Samsung VRF DVM S Water Instruction manual

Model : Premium (Compact / Energy Efficiency) Type
Standard Type
VRF
Technical
Data Book
DVM S for Europe
(R410A, 50Hz, HP)

2
History
Version Modification Date Remark
Ver. 1.0 Release DVM S 30 HP High EER TDB for Europe (R410A, 50 Hz, HP) 15.12.30
Ver. 1.1 Add Sound Pressure Spec for Modules (At cooling mode / P.15 to 58) 16.01.06
Ver. 1.2
Modify Electric Diagram Mapping (For AM160KXVGGH** Model/P.65 to 66)
Line-up Name (Standard → Premium Compact, High Effi. →
Premium High Efficiency / P. 4, 5)
16.01.13
Ver. 2.0 Update all contents including installation 16.07.07
Ver. 2.01 Modify the Accessory Compatibility table for MCU kit(P163) 17.09.13

3
(1) Classification
AM DVM
(2) Capacity
x 1/10 HP (3 digits)
(3) Version
F2013
H2014
J2015
K2016
(4) Product Type
XOutdoor Unit
NIndoor Unit
(5) Feature 1
VInverter
MDVM S Eco
(6) Feature 2
AStandard + General Temp.+ Module
HHigh EER + Low Temp + Module
GHigh EER + General Temp + Module
(7) Rating Voltage
E1Ø, 220~240V, 50Hz
G3Ø, 380~415V, 50Hz
(8) Mode
HHeat Pump
RHeat Recovery
Installation
Nomenclature
Outdoor Unit
Model Name
(1) (2) (3) (4) (5) (6) (7) (8) Buyer

4
Features & Benefits
Samsung’s VRF system air conditioners offer instant temperature control, user-friendly installation and advanced
functionality, along with smart power usage. Our flagship VRF-based Samsung DVM S is a highly innovative system
that adopts the new third-generation Samsung Scroll Compressor (SSC) technology with Dual Digital Inverter
.
DVM S provides world-class energy efficiency and the most powerful cooling and heating performance available on
the market. This ideal air conditioning system accomodates all variable environments, including large commercial
or residential buildings.
Samsung DVM S offers innovative features to benefit the indoor comfort as well operational coasts of the system
through technological advances such as:
The world’s largest capacity
Capacities of the outdoor units offer up to 30 HP rooftop space savings as well as
lowering the installations and transportation costs.
High seasonal energy efficiency
Samsung DVM S adopts a dual inverter scroll compressor that upgrades refrigerant
flow and the motor’s operating performance. It makes ESEER of DVM S is up to 8.00.
Superior Heating Performance &
Wide Operating Temperature Range with Flash injection
Increase refrigerant flow by 32%, extend heating operation range at -25°C, thanks to
Flash Injection technology, extended compressor reliability range and control
compression ratio.

5
Features & Benefits
Intelligent Defrosting Logic
DVM S Intelligent Defrost Control logic keeps the unit in the heating mode
for up to 40% longer through out the heating season compared to
conventional model by monitoring the air resistance through the heat
exchanger.
Optimised Heat Exchanger
Combination of optimised coil path and different types of fin design for upper and
lower parts of the condenser evens out the airflow profile to optimise the heat transfer
process.
Extended Piping Length Limits
Allows extended piping length of up to 220 m, and units will still give
a great performance over wide areas. With this technology,
installation is available with a maximum height level of 110 m, which
is equivalent to 20 stories (each story is considered 5 m high).
Smart management
Further improves system’s energy efficiency due to precise indoor
climate control. Web-based remote monitoring and management
system allows quick and easy HVAC control and breakdown alert.
Eurovent Certified Performance
Samsung DVM S had become the 1st VRF Product to be certified by
Eurovent, the European Committee of HVAC&R, in March 2014.

7
1. Combination Table: Outdoor units
Premium Compact
System Model Capacity of Single Unit (HP)
Capa Code No. of Modules 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP
8HP
AM080JXVHGH/EU 1 1
10HP AM100JXVHGH/EU 1 1
12HP AM120JXVHGH/EU 1 1
14HP AM140KXVGGH/EU 1 1
16HP AM160KXVGGH/EU 1 1
18HP AM180KXVGGH/EU 1 1
20HP AM200KXVGGH/EU 1 1
22HP AM220KXVGGH/EU 1 1
24HP AM240KXVGGH/EU 1 1
26HP AM260KXVGGH/EU 1 1
28HP AM280KXVGGH/EU 1 1
30HP AM300KXVAGH/EU 1 1
32HP AM320KXVGGH1EU 2 1 1
34HP AM340KXVGGH1EU 2 1 1
36HP AM360KXVGGH1EU 2 1 1
38HP AM380KXVGGH1EU 2 1 1
40HP AM400KXVGGH1EU 2 1 1
42HP AM420KXVGGH1EU 2 1 1
44HP AM440KXVGGH1EU 2 1 1
46HP AM460KXVGGH1EU 2 1 1
48HP AM480KXVGGH1EU 2 1 1
50HP AM500KXVGGH1EU 2 1 1
52HP AM520KXVGGH1EU 2 1 1
54HP AM540KXVGGH1EU 2 1 1
56HP AM560KXVGGH1EU 2 1 1
58HP AM580KXVGGH1EU 2 1 1
60HP AM600KXVGGH1EU 2 2
62HP AM620KXVGGH1EU 3 1 1 1
64HP AM640KXVGGH1EU 3 1 1 1
66HP AM660KXVGGH1EU 3 1 1 1
68HP AM680KXVGGH1EU 3 1 1 1
70HP AM700KXVGGH1EU 3 1 1 1
72HP AM720KXVGGH1EU 3 1 1 1
74HP AM740KXVGGH1EU 3 2 1
76HP AM760KXVGGH1EU 3 1 1 1
78HP AM780KXVGGH1EU 3 1 1 1
80HP AM800KXVGGH1EU 3 1 1 1
82HP AM820KXVGGH1EU 3 1 2
84HP AM840KXVGGH1EU 3 1 2
86HP AM860KXVGGH1EU 3 1 2
88HP AM880KXVGGH1EU 3 1 2
90HP AM900KXVGGH1EU 3 3
NOTE
•Make sure to
use an indoor unit that is compatible with DVM S.
•Indoor units can be connected within the range indicated in following table.
•If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
•Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
•In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit
and deciding on piping length in accordance with design of the building.

1. Combination Table: Outdoor units
8
Premium Energy Efficiency
System Model Capacity of Single Unit (HP)
Capa Code No. of Modules 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP
8HP AM080JXVHGH/EU 1
1
10HP AM100JXVHGH/EU 1
1
12HP AM120JXVHGH/EU 1
1
14HP AM140KXVGGH/EU 1
1
16HP AM160KXVGGH/EU 1
1
18HP AM180KXVGGH/EU 1 1
20HP AM200KXVGGH/EU 1 1
22HP AM220KXVGGH2EU 2
1 1
24HP AM240KXVGGH2EU 2 2
26HP AM260KXVGGH2EU 2
1 1
28HP AM280KXVGGH2EU 2
1 1
30HP AM300KXVGGH2EU 2
1
1
32HP AM320KXVGGH2EU 2
1 1
34HP AM340KXVGGH2EU 3
2
1
36HP AM360KXVGGH2EU 2 2
38HP AM380KXVGGH2EU 2 1
1
40HP AM400KXVGGH2EU 3
1 1
1
42HP AM420KXVGGH2EU 3
1 1
1
44HP AM440KXVGGH2EU 3 1 2
46HP AM460KXVGGH2EU 3 1
1
1
48HP AM480KXVGGH2EU 3 1
2
50HP AM500KXVGGH2EU 3
1
2
52HP AM520KXVGGH2EU 3 1
1 1
54HP AM540KXVGGH2EU 3
1 1 1
56HP AM560KXVGGH2EU 3
1
1 1
58HP AM580KXVGGH2EU 3 1
1
1
60HP AM600KXVGGH2EU 3 2
1
62HP AM620KXVGGH2EU 4 1
3
64HP AM640KXVGGH2EU 4
1
2
1
66HP AM660KXVGGH2EU 4
1
3
68HP AM680KXVGGH2EU 4
1
3
70HP AM700KXVGGH2EU 4
1
2
1
72HP AM720KXVGGH2EU 4 4
74HP AM740KXVGGH2EU 4 3
1
76HP AM760KXVGGH2EU 4 2
2
78HP AM780KXVGGH2EU 4 1 3
80HP AM800KXVGGH2EU 4 3
1
82HP AM820KXVGGH2EU 4 2 1
1
84HP AM840KXVGGH2EU 4 1
2
1
86HP AM860KXVGGH2EU 4 1 1
1
1
88HP AM880KXVGGH2EU 4 1 1
1
1
90HP AM900KXVGGH2EU 4 1 1 2
NOTE
•Make sure to
use an indoor unit that is compatible with DVM S.
•Indoor units can be connected within the range indicated in following table.
•If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
•Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
•In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit
and deciding on piping length in accordance with design of the building.

9
1. Combination Table: Outdoor units
Standard
System Model Capacity of Single Unit (HP)
Capa Code No. of Modules 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP
8HP AM080JXVAGH/EU 1
1
10HP AM100JXVAGH/EU 1
1
12HP AM120JXVAGH/EU 1
1
14HP AM140KXVAGH/EU 1
1
16HP AM160KXVAGH/EU 1
1
18HP AM180KXVAGH/EU 1 1
20HP AM200KXVAGH/EU 1 1
22HP AM220KXVAGH/EU 1
1
24HP AM240KXVAGH/EU 1
1
26HP AM260KXVAGH/EU 1
1
28HP AM280KXVAGH/EU 1
1
30HP AM300KXVAGH/EU 1
1
32HP AM320KXVAGH/EU 2
1 1
34HP AM340KXVAGH/EU 2
1
1
36HP AM360KXVAGH/EU 2
1
1
38HP AM380KXVAGH/EU 2
1
1
40HP AM400KXVAGH/EU 2
1
1
42HP AM420KXVAGH/EU 2
1
1
44HP AM440KXVAGH/EU 2 2
46HP AM460KXVAGH/EU 2
1 1
48HP AM480KXVAGH/EU 2
1
1
50HP AM500KXVAGH/EU 2
1
1
52HP AM520KXVAGH/EU 2
1
1
54HP AM540KXVAGH/EU 2
1
1
56HP AM560KXVAGH/EU 2
1
1
58HP AM580KXVAGH/EU 2
1
1
60HP AM600KXVAGH/EU 2 2
62HP AM620KXVAGH/EU 3
1 1
1
64HP AM640KXVAGH/EU 3
1
1 1
66HP AM660KXVAGH/EU 3
1
1 1
68HP AM680KXVAGH/EU 3
1
1 1
70HP AM700KXVAGH/EU 3
1
1 1
72HP AM720KXVAGH/EU 3
1
1 1
74HP AM740KXVAGH/EU 3 2 1
76HP AM760KXVAGH/EU 3 1
1
1
78HP AM780KXVAGH/EU 3 1
1
1
80HP AM800KXVAGH/EU 3 1
1
1
82HP AM820KXVAGH/EU 3 1 2
84HP AM840KXVAGH/EU 3
1
2
86HP AM860KXVAGH/EU 3
1
2
88HP AM880KXVAGH/EU 3
1
2
90HP AM900KXVAGH/EU 3 3
NOTE
•Make sure to
use an indoor unit that is compatible with DVM S.
•Indoor units can be connected within the range indicated in following table.
•If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
•Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
•In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit
and deciding on piping length in accordance with design of the building.

10
1. Combination Table: Indoor units
Model Capacity (kW)
1.5 1.7 2.2 2.8 3.2 3.6 4.5 5.6 6.0 7.1 8.2 9.0 11.2 12.8 14.0 16.0
1Way
CST
JSF-0
JSF-1
JSF-2
2Way CST
4Way CST
360 CST
Floor
Standing
Unit
4Way
CST S
(600X600)
Duct S
(MSP)
Slim Duct
MSP Duct
Ceiling
Console
Boracay
Boracay
(with EEV)
AR5000
AR5000
(with EEV)

11
1. Combination Table: Indoor units
Model Capacity (kW)
1.5 1.7 2.2 2.8 3.2 3.6 4.5 5.6 6.0 7.1 8.2 9.0 11.2 12.8 14.0 16.0
HSP Duct
OAP Duct
Big Duct
Hydro
Unit HE
Hydro
Unit HT
ERV Plus
NOTE
•Make sure to use an indoor unit that is compatible with DVM S.
•Indoor units can be connected within the range indicated in following table.
•If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
•Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.

12
1. Combination Table: External Appearance
Premium compact
Capa [HP] Model Nane Model Capa [HP] Model Nane Model
8
10
12
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU
14
16
18
20
22
AM140KXVGGH/EU
AM160KXVGGH/EU
AM180KXVGGH/EU
AM200KXVGGH/EU
AM220KXVGGH/EU
24
26
28
30
AM240KXVGGH/EU
AM260KXVGGH/EU
AM280KXVGGH/EU
AM300KXVAGH/EU
32
34
AM320KXVGGH1EU
AM340KXVGGH1EU
36
38
40
42
AM360KXVGGH1EU
AM380KXVGGH1EU
AM400KXVGGH1EU
AM420KXVGGH1EU
44
46
48
50
52
AM440KXVGGH1EU
AM460KXVGGH1EU
AM480KXVGGH1EU
AM500KXVGGH1EU
AM520KXVGGH1EU
54
56
58
60
AM540KXVGGH1EU
AM560KXVGGH1EU
AM580KXVGGH1EU
AM600KXVGGH1EU
62
64
AM620KXVGGH1EU
AM640KXVGGH1EU
66
68
70
72
74
AM660KXVGGH1EU
AM680KXVGGH1EU
AM700KXVGGH1EU
AM720KXVGGH1EU
AM740KXVGGH1EU
76
78
80
82
AM760KXVGGH1EU
AM780KXVGGH1EU
AM800KXVGGH1EU
AM820KXVGGH1EU
84
86
88
90
AM840KXVGGH1EU
AM860KXVGGH1EU
AM880KXVGGH1EU
AM900KXVGGH1EU
Capa [HP] Model Nane Model Capa [HP] Model Nane Model
8
10
12
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU
14
16
18
20
22
AM140KXVGGH/EU
AM160KXVGGH/EU
AM180KXVGGH/EU
AM200KXVGGH/EU
AM220KXVGGH/EU
24
26
28
30
AM240KXVGGH/EU
AM260KXVGGH/EU
AM280KXVGGH/EU
AM300KXVAGH/EU
32
34
AM320KXVGGH1EU
AM340KXVGGH1EU
36
38
40
42
AM360KXVGGH1EU
AM380KXVGGH1EU
AM400KXVGGH1EU
AM420KXVGGH1EU
44
46
48
50
52
AM440KXVGGH1EU
AM460KXVGGH1EU
AM480KXVGGH1EU
AM500KXVGGH1EU
AM520KXVGGH1EU
54
56
58
60
AM540KXVGGH1EU
AM560KXVGGH1EU
AM580KXVGGH1EU
AM600KXVGGH1EU
62
64
AM620KXVGGH1EU
AM640KXVGGH1EU
66
68
70
72
74
AM660KXVGGH1EU
AM680KXVGGH1EU
AM700KXVGGH1EU
AM720KXVGGH1EU
AM740KXVGGH1EU
76
78
80
82
AM760KXVGGH1EU
AM780KXVGGH1EU
AM800KXVGGH1EU
AM820KXVGGH1EU
84
86
88
90
AM840KXVGGH1EU
AM860KXVGGH1EU
AM880KXVGGH1EU
AM900KXVGGH1EU

13
1. Combination Table: External Appearance
Premium Energy Efficiency
Capa [HP] Model Nane Model Capa [HP] Model Nane Model
8
10
12
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU
14
16
18
20
AM140KXVGGH/EU
AM160KXVGGH/EU
AM180KXVGGH/EU
AM200KXVGGH/EU
22
24
AM220KXVGGH2EU
AM240KXVGGH2EU
26
28
30
AM260KXVGGH2EU
AM280KXVGGH2EU
AM300KXVAGH2EU
32
36
38
AM320KXVGGH2EU
AM360KXVGGH2EU
AM380KXVGGH2EU
34 AM340KXVGGH2EU
40
42
44
46
48
AM400KXVGGH2EU
AM420KXVGGH2EU
AM440KXVGGH2EU
AM460KXVGGH2EU
AM480KXVGGH2EU
50 AM500KXVGGH2EU
52
54
56
AM520KXVGGH2EU
AM540KXVGGH2EU
AM560KXVGGH2EU
58 AM580KXVGGH2EU
60 AM600KXVGGH2EU
62
64
66
AM620KXVGGH2EU
AM640KXVGGH2EU
AM660KXVGGH2EU
68
72
74
76
78
AM680KXVGGH2EU
AM720KXVGGH2EU
AM740KXVGGH2EU
AM760KXVGGH2EU
AM780KXVGGH2EU
70 AM700KXVGGH2EU
80
82
84
86
AM800KXVGGH2EU
AM820KXVGGH2EU
AM840KXVGGH2EU
AM860KXVGGH2EU
88
90
AM880KXVGGH2EU
AM900KXVGGH2EU

1. Combination Table: External Appearance
14
Standard
Capa [HP] Model Nane Model Capa [HP] Model Nane Model
8
10
12
AM080JXVAGH/EU
AM100JXVAGH/EU
AM120JXVAGH/EU
14
16
18
20
22
AM140KXVAGH/EU
AM160KXVAGH/EU
AM180KXVAGH/EU
AM200KXVAGH/EU
AM220KXVAGH/EU
24
26
28
30
AM240KXVAGH/EU
AM260KXVAGH/EU
AM280KXVAGH/EU
AM300KXVAGH/EU
32
34
AM320KXVAGH/EU
AM340KXVAGH/EU
36
38
40
42
44
AM360KXVAGH/EU
AM380KXVAGH/EU
AM400KXVAGH/EU
AM420KXVAGH/EU
AM440KXVAGH/EU
46
48
50
52
AM460KXVAGH/EU
AM480KXVAGH/EU
AM500KXVAGH/EU
AM520KXVAGH/EU
54
56
58
60
AM540KXVAGH/EU
AM560KXVAGH/EU
AM580KXVAGH/EU
AM600KXVAGH/EU
62
64
AM620KXVAGH/EU
AM640KXVAGH/EU
66
68
70
72
74
AM660KXVAGH/EU
AM680KXVAGH/EU
AM700KXVAGH/EU
AM720KXVAGH/EU
AM740KXVAGH/EU
76
78
80
82
AM760KXVAGH/EU
AM780KXVAGH/EU
AM800KXVAGH/EU
AM820KXVAGH/EU
84
86
88
90
AM840KXVAGH/EU
AM860KXVAGH/EU
AM880KXVAGH/EU
AM900KXVAGH/EU

15
2. Specifications
Premium Compact
Type
DVM S DVM S DVM S
Model Name
AM080JXVHGH/EU AM100JXVHGH/EU AM120JXVHGH/EU
Outdoor unit module 1
---
Outdoor unit module 2
---
Outdoor unit module 3
---
Outdoor unit module 4
---
Power Supply Ø, #, V, Hz
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
Mode -
HEAT PUMP HEAT PUMP HEAT PUMP
Perfor-
mance
HP HP
8 10 12
Capacity (Nominal)
Cooling kW
22.4 28.0 33.6
Btu/h
76,400 95,500 114,600
Heating kW
25.2 31.5 37.8
Btu/h
86,000 107,500 129,000
Maximum number of connectable indoor units EA
14 18 21
Total capacity of the connected Indoor Units Min. kW
11.2 14.0 16.8
Total capacity of the connected Indoor Units Max. kW
29.1 36.4 43.7
Power
Power Input (Nominal) Cooling kW
4.59 6.22 7. 5 7
Heating kW
4.59 5.89 7. 5 6
Current Input (Nominal) Cooling A
7.40 10.00 12.10
Heating A
7.40 9.40 12.10
Current
Minimum Ssc
MVA
3.1 4.6 5.3
MCA A
18.0 21.1 25.0
MFA A
25 32 32
Efficiency
EER (Nominal) Cooling W/W
4.88 4.50 4.44
COP (Nominal) Heating W/W
5.49 5.35 5.00
ESEER W/W
8.00 7.4 3 7. 2 3
Casing Material Body -
EGI Steel Plate EGI Steel Plate EGI Steel Plate
Base -
EGI Steel Plate EGI Steel Plate EGI Steel Plate
Heat
Exchanger
Type -
Fin & Tube Fin & Tube Fin & Tube
Material Fin -
Al Al Al
Tube -
Cu Cu Cu
Fin Treatment -
Anti-corrosion Anti-corrosion Anti-corrosion
Compressor
Model Name -
DS-GB052FAVBSG x 1 DS-GB066FAVBSG x 1 DS-GB066FAVBSG x 1
Output kW x n
5.18 x 1 6.39 x 1 6.39 x 1
Oil Type -
PVE PVE PVE
Initial charge
cc x n
1,100 x 1 1,100 x 1 1,100 x 1
Fan
Type -
Propeller Propeller Propeller
Discharge direction -
Top Top Top
Quantity EA
111
Air Flow Rate m
5
/min
170 170 220
l/s
2,833 2,833 3,667
External Static Pressure Max. mmAq
888
Pa
78.45 78.45 78.45
Fan Motor Type -
BLDC Motor BLDC Motor BLDC Motor
Output W x n
830 x 1 830 x 1 830 x 1
Piping
Connections
Liquid Pipe Type
Braze connection Braze connection Braze connection
Φ, mm (inch)
9.52 (3/8) 9.52 (3/8) 12.70 (1/2)
Gas Pipe Type
Braze connection Braze connection Braze connection
Φ, mm (inch)
19.05 (3/4) 22.22 (7/8) 28.58 (1-1/8)
High pressure Gas Pipe(HR Only) Type
---
Φ, mm (inch)
---
Heat Insulation -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Max. [Equiv.]
m
200 [220] 200 [220] 200 [220]
Piping length (1st Branch-IDU) Max. m
90 90 90
Total piping length (System) Max. m
1,000 1,000 1,000
Level difference (ODU in highest position)
Max. m
110 110 110
Level difference (IDU in highest position) Max. m
110 110 110
Level difference (IDU-IDU) Max. m
50 50 50

2. Specifications
16
Wiring
connections
Transmission Cable mm
2
0.75 0.75 0.75
Remark -
F1, F2 F1, F2 F1, F2
Power supply intake -
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
Refrigerant Type -
R410A R410A R410A
Factory Charging kg
6.5 6.5 6.5
Sound
Sound Pressure Cooling dB(A)
57 58 62
Sound Pressure Heating dB(A)
59 60 64
Sound Power dB(A)
77 79 81
External
Dimension
Net Weight kg
195.5 195.5 195.5
Shipping Weight kg
211.5 211.5 211.5
Net Dimensions (WxHxD) mm
880 x 1,695 x 765 880 x 1,695 x 765 880 x 1,695 x 765
Shipping Dimensions (WxHxD) mm
948 x 1,887 x 832 948 x 1,887 x 832 948 x 1,887 x 832
Operating
Temp. Range
Cooling ℃
-5 ~ 48 -5 ~ 48 -5 ~ 48
Heating ℃
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
•Specification may be subject to change without prior notice.
•Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.

17
2. Specifications
Premium Compact
Type
DVM S DVM S DVM S
Model Name
AM140KXVGGH/EU AM160KXVGGH/EU AM180KXVGGH/EU
Outdoor unit module 1
---
Outdoor unit module 2
---
Outdoor unit module 3
---
Outdoor unit module 4
---
Power Supply Ø, #, V, Hz
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
Mode -
HEAT PUMP HEAT PUMP HEAT PUMP
Perfor-
mance
HP HP
14 16 18
Capacity (Nominal)
Cooling kW
40.0 45.0 50.4
Btu/h
136,500 153,500 172,000
Heating kW
45.0 50.4 56.7
Btu/h
153,500 172,000 193,500
Maximum number of connectable indoor units EA
26 29 32
Total capacity of the connected Indoor Units Min. kW
20.0 22.5 25.2
Total capacity of the connected Indoor Units Max. kW
52.0 58.5 65.5
Power
Power Input (Nominal) Cooling kW
8.89 10.92 10.68
Heating kW
9.62 10.75 10.52
Current Input (Nominal) Cooling A
14.30 17.50 17.10
Heating A
15.40 17.20 16.90
Current
Minimum Ssc
MVA
5.4 7. 2 8.8
MCA A
25.0 32.0 39.2
MFA A
32 40 50
Efficiency
EER (Nominal) Cooling W/W
4.50 4.12 4.72
COP (Nominal) Heating W/W
4.68 4.69 5.39
ESEER W/W
7. 7 8 7. 3 8 7. 2 5
Casing Material Body -
EGI Steel Plate EGI Steel Plate EGI Steel Plate
Base -
EGI Steel Plate EGI Steel Plate EGI Steel Plate
Heat
Exchanger
Type -
Fin & Tube Fin & Tube Fin & Tube
Material Fin -
Al Al Al
Tube -
Cu Cu Cu
Fin Treatment -
Anti-corrosion Anti-corrosion Anti-corrosion
Compressor
Model Name -
DS-GB066FAVB x 1 DS4GJ5080FVA x 1 DS-GB066FAVB x 2
Output kW x n
6.39 x 1 7.81 x 1 6.39 x 2
Oil Type -
PVE PVE PVE
Initial charge
cc x n
1,100 x 1 1,400 x 1 1,100 x 2
Fan
Type -
Propeller Propeller Propeller
Discharge direction -
Top Top Top
Quantity EA
222
Air Flow Rate m
5
/min
255 255 290
l/s
4,250 4,250 4,833
External Static Pressure Max. mmAq
888
Pa
78.45 78.45 78.45
Fan Motor Type -
BLDC Motor BLDC Motor BLDC Motor
Output W x n
620 x 2 620 x 2 620 x 2
Piping
Connections
Liquid Pipe Type
Braze connection Braze connection Braze connection
Φ, mm (inch)
12.70 (1/2) 12.70 (1/2) 15.88 (5/8)
Gas Pipe Type
Braze connection Braze connection Braze connection
Φ, mm (inch)
28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8)
High pressure Gas Pipe(HR Only) Type
---
Φ, mm (inch)
---
Heat Insulation -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Max. [Equiv.]
m
200 [220] 200 [220] 200 [220]
Piping length (1st Branch-IDU) Max. m
90 90 90
Total piping length (System) Max. m
1,000 1,000 1,000
Level difference (ODU in highest position)
Max. m
110 110 110
Level difference (IDU in highest position) Max. m
110 110 110
Level difference (IDU-IDU) Max. m
50 50 50

2. Specifications
18
Wiring
connections
Transmission Cable mm
2
0.75 0.75 0.75
Remark -
F1, F2 F1, F2 F1, F2
Power supply intake -
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
Refrigerant Type -
R410A R410A R410A
Factory Charging kg
9.4 8.4 8.4
Sound
Sound Pressure Cooling dB(A)
61 63 65
Sound Pressure Heating dB(A)
63 65 67
Sound Power dB(A)
81 83 89
External
Dimension
Net Weight kg
241.0 255.0 285.0
Shipping Weight kg
261.0 275.0 305.0
Net Dimensions (WxHxD) mm
1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765
Shipping Dimensions (WxHxD) mm
1,363 x 1,887 x 832 1,363 x 1,887 x 832 1,363 x 1,887 x 832
Operating
Temp. Range
Cooling ℃
-5 ~ 48 -5 ~ 48 -5 ~ 48
Heating ℃
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
•Specification may be subject to change without prior notice.
•Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.

19
2. Specifications
Premium Compact
Type
DVM S DVM S DVM S
Model Name
AM200KXVGGH/EU AM220KXVGGH/EU AM240KXVGGH/EU
Outdoor unit module 1
---
Outdoor unit module 2
---
Outdoor unit module 3
---
Outdoor unit module 4
---
Power Supply Ø, #, V, Hz
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
Mode -
HEAT PUMP HEAT PUMP HEAT PUMP
Perfor-
mance
HP HP
20 22 24
Capacity (Nominal)
Cooling kW
56.0 61.6 6 7. 2
Btu/h
191,100 210,200 229,300
Heating kW
63.0 69.3 75.6
Btu/h
215,000 236,500 258,000
Maximum number of connectable indoor units EA
36 40 43
Total capacity of the connected Indoor Units Min. kW
28.0 30.8 33.6
Total capacity of the connected Indoor Units Max. kW
72.8 80.1 8 7.4
Power
Power Input (Nominal) Cooling kW
12.50 15.75 16.00
Heating kW
12.75 15.86 15.43
Current Input (Nominal) Cooling A
20.00 25.30 25.70
Heating A
20.50 25.40 24.70
Current
Minimum Ssc
MVA
8.1 8.6 12.5
MCA A
42.0 44.6 55.0
MFA A
63 63 63
Efficiency
EER (Nominal) Cooling W/W
4.48 3.91 4.20
COP (Nominal) Heating W/W
4.94 4.37 4.90
ESEER W/W
6.82 6.43 7.1 8
Casing Material Body -
EGI Steel Plate EGI Steel Plate EGI Steel Plate
Base -
EGI Steel Plate EGI Steel Plate EGI Steel Plate
Heat
Exchanger
Type -
Fin & Tube Fin & Tube Fin & Tube
Material Fin -
Al Al Al
Tube -
Cu Cu Cu
Fin Treatment -
Anti-corrosion Anti-corrosion Anti-corrosion
Compressor
Model Name -
DS-GB066FAVB x 2 DS-GB066FAVB x 2 DS-GB070FAVA x 2
Output kW x n
6.39 x 2 6.39 x 2 6.76 x 2
Oil Type -
PVE PVE PVE
Initial charge
cc x n
1,100 x 2 1,100 x 2 1,100 x 2
Fan
Type -
Propeller Propeller Propeller
Discharge direction -
Top Top Top
Quantity EA
222
Air Flow Rate m
5
/min
290 290 340
l/s
4,833 4,833 5,667
External Static Pressure Max. mmAq
888
Pa
78.45 78.45 78.45
Fan Motor Type -
BLDC Motor BLDC Motor BLDC Motor
Output W x n
620 x 2 620 x 2 620 x 2
Piping
Connections
Liquid Pipe Type
Braze connection Braze connection Braze connection
Φ, mm (inch)
15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Gas Pipe Type
Braze connection Braze connection Braze connection
Φ, mm (inch)
28.58 (1-1/8) 28.58 (1-1/8) 34.92 (1-3/8)
High pressure Gas Pipe(HR Only) Type
---
Φ, mm (inch)
---
Heat Insulation -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Max. [Equiv.]
m
200 [220] 200 [220] 200 [220]
Piping length (1st Branch-IDU) Max. m
90 90 90
Total piping length (System) Max. m
1,000 1,000 1,000
Level difference (ODU in highest position)
Max. m
110 110 110
Level difference (IDU in highest position) Max. m
110 110 110
Level difference (IDU-IDU) Max. m
50 50 50

2. Specifications
20
Wiring
connections
Transmission Cable mm
2
0.75 0.75 0.75
Remark -
F1, F2 F1, F2 F1, F2
Power supply intake -
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
Refrigerant Type -
R410A R410A R410A
Factory Charging kg
8.4 8.4 14.0
Sound
Sound Pressure Cooling dB(A)
65 65 69
Sound Pressure Heating dB(A)
67 67 71
Sound Power dB(A)
89 89 90
External
Dimension
Net Weight kg
285.0 285.0 342.0
Shipping Weight kg
305.0 305.0 364.0
Net Dimensions (WxHxD) mm
1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,795 x 765
Shipping Dimensions (WxHxD) mm
1,363 x 1,887 x 832 1,363 x 1,887 x 832 1,363 x 1,987 x 832
Operating
Temp. Range
Cooling ℃
-5 ~ 48 -5 ~ 48 -5 ~ 48
Heating ℃
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
•Specification may be subject to change without prior notice.
•Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
Other manuals for VRF DVM S Water
1
This manual suits for next models
42
Table of contents
Other Samsung Fan manuals

Samsung
Samsung SER 450 User manual

Samsung
Samsung Fresh Access AN035NSEDAV/AA User manual

Samsung
Samsung RHF025EE Series User manual

Samsung
Samsung ERV User manual

Samsung
Samsung AN JSKLKN Series User manual

Samsung
Samsung RHF025EE Series User manual

Samsung
Samsung RHF025EE Series User manual

Samsung
Samsung RHF100KHEA Guide

Samsung
Samsung MOS-C1 User manual