The table below shows a list of UPS setting menus.
For setting menus marked with "", after you change the setting value, the value will not take effect until after you restart the UPS.
No. Page Item
No. Setting Menu Menu LED Setting Value Setting Value
LED
Default
Setting
Current
Setting Description
1 5 2.1 UPS operation mode ●○○○○
Automatic ■□□□
*1
Automatically switch between double conversion mode and
economy mode.
Fixed to double
conversion mode □■□□ Fix the operation mode to double conversion mode.
2 6 2.2 Output voltage ○●○○○
100 200 ■□□□
*1
100 V 200 V
Set the UPS output voltage.
Same as the input voltage.
110 220 □■□□ 110V 220V
115 230 ■■□□ 115V 230V
120 240 □□■□ 120V 240V
- 208 ■□■□ - 208V
3 7 2.3
Synchronous frequency
range ●●○○○
1% ■□□□
Set the range (%) of the output frequency when the operation
mode is set to “Auto”.
3% □■□□ *
5% ■■□□
4 8 2.4 Interface ○○●○○
Standalone ■□□□ Standalone
WS □■□□ * Workstation. Set when using power management software and a
LAN interface card (optional).
Terminal ■■□□ Terminal. Do not set this value.
5 9 2.5 Baud rate ●○●○○
9600 ■□□□ * Baud rate 9600 bps Set the baud rate for connection
with a PC, LAN interface card
(optional), or workstation.
4800 □■□□ Baud rate 4800 bps
2400 ■■□□ Baud rate 2400 bps
6 10 2.6 PC I/F connector ○●●○○
RS-232C ■□□□ * Use the RS-232C connector.
USB □■□□ Use the USB connector.
7 11 2.7
UPS operation upon
power recovery ●●●○○
Automatic ■□□□ * Auto start
Operation to be performed when
the utility power recovers after
the UPS stops due to end of
battery discharge during a power
outage
OFF □■□□ OFF state retention
30% ■■□□ Automatically start if the battery
is at least 30% charged.
50% □□■□ Automatically start if the battery
is at least 50% charged.
80% ■□■□ Automatically start if the battery
is at least 80% charged.
8 12 2.8 Buzzer sound ○○○●○
All ■□□□ * Sound all.
Level 1 □■□□ Buzz when there is a key click sound, major fault signal, or battery
warning.
Level 2 ■■□□ Buzz when there is a key click sound or a major fault signal.
OFF □□■□ Buzz only when there is a key click sound.
9 13 2.9 UPS OFF Operation ●○○●○
1 sec. ■□□□ * Turn off when pressed for 1
second.
Set the switch operation when
stopping the UPS.
3 sec. □■□□ Turn off when pressed for 3
seconds.
Special operation ■■□□ Turn off by special operation.
10 14 2.10 Overload operation ○●○●○
Automatic return ■□□□ * Automatic return from bypass Set what to do after the power
supply switches to bypass due to
overload.
Bypass □■□□ Fix to bypass power supply
during overload.
11 15 2.11
Operation when
OFF
●●○●○
OFF ■□□□ * OFF when stopped Set the output power supply
state when UPS stops.
Bypass □■□□ Bypass power supply when
stopped
12 16 2.12
Bypass power supply
switch during input
erro
○○●●○
Enabled ■□□□ * Enable or disable power supply switches to bypass when an input
error occurs.
Disabled □■□□
13 17 2.13
Transmission signal at
minor error ●○●●○
Output ■□□□ * Set whether or not to send a transmission signal when a minor
error occurs.
Do not output □■□□
14 18 2.14
Simulated transmission
signal output for device
erro
○●●●○
Output ■□□□ Output a device error transmission signal for testing.
Do not output □■□□ * Do not output
15 19 2.15
Simulated transmission
signals for battery
voltage dip
●●●●○
Output ■□□□ Output a low battery voltage transmission signal for testing.
Do not output □■□□ * Do not output
16 20 2.16 Battery power startup ○○○○●
Disabled ■□□□ * Disable battery power startup Battery power startup on utility
power supply error.
Set whether to enable or disable.
If enabled, select the output
frequency.
Enabled 50 Hz □■□□ Enable: 50Hz
Enabled 60 Hz ■■□□ Enable: 60Hz
17 21 2.17
Timing of low battery
voltage warning ●○○○●
Battery voltage ■□□□ * When battery voltage level is
detected
Low battery voltage warning.
Set the timing for (Buzzer sound,
BATT.LOW (Red) Lit) to trigger.
1 min. □■□□ When there is one minute left
in battery capacity
2 min. ■■□□ When there are 2 minutes left
in battery capacity
5 min. □□■□ When there are 5 minutes left
in battery capacity
10 min. ■□■□ When there are 10 minutes
left in battery capacity
●,■: Indicates that the LED is blinking.