Coat-Endure User Manual & Datasheet V 2.3
7 Application Specifications
Please refer to Table 3 for Application Specifications.
PARAMETER VALUE
Response Time 1 second
Sensitivity Refer Table No. 4
Table 3: Application Specifications
8 Installation Guidelines
8.1 Procedure for Installation
For quick and easy installation, follow the steps in the
order mentioned below:
1. Testing Electrical Connections: Before mounting the
device on the tank, understand and test the connec-
tions outside the tank for at least one piece. For details
on connections, refer to Figure 5 before connecting the
device to outputs and power supply.
2. Mounting the Device: Correct mounting of the in-
strument is critical to the operation of the instrument.
Please refer to Tank Mounting Installation to mount the
instrument in the tank/silo or hopper. Coat-Endure is
designed to work properly in metal-body tanks only,
e.g. MS, SS or Aluminium tanks. Performance in plas-
tic tanks might not be satisfactory.
3. Electrical Connections: Perform the electrical con-
nections as mentioned earlier in Step 1.
4. Calibration and Settings:
•For non-conductive materials, Coat-Endure can
be calibrated in an empty process tank without
the application material.
•If the application material is conductive, Coat-
Endure has to be calibrated with the material.
Time-delay and fail-safe selection should be done af-
ter this stage. Section Calibration and Settings covers
settings in more detail.
5. Trial Run: Perform a trail run of the application pro-
cess with the application material. In case of errors
or unsatisfactory output, refer to Section Error Indica-
tions.
6. Finishing the Installation: Tighten the lid and the ca-
ble entries on the instrument so that no moisture seeps
into the instrument.
8.2 Tank Mounting Installations
•Coat-Endure is designed to work in metal-body tanks
only, e.g. M.S., S.S. or Aluminium tanks. Performance
in plastic tanks might not be satisfactory.
•The Coat-Endure probe can be installed in the ves-
sel in both horizontal (side mounting) and vertical (top
mounting) positions. Please refer to Figures 3 and 4.
•To prevent the ingress of moisture and water seepage
in side mounting position, the cable entries should al-
ways point downwards.
•Weatherproofness of enclosure is guaranteed only if
the cover is in place and glands are adequately tight-
ened. Damage due to accidental entry of water can be
avoided if the instrument is installed in a rain shade.
•If the ambient temperature is high, the instrument
should not be installed to receive direct sunlight. If
such a position of shade is not available, a heat shield
should be fitted above the instrument especially if the
operating temperature lies between 60◦C and 80◦C.
•Grounding part (S.S. material) of the probe should be
exposed atleast 20mm inside the hopper after thread-
ing/nozzle.
Figure 3: Dimensional Layout - Top Mounting
Figure 4: Dimensional Layout - Side Mounting
8.3 Electrical Connections
Electrical connections for the instrument will change with
the models. Please refer to figure 5 and the precautions
mentioned below before connecting the device.
Precautions for connecting Coat-Endure :
•Power Supply Rating
Make sure the power supplied to the instrument is
within the specified range mentioned in Table 1.