FIGURE 7
FIGURE 8
1. Remove cover.
2. Connect two conductor wire (14-24 AWG)
from main unit terminal block pins COM and
NO to remote horn unit terminal block.
(wire not provided). Units can be set up to
300 ft. apart. Not polarity sensitive (refer to
Fig. 1 and Fig. 7 for details).
3. Connect internal battery.
4. Mount similar to main unit with #8 x 1 in.
screws and anchors if necessary.
5. Replace cover and screws.
6. Turn key switch to ON position.
*Note: The ON/OFF key position is opposite
from 6400 main unit. Remote horn sounds
when main unit alarm is activated.
1. Determine length needed for reed
switch wires. STI provides 6 ft. which
can be cut to desired length.
2. Connect first reed switch in RS1 and
second in RS2 (Figure 7). (Refer to
Figure 1 for additional details on
page 4.)
3. If not using extra reed switch, add
jumper across two terminals of RS2
on terminal block.
*Note: Alarm will sound when either
door is opened.
TI-6404 DOUBLE DOOR WITH REMOTE HORN IN TALL NOTE
The STI-6404 is a combination unit for double doors with a remote horn. Reference the
installation instructions for the main unit, the STI-6402 and the STI-6403 for complete
installation.
TI-6405 EXIT TOPPER WITH MOMENTARY RE ET
The STI-6405 uses a momentary switch. After initial installation, unit
is always on and you do not have to remember to turn it on when
you leave a protected area. This model also eliminates having to
remember to re-arm it because it is never off.
When the alarm is triggered, to silence the alarm, insert the key and
turn completely to the "RESET" position and hold for 2 seconds, then
release. The switch will spring back to its original position and push
the key out. To turn the unit off, supply power must be removed.