Sauer Sundstrand MCV104A5927 User manual

K18127 UNIT SPEC 1 OF 2
Unit Specification
saue
3500 Annapolis Lane North, Minneapolis, MN 55447
Telephone: (612) 509-2084 Telefax: (612) 559-0108 ISSUE: 1 DATE: March 1995
MCV104A5927
Electrical Displacement Control
GENERAL DESCRIPTION
This device is a two-stage electrohydraulic pump stroke control which uses mechanical feedback to establish closed loop
control of the swashplate angle of Sauer-Sundstrand Series 20 PV. Refer to bulletin number 95-8965 for more information.
Features: ◆ Standard.
©Copyright 1995, SAUER-SUNDSTRAND COMPANY.
All rights reserved. Contents subject to change.
ELECTRICAL CONNECTION
1835
TheEDCisdesignedtobecontrolledfromadccurrentsourceorvoltagesource.Pulsewidthmodulation(PWM)isnotrequired.
ButifaPWMsignalisused,avoidacarrierfrequency<200Hz.Donotuseapulsecurrentofmorethan120%ofthatrequired
for full output.
MAXIMUM CONTINUOUS VOLTAGE @ 93.9°C (200°F): 7.5 Vdc
ELECTRICAL CHARACTERISTICS
BCDA
+
Produces
Flow Out
Of Port
Input
Shaft
Rotation A or C B or D
A or C B or D
A D B A
A D A B
Clockwise
Counterclockwise
Start Current
Full Stroke Current
Start Current
Full Stroke Current
A and C B and D
A and C B and D
ABCD
+++
BCDA
+
INPUT SHAFT ROTATION VS. TERMINAL CONNECTION VS. OUTPUT FLOW
(+) Voltage to Terminal
One of Dual Coils Dual Coils in Parallel Dual Coils in Series
(These voltage levels are at 75°F (24°C).)
A/B 22 mA with 0.44 Vdc
A/B 125 mA with 2.5 Vdc
C/D 22 mA with 0.35 Vdc
C/D 125 mA with 2.0 Vdc
22 mA with 0.2 Vdc
125 mA with 1.2 Vdc
11 mA with 0.40 Vdc
62 mA with 2.14 Vdc
Pump Phasing With EDC Manual Operator (MO)
Pump MO
Rotation Pump Flow
Rotation Out Port
CW Towards Connector
Towards Connector A
CCW B
1622
D
C
A
B
Pin Orientation of 4-pin, 90°MS Mating
Connector. Part No. MS3108E-14S-2S
(Sauer-Sundstrand Part No. K03384). Dimensions of the MCV104A5927 in Millimeters (Inches).

K18127 UNIT SPEC 2 OF 2
PERFORMANCE and/or FEATURES
MOUNTING
123456789012345678901234567890121234567890123
1
2345678901234567890123456789012123456789012
3
1
2345678901234567890123456789012123456789012
3
1
2345678901234567890123456789012123456789012
3
1
2345678901234567890123456789012123456789012
3
123456789012345678901234567890121234567890123
1
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678901
2
1
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678901
2
1
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678901
2
1
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678901
2
123456789012345678901234567890121234567890123456789012345678901212345678901234567890123456789012
The control and feedback link must have the proper identification in order to be installed. Installing a control with an improper
controlfeedbacklinkcanresultinacontrolfailurewhichcancausethepumpswashplatetomovetofullangleandremainthere
independent of signal input.
DonotattempttoinstallanEDConapumpforwhichitwasnotoriginallydesignedwithoutchangingthelink-and-ballassembly.
Merely changing the swashplate drag link is inadequate. See Ordering Information for the necessary link-and-ball assembly
number. In no case should a valve originally built for a Series 2X pump be used on a Series 3X pump.
Installingacontrolnotdesignedforusewiththepressurelimiteron33,34and36Seriespumpswillpreventthepressurelimiter
from operating.
PUMP NEUTRAL ADJUSTMENT
WARNING
Usethefollowingproceduretobringthepumptoneutralonce
the Electrical Displacement Control has been mounted.
1. Install a 300 psi gauge into the charge pressure port on
the pump.
2. Using a 9/16-inch wrench, loosen the hex lock nut on
the null adjustment screw. See Dimension drawing.
3. Disconnect the electrical line at the connector.
4. Start the prime mover and run at low idle.
5. Slowly increase the prime mover speed to rated RPM.
6. If the transmission operates as shown by motor shaft
rotation,reducespeedto idle.Usinga 3/16-inchinternal
WARNING
Toadjustneutralrequiresoperatingthepump.Takethe
necessary safety precautions such as having unneces-
sarypersonnelstandawayfromthemachine.Maximum
system pressure may occur upon start up, and the
machine may move. Ensure that the operator is not in a
position to be injured should the machine move.
This model EDC is considered standard; it does not offer high response, pressure override, or servo ports.
1. Note, that all new EDCs are linkless, and therefore an installation kit is required for assembly. The installation kits
(ordered separately) provide the necessary hardware such as link, O-rings, gasket, etc. Kits include two control port
orifices, if installed pump response will reduce to one third original response.To ensure using the correct feedback link,
check the pump series which is stamped on the link.
2. Install one gasket and three O-rings between the EDC and the pump housing. If the pump is either a Series 20 or 26, an
additional set of gasket and O-rings is required because of the spacer which is installed between the EDC and pump.
Spacer thickness is 1/4 inch for Series 20 and 1 1/4 inch for Series 26.
3. Engage the feedback pin on the EDC in the pump drag link and swing the control into place against the pump housing.
The drag link should be on the cylinder block side of the swashplate. Install the seven mounting screws and tighten to
10 -11 ft·lb of torque.
hex wrench, slowly turn the null adjustment screw
clockwise or counterclockwise until the transmission
does not operate. Repeat Step 5. Note that charge
pressureshoulddropapproximately20psiwithforward
or reverse stroking of the pumpswashplate due to the
shifting of the shuttle valve in the motor manifold.
7. With a 3/16-inch internal hex wrench, slowly turn the
null adjustment screw clockwise until charge pressure
begins to decrease. Then slowly turn the adjustment
screw counterclockwise, observing the angle of
rotation,untilchargepressuredecreasesagain(charge
pressure will rise in neutral and drop when going into
stroke).
8. Turn the adjustment screw clockwise half the amount
oftheturnobservedinStep7.Thisshouldbethecenter
of neutral.
9. Holdtheadjustmentscrewandsecurelytighten thehex
lock nut on the adjustment screw to 14 - 18 ft·lb. Note
thatif a motorisused which does nothaveamanifold,
neutral should be adjusted (Steps 8 -10) by observing
the motor shaft rotation without a load.
10. Stopthe prime mover, andreconnect the electrical line.
11. Reconnect the electrical line.
Table of contents
Popular Control Unit manuals by other brands

Bosch
Bosch rexroth M1-16 Series instruction manual

Johnson Controls
Johnson Controls Tyco DV-5a Series Summary Instructions

Moxa Technologies
Moxa Technologies WE-2100T Series user manual

DMP Electronics
DMP Electronics 734N Series Installation and programming guide

nextys
nextys NCP12 Short Form Installation User Manual

ICP DAS USA
ICP DAS USA SP-S2-DS quick start

ADLINK Technology
ADLINK Technology cPCI-3534 user guide

WIDE Automation
WIDE Automation WALR 24-2A operating instructions

Simu
Simu SIMUDRIVE SD100Hz user guide

Samson
Samson 2406 Mounting and operating instructions

Interlogix
Interlogix ATS7200E Installation sheet

HP
HP R6000 - UPS - Lead Acid Expandable installation instructions