less
start/stop cycles of the heat pump
and more economic operation.
N/A [8-06] Leaving water temperature maximum
modulation:
0°C~10°C (default: 3°C)
Requires modulation to be enabled.
This is the value by which the desired
leaving water temperature is increased
or lowered.
INFORMATION
When leaving water temperature modulation is enabled,
the weather‑dependent curve needs to be set to a higher
position than [8-06] plus the minimum leaving water
temperature setpoint required to reach a stable condition
on the comfort setpoint for the room. To increase
efficiency, modulation can lower the leaving water setpoint.
By setting the weather‑dependent curve to a higher
position, it cannot drop below the minimum setpoint. Refer
to the illustration below.
a
+[8-06]
−[8-06]
b
Ta
Tt
aWeather-dependent curve
bMinimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
room.
Leaving water temperature: Emitter type
# Code Description
[A.3.1.1.7] [9-0B] Reaction time of the system:
▪ 0 (Quick)(default)
Example: Small water volume and
fan coils.
▪ 1 (Slow)
Example: Large water volume, floor
heating loops.
Depending on the system water volume
and the heat emitters type, the heat up
of a space can take longer. This setting
can compensate for a slow or a quick
heating system by adjusting the unit
capacity during the heat up cycle.
5.2.6 Domestic hot water control
# Code Description
[A.4.1] [6-0D] Domestic hot water Type:
▪ 0 (Reheat only): Only reheat operation
is allowed.
▪ 1 (Reheat + sched.)(default): Same as
2, but between the scheduled heatup
cycles, reheat operation is allowed.
▪ 2 (Scheduled only): The domestic hot
water tank can ONLY be heated
according to a schedule.
[A.4.5] [6-0E] The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.
INFORMATION
There is a risk of space heating capacity shortage/comfort
problem (in case of frequent domestic hot water operation,
frequent and long space heating interruption will happen)
when selecting [6‑0D]=0 ([A.4.1] Domestic hot water
Type=Reheat only).
5.2.7 Contact/helpdesk number
# Code Description
[6.3.2] N/A Number that users can call in case of
problems.

5 Configuration
Installation manual
18
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
5.3 Advanced configuration/
optimization
5.3.1 Space heating operation: advanced
Room frost protection
NOTICE
If Emergency is set to Manual ([A.5.1.2]=0), and the unit is
triggered to start emergency operation, the user interface
will ask confirmation before starting. Room frost protection
is active even if the user does NOT confirm emergency
operation.
5.3.2 Heat source settings
Auto emergency
When the heat pump fails to operate the backup heater can serve as
an emergency heater and either automatically or non-automatically
take over the heat load. When auto emergency is set to Automatic
and a heat pump failure occurs, the backup heater will automatically
take over the heat load. When a heat pump failure occurs and auto
emergency is set to Manual the domestic hot water and space
heating operations will stop and need to be recovered manually. The
user interface will then ask you to confirm whether the backup heater
can take over the heat load or not. When the heat pump fails, will
appear on the user interface. If the house is unattended for longer
periods, we recommend that setting [A.5.1.2] Emergency shall be
set to Automatic.
# Code Description
[A.5.1.2] N/A Defines whether in an emergency
situation the backup heater is allowed to
automatically take over the entire heat
load or whether manual confirmation is
required.
▪ 0: Manual (default)
▪ 1: Automatic
INFORMATION
The auto emergency setting can be set in the menu
structure of the user interface only.
INFORMATION
If a heat pump failure occurs and [A.5.1.2] is set to Manual,
the room frost protection function, the underfloor heating
screed dryout function, and the water pipe antifreeze
function will remain active even if the user does NOT
confirm emergency operation.
5.3.3 System settings
Power consumption control
NOTICE
During periods of excessive capacity demand (example:
screed dryout function), the power limitation can be
activated in accordance to the dimension of the brine earth
collector.

5 Configuration
Installation manual
19
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
5.4 Menu structure: Overview installer settings
[A]
[A.2]
[A.2.1]
[A.2.2]
[A.2.2.6]
[A.3]
[A.3.1]
[A.3.1.1]
[A.3.2]
[A.3.3]
[A.4]
[A.4.4]
[A.5]
[A.5.1]
[A.7]
[A.6]
[A.6.3]
[A.6.2]
Installer settings
Language
System layout
Space operation
Domestic hot water (DHW)
Heat sources
System operation
Commissioning
Overview settings
System layout
Standard
Options
Capacities
Confirm layout
Space operation
LWT settings
Room thermostat
Operation range
Domestic hot water
Type
Disinfection
Maximum setpoint
SP mode
Weather-dependent curve
Heat sources
Backup heater
System operation
Auto restart
Preferential kWh rate
Pwr consumpt. control
Averaging time
Ext amb. sensor offset
Commissioning
Test run
UFH screed dryout
Air purge
Actuator test run
Standard
Unit type
Compressor type
Indoor software type
BUH type
Preferential kWh rate
Unit control method
Number of LWT zones
Pump operation mode
Power saving possible
User interface location
Options
Contact type main
Contact type add.
Digital I/O PCB
Demand PCB
External kWh meter
External kWh meter
DHW pump
External sensor
Leaving water
Main
Additional
Delta T source
Room thermostat
Room temp. range
Room temp. offset
Ext. room sensor offset
Operation range
Space heating OFF temp
Disinfection
Disinfection
Operation day
Start time
Temperature target
Duration
Backup heater
Operation mode
Emergency
Enable BUH step 2
Equilibrium temp.
Prefer. kWh rate PS
Allowed heaters
Forced pump OFF
Pwr consmp ctrl
Mode
Type
Amp. value
Amp. limits for DI
kW value
kW limits for DI
Priority
Digital I/O PCB
Ext. backup heat src
Solar kit
Alarm output
Main
LWT setpoint mode
Temperature range
Modulated LWT
Shut-off valve
Emitter type
[A.3.1.2] Additional
LWT setpoint mode
Temperature range
Room temp. step
Brine freezeup temp
[A.3.1.3] Delta T source
Heating
INFORMATION
Solar kit settings are shown but are NOT applicable for this
unit. Settings shall NOT be used or changed.
INFORMATION
Power saving settings are shown but are NOT applicable
for this unit. Settings shall NOT be used or changed.
INFORMATION
Depending on the selected installer settings, settings will
be visible/invisible.

6 Commissioning
Installation manual
20
RGSQH10S18AA9W
ROTEX HPU ground
4P353879-1A – 2015.10
6 Commissioning
NOTICE
NEVER operate the unit without thermistors and/or
pressure sensors/switches. Burning of the compressor
might result.
6.1 Checklist before commissioning
Do NOT operate the system before the following checks are OK:
You read the complete installation instructions, as
described in the installer reference guide.
The indoor unit is properly mounted.
The following field wiring has been carried out according
to this document and the applicable legislation:
▪ Between the local supply panel and the indoor unit
▪ Between the indoor unit and the valves (if applicable)
▪ Between the indoor unit and the room thermostat (if
applicable)
The system is properly earthed and the earth terminals
are tightened.
The fuses or locally installed protection devices are
installed according to this document, and have not been
bypassed.
The power supply voltage matches the voltage on the
identification label of the unit.
There are NO loose connections or damaged electrical
components in the switchbox.
There are NO damaged components or squeezed
pipes on the inside of the indoor unit.
There are NO refrigerant leaks.
The correct pipe size is installed and the pipes are
properly insulated.
There is NO water and/or brine leak inside the indoor
unit.
There are no odour traces noticeable of the used brine.
The space heating air purge valve is open (at least 2
turns).
The pressure relief valves purge to a safe location when
opened.
The minimum water volume is guaranteed in all
conditions. See "To check the water volume and flow rate
of the space heating circuit and brine circuit" in
"3.2Preparing piping"on page4.
6.2 Checklist during commissioning
The minimum flow rate during backup heater/defrost
operation is guaranteed in all conditions. See "To check
the water volume and flow rate of the space heating circuit
and brine circuit" in "3.2Preparing piping"on page4.
To perform an air purge.
To perform an air purge on the brine circuit.
To perform a test run.
To perform an actuator test run.
Underfloor screed dryout function
The underfloor screed dryout function is started (if
necessary).
6.2.1 To check the minimum flow rate
1Confirm according to the hydraulic configuration which space
heating loops can be closed due to mechanical, electronic, or
other valves.
2Close all space heating loops that can be closed (see previous
step).
3Start the pump test run operation (see "6.2.5 To perform an
actuator test run"on page21).
4Go to [6.1.8]: > Information > Sensor information > Flow rate
to check the flow rate. During pump test run operation, the unit
can operate below this minimum required flow rate that is
needed during defrost/backup heater operation.
Bypass valve foreseen?
Yes No
Modify the bypass valve setting
to reach the minimum required
flow rate + 2l/min
In case the actual flow rate is
below the minimum flow rate
(required during defrost/backup
heater operation), modifications
at hydraulic configuration are
required. Increase the space
heating loops that can NOT be
closed or install a pressure
controlled bypass valve.
Minimum required flow rate during backup heater operation
12l/min
6.2.2 To perform an air purge
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home
page are turned OFF.
1Go to [A.7.3]: > Installer settings > Commissioning > Air
purge.
2Set the type.
3Select Start air purge and press .
4Select OK and press .
Result: The air purge starts. It stops automatically when done. To
stop it manually, press , select OK and press .
6.2.3 Air purge function on the brine circuit
When installing and commissioning the unit, it is very important to
remove all air from the brine circuit.
NOTICE
It is required that the brine circuit is filled BEFORE the
brine pump test run is activated.
There are 2 ways to perform an air purge:
▪ with a brine filling station (field supply),
▪ with a brine filling station (field supply) in combination with the
unit's own brine pump.
10‑day brine pump operation. If a brine buffer vessel is part of the
system, it may be required to let the brine pump run continuously for
10 days after the system is commissioned. If 10‑day brine pump
operation is:
▪ ON: The unit operates as normal, except that the brine pump
operates continuously for 10 days, independent of compressor
status.
Other manuals for HPU ground
2
Table of contents
Other Rotex Heating System manuals
Popular Heating System manuals by other brands

BriskHeat
BriskHeat Custom Series instruction manual

Eraser
Eraser Bench Glo-Ring AH2711 operating manual

VES
VES ecovent EVC Installation, operation and maintenance manual

TERMA
TERMA MOA 43D user manual

Uponor
Uponor KaMo Combi Port Base Installation and operation manual

Soler & Palau
Soler & Palau CAD-COMPACT Series manual

Life Smart
Life Smart LS1002HH13 owner's manual

United CoolAir
United CoolAir SCPAC5G AS Series Installation, operation and maintenance manual

flakt woods
flakt woods RDKG manual

Magic-Pak
Magic-Pak HWC8 V Series installation instructions

Ambirad
Ambirad Herringbone HB manual

Thomas&Betts
Thomas&Betts RZ-NA 441-OMS Operating and maintenance