Specifications
Order no. S-A11KL102B0013SSN00 S-A11KL152B0008SSN00 S-A11KL152B0019SSN00 S-A11KL202B0015SS□00
Rated output capacity (apparent power / active power) 1 kVA / 0.8 kW 1.5 kVA / 1.2 kW 2 kVA / 1.6 kW
Technology Topology Double conversion online
Rectifier High power factor converter
Cooling method Forced air cooling
Inverter High-frequency PWM
AC input No. of phases/wires Single-phase 2-wire(1)
Rated voltage 100/110/120 V (Same as output voltage)
Voltage range At load level < 70%: Within -40 to +20% of rated voltage (-40% becomes -20% for recovery voltage)
At load level ≥ 70%: Within ±20% of rated voltage
Rated frequency 50/60 Hz (auto-sensing(2))
Frequency range Within ±1, 3, 5, or 7% of rated frequency (same as output frequency regulation)
Required capacity(3) 1.1 kVA 1.5 kVA 2.0 kVA
Input power factor 0.95 or greater 0.95 or greater 0.97 or greater
AC output No. of phases/wires Single-phase 2-wire
Rated voltage 100/110/120 V (User-selectable. Factory setting: 100 V)
Rated current 10 A 15 A 20 A
Voltage regulation Within ±2% of rated voltage (at rated output)
Rated frequency 50/60 Hz (Same as the input rated frequency)
Frequency regulation During grid operation Within ±1, 3, 5, or 7% of the rated frequency (User-selectable. Factory setting: ±3%)
During battery operation Within ±0.5% of rated frequency
Output waveform Pure sine wave
Voltage harmonic
distortion
At linear load 3% or less (At rated output)
At rectifier load 7% or less (At rated output)
Load power factor Rated 0.8 lagging (Variation range: 0.7 lagging to 1.0)
Transient voltage
fluctuation
For abrupt load change Within ±5% of rated voltage (For 0 ⇔100% load step changes at rated input)
For loss or return of input power Within ±5% of rated voltage (At rated output)
For abrupt input voltage change Within ±5% of rated voltage (For ±10% abrupt change)
Overcurrent protection Automatic transfer to bypass (With automatic retransfer function)
Overload capability Inverter 105% (for 200 ms)
Bypass 200% (for 30 s), 800% (for 2 cycles)
Output Line Control Yes An optional outlet box is required
Battery Type Lithium-ion battery
Battery backup time(4) Initial value 13 min (15 min) 8 min (10 min) 19 min (20 min) 15 min (16 min)
After 10 years(5) 11 min (12 min) 6 min (8 min) 16 min (17 min) 12 min (13 min)
Battery self-test Settings possible (Factory setting: "disabled")
Interface PC port RS-232C
Remote port Remote ON/OFF switch (can control up to 5 UPS units in Linked Operation using a dedicated connection cable)
Auxiliary port Output Line Control contact(6)
Dry contact Optional dry contact interface card is required
Network support Optional LAN interface card is required
Acoustic noise During normal operation 41 dB 45 dB 45 dB
During battery operation or at a temperature above 40˚C51 dB 51 dB 51 dB
Heat dissipation (At rated operation, after battery charging completed) 82 W 127 W 153 W
Input leakage current 3 mA 3 mA 3 mA
Operating environment Ambient temperature: -20 to +55°C,(7) humidity: 10 to 90% RH (non-condensing)
Storage environment(8) Temperature: -20 to +55°C, humidity: 10 to 90% RH (non-condensing)
EMC standard VCCI 32-1 Class A
Separate options
Outlet box(9) ―P10030B (outlet type),
P10035B (terminal block type)
Rack support rails(10) RM030-US (2U)
Floor mounting brackets(11) FMA11KA00
Caster base(12) CBA11KA01
Air filter kit(13) FL008-3
(1) If single-wire grounding the AC input and output, set the input/output ground phase according to the
UPS specification. The W (N) terminal of AC input (S phase) and the W (N) terminal of AC output (V
phase) are to be grounded.
(2) The inverter synchronizes operation with AC input and allows uninterrupted transfer through a bypass
circuit provided that the AC input frequency is within a range of the rated frequency ±3% (1, 3, 5, or 7%
selectable) and the AC input voltage is within the rated voltage ±20% (if the load level is less than 70%:
between -40% and +20%).
(3) Max. capacity during battery recovery charging
(4) At 25°C ambient temperature and load power factor of 0.8, using new, fully charged batteries. In paren-
theses are values at 0.7 load power factor.
(5) Assuming 10 power outages per year
(6) For 2 kVA models, settings can be done with an optional outlet box.
(7) Battery charging will stop when battery temperature exceeds 55°C.
(8) Avoid use or storage in +30˚C or higher temperature for extended periods of time, or the battery's life
will be shortened. When storing the UPS for a long period without operating it, the batteries require
recharging once every six months.
(9) Enables Output Line Control, the coordinated on/off management of UPS outlets. "Output 0" is normal
output; "Output 1 (and 2)" is controlled output.
Note that its operating temperature range is different from that of the UPS.
(10) Used for mounting the UPS on a standard 19-inch rack.
(11) Used to secure a free-standing type UPS to the floor.
(12) Used to carry a vertically-installed UPS.
(13) Use an air filter at an ambient temperature of 40°C or lower.
Output capacity 1to 2kVA Battery backup time 8to 19 min
5
CATALOG No.P1023B006 ‘21.6
SANUPS A11K-Li