VISUALIZATION
The M2DL2 has a 27 x 15 mm display. The
upper line shows the displayed values 3 x 2 mm
and operation indicators, a left arrow indicates
power reversal, and a telephone indicates
established communication. The bottom line
shows the values, up to six digits of 8 x 3 mm.
The display shows all data from the recorder.
When the push-button is pressed, the display
advances and the backlighting is activated. After
30 seconds without pressing the backlight, it
turns off. The display remains on the last screen
viewed. To reset the partial counter, press and
hold for 10 seconds.
The data is displayed in the following order:
RS485 network identity
Total active energy 1 decimal
Current , 2 decimals
Voltage, 1 decimal
Active power, 2 decimals
Reactive power, 2 decimals
Power factor, 2 decimals
Frequency, 2 decimals
Zero counter, 1 decimal
Reactive energy totalizer, 1 decimal
Baud rate
COMUNICATION
The M2DL2 meter has an RS485
communication port on terminals 4 L- and 5 L+,
which communicates under MOD BUS
protocol. All meter values can be read through
the communication port, as well as modifying
the identity and baud rate.
For more detailed information on the
communication protocol, please contact
TECHINCAL DATA
VOLTAGE INPUT
Rated voltaje (Un) 230V AC.
Burden 10VA, 2W
Operating range 30% Un
Frequency 50 or 60 Hz
CURRENT INPUT
Current Ib (Imax.) 5 (80)A
Burden <1VA
Operating range 0 –Imax.
Starting current <0,4 % Ib
PULSE OUTPUT
Pulse weight 1600 pulses/kWh
Type SO DIN 43864
Insulation 3kV 1min.
Voltage 18 –27V DC
Pulse length > 30ms
GENERAL
Class 1 active
2 reactive
Operating temperature -20 to 60º
Energy indicator LED
Scroll pushbutton
Case material ABS, UL94, V0
Connection with screw
DIMENSIONS
Maximum dimensions
Width 2 modules DIN (35mm)
Height 90 mm
Depth 60 mm
Max. wire section:
Phase input terminal 6x6 mm
Neutral terminals 3,5 x3,5 mm
Terminals SO and RS485 Ø 1,8 mm