Salda AmberAir Compact 4 CX P Guide

AIR HANDLING UNIT WITH HEAT RECOVERY SYSTEM
Mounting and installation instructions
Subject to technical modifcation
AmberAir
Compact 4 CX P

AmberAir Compact 4 CX P
2www.salda.lt
Contents
Safety instructions and precautions 3
Information about the product 5
Description 5
Casing 6
Dimensions and weight 7
Technical data 8
Air flow diagram 10
Operating conditions 11
Standard package of components 11
Components 12
Accessories 13
Installation 15
Reception of goods 15
Transportation and storage 15
Unpacking 17
Mounting diagram 19
Place requirements for the equipment 21
Mounting 21
Mounting position 22
Drainage 26
Connection of air duct 27
Connection of accessories 28
Arrangement of controller connections in MCB 28
Arrangement of controller connections in EX1 31
Arrangement of controller connections in EX2 33
Abbreviation in electrical circuit diagrams 36
Electrical external pre-heater 37
External water pre-heater 38
External water cooler 39
External DX cooler 40
Fire protection connection 41
Motorised air dampers 42
CO2 arba RH sensors 43
Unit status indication / mode change / fire alarm inlet / fireplace
function input 44
Connection of the unit to electric network 45
Start-up recommendations 45
System protection 45
Recommendations before the start of the unit (before the final user) 45
Possible faults and troubleshooting 46
Declaration of conformity 47
Notes 48

AmberAir Compact 4 CX P
www.salda.lt 3
Safety instructions and precautions
Device is manufactured in compliance with the following directives:
Machinery Directive, 2006/42/EC;
Low Voltage Directive, EEC 2006/95;
Electromagnetic Compatibility Directive, 2004/108/EC;
Ecodesign Directive, No 1253/2014.
Read this instruction very carefully before installing and using this equipment. Installation, connection and maintenance should be carried out
by a qualifed technician and in accordance with the local rules and legal acts.
The company shall take no responsibility for the injuries suffered by the people or for the damaged property, if the safety requirements are not
followed or the device is modifed without the permission of the manufacturer.
Main safety rules
Danger
• Before performing any electricity or maintenance tasks make sure, that the device is disconnected from the mains, that all
moving parts of the device have stopped.
• Make sure that the fans can not be entered through air ducts or branch openings.
• If you notice liquids on electric parts or connections that bear voltage, stop the operation of the appliance.
• Do not plug the device into the mains, that differs from the one indicated on the label or on the housing.
• Voltage of the mains should comply with the electrotechnical parameters indicated on the label.
• The device should be earthed in accordance with the rules of installation of electric appliances. It is forbidden to turn on and
use unearthed device. Follow the requirements of the device’s labels that indicate Danger.
Warnings
• Connection of electricity and maintenance of the device should be performed only by a qualifed personnel, in accordance with
the manufacturer’s instructions and valid safety requirements.
• In order to reduce the risk during installation and maintenance, suitable protective clothes should be worn.
• Beware of sharp angles while performing installation and maintenance tasks.
• Do not touch heating elements until they haven’t cooled down.
• Some devices are heavy, thus one should be very careful while transporting and installing. Use suitable lifting equipment.
• While connecting electricity to the mains a circuit breaker of suitable size is necessary.
Warning!
• If the device is installed in a cold environment, make sure that all connections and tubes are properly isolated. Intake and
discharge air ducts should be isolated in all cases.
• Openings of the ducts should be covered during transportation and installation.
• Make sure not to damage the heater when connecting the piping of the water heater. For tightening up, use a wrench/spanner.
Before starting the equipment
• make sure, that there are no strange objects inside;
• manually check whether fans are not stuck or blocked;
• if rotary heat exchanger is installed in the device, make sure that it is not stuck or blocked;
• check the grounding;
• make sure that all components and accessories are connected in accordance with the project or provided instructions.
Danger: Fumes
"Salda Antifrost" system uses dis-balancing of the air flow and it may cause negative pressure in premises. Great care should be
taken when using at the same time in premises as another heating appliance what depend on the air in premises. Such
appliances include gas, oil, wood or coal-fred boilers and heaters, freplaces, continuous flow or other water heaters, gas hobs,
cookers or ovens which draw air in from the room and duct exhaust gases out through a chimney or extraction ducting. The
heating appliance can be starved of oxygen, impairing combustion. In exceptional cases harmful gases could be drawn out of the
chimney or extraction ducting back into the room. In this case we strictly recommend to turn off "Salda Antifrost" and use an
external preheater for heat exchanger anti-frost protection (see "Salda Antifrost" function on the Remote controller manual).

AmberAir Compact 4 CX P
4www.salda.lt
Warning – pay attention Additional information
Stick the auxiliary label on the unit (on an easily accessible place) or on the
dashed place of a technical manual in order to keep the important
information about the unit.
STICK HERE
1 – Logo
2 – Internal usage code
3 – Brand name
4 – Technical data
5 – Units number
6 – Web address
Units tested and produced according to EC directives
AmberAir Compact units are Eurovent Certita Certification certified in AHU program.
SALDA – associated member of the Eurovent association (Europe’s Industry Association for Indoor Climate
(HVAC), Process Cooling, and Food Cold Chain Technologies)
AmberAir Compact SD50+ units designed of the VDI 6022 Part 1 guideline (Hygiene requirements for
ventilation and air-conditioning systems and units)
SALDA world like to inform you that based on the Commission Regulation (EU) No 1253/2014 for enforcing
directive 2009/125/EC (hereinafter referred to as ErP diretive), the operational area of certain AHU within
the European Union is regulated by certain conditions
The AHU can only be used within the EU when it meets the requirements of the ErP directive. If certain
AHU doesn’t have CE mark on it, it is strictly forbidden to use it in the EU.

AmberAir Compact 4 CX P
www.salda.lt 5
Information about the product
Description
AmberAir Compact is a compact-class ventilation unit with a heat recovery system. Its technical parameters are provided in the tables below.
Parameter Value
Model size 4-CXP CD50 LF1B1W1C1P
Heat exchange type Counterflow
Installation type Ceiling
Service side Left
Fan type EC
By-pass damper 100%
Integrated heater Water
Control type Comfort MCB
Filter type Panel
Outdoor installation version Indoor
Selected parameters
Parameter Unit of measurement Value
Winter Summer
Air flow (supply) [m³/h] 2590 2590
Air flow (extract) [m³/h] 2590 2590
External pressure (supply) [Pa] 250 250
External pressure (extract) [Pa] 250 250
Outdoor air temperature [ºC] -10 30
Outdoor air humidity [%] 90 50
Extract air temperature [ºC] 21 24
Extract air humidity [ºC] 50 50
Thank you for purchasing the devices of our company!
Not suitable for swimming pools, saunas and other
similar facilities.

AmberAir Compact 4 CX P
6www.salda.lt
Casing
The casing of AmberAir Compact CD50 shows exclusive tightness and thermal characteristics. More detailed information is provided in the tables
below.
EN 1886:2008 parameters
Model box CD50
Casing strength class D2*
Casing air leakage class at - 400 Pa L2
Casing air leakage class at + 700 Pa L3
Filter bypass leakage class F7*
Thermal transmittance class T3*
Thermal bridging factor class TB4
Thickness of double skin panel 50 mm
Insulation material Mineral wadding
Insulation material density 40 kg/m3
Insulation material thermal conductivity 0,036 W/mK
Insulation material fre reaction class (EN 13501-1:2007) A1
External sheet metal thickness and coating options 0,7 mm Zn polyester painting RAL 7040
Internal sheet metal thickness and coating options 0,7 mm Zn
AmberAir Compact CD50 cross-section
1 – external sheet metal; 2 – internal sheet metal; 3 – Mineral wool insulation

AmberAir Compact 4 CX P
www.salda.lt 7
Dimensions and weight
ODA
outdoor air
SUP
supply air
EHA
extract air
ETA
exhaust air
Weight (without package and accessories) [kg] 442

AmberAir Compact 4 CX P
8www.salda.lt
Technical data
General parameters
Parameter Unit of measurement Value
Thermal input (EN 308) [%] 80.7
SFPv class (clean flters) [ kW/m3/s] 2.22
SFPe class (design load) [ kW/m3/s] 2.49
Energy efciency class (Eurovent 2016) A
System pressure [Pa] 250/250
Maximum external leakage [%] <1
Maximum internal leakage [%] <1
Total power/current consumption [kW/A] 4.65/6.71
Phase/voltage/frequency [f/VAC/Hz] 3/400/50
Control board Comfort MCB
Insulation of walls [mm] 50/30
Fans
Fan type EC
Impeller type Backward curved
Supply air fan
Phase/voltage/frequency [f/VAC/Hz] 3/400/50
Power/current [kW/A] 0.90592/3.5
Speed [min-1]2642
Control input [VDC] 0-10
Protection class IP54
Exhaust air fan
Phase/voltage/frequency [f/VAC/Hz] 3/400/50
Power/current [kW/A] 0.90592/3.5
Speed [min-1]2627
Control input [VDC] 0-10
Protection class IP54
Integrated water heater
Model H-WH-865-390-130-01-11-35-01-L1ZN-1xDN15-S
Air flow [m3/h] 2590
Input temperature [°C] 18.1
Input relative humidity [%] 11.3
Output temperature [°C] 25
Output relative humidity [°C] 6.95
Airspeed [m/s] 2.41
Pressure drop [Pa] 17
Power [kW] 5.99
Water pressure drop [kPa] 7.19
Input water temperature [°C] 70
Output water temperature [°C] 49.3
Water flow [l/s] 0.08
Connection dimensions [mm] 1xDN15
Filters
Supply air flter
Class F7
Width [mm] 1113
Height [mm] 379
Thickness [mm] 46
Model MPL 1113x379x46-F7
Exhaust air flter
Class M5
Width [mm] 1113

AmberAir Compact 4 CX P
www.salda.lt 9
Height [mm] 379
Thickness [mm] 46
Model MPL 1113x379x46-M5
Pressure losses
Assembly Unit of measurement Supply air Exaust air
Heat exchanger [Pa] 93 120
Heater [Pa] 17 -
Filter [Pa] 162 85
Dampers [Pa] 19 -
Total [Pa] 291 205
Total system pressure [Pa] 250 250
Fan pressure losses [Pa] 119 190
Stationary pressure produced by fans [Pa] 541 455

AmberAir Compact 4 CX P
10 www.salda.lt
Air flow diagram
operational limits
power consumption
Supply air
Exhaust air

AmberAir Compact 4 CX P
www.salda.lt 11
Operating conditions
Place of operation Indoors / outdoors / indoors and outdoors / outdoors with special
accessories
Operation in explosive environment prohibited
Transporting of the polluted air prohibited
Outdoor air temeperature without preheater (Salda Antifrost** off) [°C] -5/+40*
Outdoor air temeperature without preheater (Salda Antifrost** on) [°C] -15/+40
Outdoor air temperature with 100% by-pass*** [°C] -23/+40
Outdoor air temperature with segmental by-pass*** [°C] -30/+40
Outdoor air temperature limits with a selected pre-heater on an air duct [°C] -40/+40
Outdoor air max humidity [%] 90
Temperature limits of an extracted air [°C] +15 / +40
Extract air max humidity [%] 60
Maximum room temperature for installing the unit [°C] +40
* ‒ when relative humidity of extracted air is lower than 35 %.
** ‒ uses dis-balancing of the air flow and it may cause negative pressure in premises.
*** ‒ depends on AHU confguration.
The air handling units installed outdoors shall be started only when the following obligatory conditions established by the manufacturer are met:
Units that are stored at the site before installation shall be sealed using additional means in order to prevent the accumulation of moisture inside
the unit.
If the unit is installed and is not started for continuous operation, it must be ensured that no warm/humid air enters the unit through air ducts
and that no moisture condensates inside the unit.
If the ventilation units stand idle for a long time or are started infrequently, the system must be blown down at the maximum capacity 1/24 h to
dehumidify.
Voltage to the automatics of the unit is installed and connected; the system of water products is flled with glycol/water
In case of failure to comply with the requirements set out above, the manufacturer shall have the right not to apply the warranty in respect of the
occurrence of moisture/water in damaged components.
Standard package of components
Standard package (without optional accessories) includes:
Key
1 pc.
Supply air temperature sensor
TJ
1 pcs.
Water temperature sensor for
water heater TV1
1 pcs. (water version only)
Hanging bracket
8 pcs. (Compact 1-3 CXP)
16 pcs. (Compact 4 CXP)
Anti-vibration rubber
8 pcs. (Compact 1-3 CXP)
16 pcs. (Compact 4 CXP)
Legs for ground version
2 pcs. (Compact 1 CXP)
3 pcs. (Compact 2-4 CXP)
Legs for vertical version
2 pcs. (Compact 1 CXP)
3 pcs. (Compact 2-4 CXP)

AmberAir Compact 4 CX P
12 www.salda.lt
Components
Heat exchanger1.
Supply air flter2.
Exhaust air flter3.
Exhaust air fan4.
Supply air fan5.
By-pass6.
Water heater7.
Control board8.
Supply air flter9.
Exhaust air flter10.

AmberAir Compact 4 CX P
www.salda.lt 13
Accessories

AmberAir Compact 4 CX P
14 www.salda.lt
Roof for AmberAir Compact Roof for 4 CXP GNGPR168_1099_0
Reducer STP STP-C 750x350_400 GSFSTPC161_340
Outlet-intake cover ABV 400 GFDABV0400
Shut-off dampers Damper SKG-A 400 GSKSKG037
Flange with Flexible Connection LSVF 400 GVELSVF007
Clamps Clamp AP 400 GAPAP009
Circular duct silencer AKS AKS 400-10 GSOAKS046
Reducer STP STP 750x350-700x400 GSFSTP161_342
Flexible connection LJ-PG 75-35 GLJLJ/PG089
Dampers for rectangular ducts SSK 750-350 GSKSSK713
Rectangular duct silencer SSP SSP 750x350x1000-4/100 GSOSSP216_136
Rectangular duct silencer SSP SSP 750x350x900-6/100/D GSOSSP216_1025
Outlet-intake cover OCR Outlet Cover 750x350 GNGPR168_737_0
Outlet-intake cover Outlet Cover 4CXP_45 GNGPR168_1093_0
Water coolers for rectangular ducts RWC 700x350 C4 GNGPR168_1068_0
Water coolers for rectangular ducts RWC 750x350 C2 GNGPR168_1070_0
DX coolers RFC for rectangular ducts RFC 750x350 F4 GNGPR168_1069_0
DX coolers RFC for rectangular ducts RFC 750x350 F2 GNGPR168_1071_0
Filter boxes FDS 75-35-M5 GFZFDS050
Filter boxes FDS 75-35-F7 GFZFDS055
Filter boxes FDS 75-35-G4 GFZFDS056
Rails for cover Compact CXP Rails 4CXP GNGPR168_1036_0
Base frame for Compact CXP ground version Base frame 4CXP GNGPR168_1028_0
Legs for Compact CXP horizontal version Legs 4CXPH GNGPR168_1035_0
Room CO2 sensor S-RCO2-F2 S-RCO2-F2 ZAKKT0048
Duct CO2 sensor S-KCO2 S-KCO2 ZAKKT0049
Duct RH sensor S-KFF-U S-KFF-U ZAKKT0051
Room RH sensor S-RFF-U-D-F2 S-RFF-U-D-F2 ZAKKT0050
Remote control panel FLEX MCB FLEX MCB without logo PRGPU107
PRGPU108
Control panel Stouch Stouch PRGPU051
Network module MB-Gateway MB-Gateway PRGPU082
Wireless Router Wireless N Nano Router TL-
WR802N PRGPU105
Switch 774451_774411 Switch 774451_774411 ZEPSM001
Duct smoke detector Ug3a4o Ug3a4o ZAKKT0110
IR presence sensor IR24-P IR24-P ZAKJT019
IR presence sensor IR24-PC IR24-PC ZAKJT020
IR presence sensor PATROL 701 Patrol 701 ZAKJT021
Actuator for damper LM230A-TP ZAKP0045
Actuator for damper TF 230 ZAKP0063
Energy Analyzers Energy Analyzer EM23 (Pulse) ZAKKT0118
Energy Analyzers Energy Analyzer EM23
(Pulse+ModBus) ZAKKT0119
Energy Analyzers Energy Analyzer EM24 (M-Bus) ZAKKT0121

AmberAir Compact 4 CX P
www.salda.lt 15
Installation
Reception of goods
Each device is thoroughly checked before transportation. While receiving goods it is recommended to check whether devices were not damaged
during transportation. If a damage to the device is noticed, immediately address the representatives of a transport company. Please inform a
representative of the manufacturer, if any deviation from the order is noticed.
Transportation and storage
The package is only for protection purpose!
While unloading and storing the units, use suitable lifting equipment to avoid damages and injuries. Do not lift units by holding on power
supply cables, connection boxes, air extract or exhaust flanges. Avoid hits and shock overloads. Before installation units must be stored in a
dry room with the relative air humidity not exceeding 70% (at +20 °C) and with the average ambient temperature ranging between +5 °C
and +30 °C. The place of storage must be protected against dirt and water.
The units must be transported to the storage or installation site using forklifts.
The storage is not recommended for a period longer than one year. In case of storage longer than one year, before the installation it is
necessary to verify whether the bearings of fans and motor rotate easily (turn the impeller by hand) and if the electric circuit insulation is
not damaged or the moisture is accumulated.
AmberAir Compact CX P are lifted from the pallet with a forklift or slings.
When lifting with a forklift, protect the condensate
drainage pipes. The product is heavy. Exercise
caution when transporting and installing. Follow
safety requirements established in your country.
Unit Dimensions, [mm]
H W L
Comapct 1 CX V 1750 1000 1945
Comapct 2 CX V 2095 1200 2190
Comapct 3 CX V 2400 1200 2165
Comapct 4 CX V 2580 1200 2465

AmberAir Compact 4 CX P
16 www.salda.lt
The product can be lifted with a forklift or a crane using slings.
When lifting with a forklift, the length of the fork must be greater than the length or width of the product (depending on the product version).
AmberAir Compact CX P lifting with a forklift
AmberAir Compact CX P lifting with slings
Only a product placed on a pallet may be lifted in
order to prevent damage to the casing.

AmberAir Compact 4 CX P
www.salda.lt 17
Unpacking
Remove the flm from the unit.
Remove the tightening packaging tapes which keep the protective profles.
Remove the protective profles, which are screwed up to the base with wood screws.
After unpacking the unit, examine it to make sure that it has not been damaged during transportation. The installation of damaged units is
prohibited!
AmberAir Compact CX P are very heavy, so exercise
caution when handling them. Follow safety
requirements established in your country.
Accessories may be packed together with the
product. Prior to transporting the unit, frst unpack
the accessories.

AmberAir Compact 4 CX P
18 www.salda.lt
After unpacking AmberAir Compact 4 CX P, open the
side covers and unscrew the supporting legs, which
are used for transportation, from the fans.

AmberAir Compact 4 CX P
www.salda.lt 19
Mounting diagram
Electrical version
Water version

AmberAir Compact 4 CX P
20 www.salda.lt
List of components
PR Plate heat exchanger
PV Supply air fan
IF Extract air flter
PF Supply air flter
IV Exhaust fan
KE1 Electric heater
PE1 Electric pre-heater (the electric and water pre-heaters may
not be used at the same time)
KV1 Water heater (the possibility of the heating switch function)
KV2 Water pre-heater (the electric and water pre-heaters may
not be used at the same time)
KV3 Water cooler
DX DX cooler
M1 By-pass damper
M2 Supply air damper actuator
M3 Exhaust air damper actuator
M4 Water heater circulation pump
M5 Water cooler valve motor
M6 Water heater valve motor
M12 Water pre-heater valve motor
M14 Water cooler circulation pump
M15 DX cooler valve actuator
M16 Water pre-heater circulation pump
A1 Fire alarm damper actuator I
A2 Fire alarm damper actuator II
TJ Supply air temperature sensor
TL Outdoor air temperature sensor
TE Exhaust air temperature sensor
DTJ Extract air temperature and RH sensor
TV1 Water heater temperature sensor
TV2 Water preheater temperature sensor
TV3 Water cooler temperature sensor
T1 Water heater termostat
T2 Cooler switching thermostat
PS1 Supply air flter switch (NO)
PS2 Extract air flter pressure switch (NO)
PS3 Heat converter pressure switch (NC)
U3 Supply air fan pressure sensor
U4 Extract air fan pressure sensor
ODA
Outdoor air
EHA
Exhaust air
ETA
Extract air
SUP
Supply air
CO2CO2 sensor
Stouch Remote control panel
SALDA AIR Mobile application
MB-Gateway Network module
NET Network
PC Computer
Ventilated premises
Possible PCB inputs/outputs
FA Fire alarm
FPP Fireplace protection
System mode switch (START/STOP)
Fans speed switch (BOOST)
H1 Operation indication output
H2 Alarm indication output
Table of contents
Other Salda Air Conditioner manuals