Ekinex EK-EB2-TP User manual

1
Pushbutton 6-fold
Product code: EK-EB2-TP
Other characteristics
• Housing in plastic material
• Wallinstallationinushmountingbox
• Protection degree IP20 (according to EN 60529)
• Classicationclimatic3K5andmechanical3M2(accor-
ding to EN 50491-2)
• Pollution degree 2 (according to IEC 60664-1)
• Weight 55 g (75 g with mounting support)
• Dimensions122x78x35mm(WxHxD)
Technical data
• Powersupply30VdcfromKNXbusline
• Current consumption < 15 mA
• Powerfrombus<360mW
Environmental conditions
• Operating temperature: - 5 ... + 45°C
• Storage temperature: - 25 ... + 55°C
• Transport temperature: - 25 ... + 70°C
• Relative humidity: 95% not condensing
Completion of the pushbutton
Forinstallationandoperationanekinex®pushbuttonmust
becompletedwithaseparateorderof:
• operationelementsconsistingofsixsquarerockers;
• onerectangularframeoftheekinex®formorankse-
ries.
Themetallicsupport,thexingscrews(2pairs),thepro-
tectionforconstructionsiteandtheKNXterminalblock
forconnectionofthebuslinearesuppliedwiththedevice.
KNX device for switching and control single loads or
groupsofloads.IthastobeusedinKNXinstallationsfor
controlofhomesandbuildings.
Description
Theekinex®6-foldpushbutton(max12functions)isaS-
modeKNXdeviceforon/offswitchingofloads,dimming
oflightingdevices,controllingofmotordrivesorotherpro-
grammableswitchingandcontrolfunctions.Itisequipped
withanintegratedKNXbuscommunicationmoduleandis
designedforwallinstallationonushmountingbox.The
devicehastwoLEDsforeachchannelprogrammablefor
exampleasastatussignalororientationnightlight.The
pushbuttonhastobecompletedwithfourrockersanda
framethatmustbeorderedseparately.Pushingarocker,
thedevicesendsonthebusatelegram,whichisreceived
andexecutedbyoneormoreKNXactuators.Thedevice
ispoweredbytheKNXbuslinewithaSELVvoltage30
Vdcanddoesnotrequireauxiliarypower.
RFLEKEB2TP
2
1)Pushbuttonwithrockersandrectangularframeofankseries
2)Pushbuttonwithrockersandrectangularframeofformseries
1
Datasheet STEKEB2TP_EN
Note. Rockers and frame for the completion of the
device must be ordered separately. For more infor-
mation on materials, colors and nishes available,
see also the ekinex®product catalog or browse
www.ekinex.com
Main functional characteristics
• On/offswitchingofsingleloadsorgroupsofloads
• Dimmingoflightingdevices
• Controlofmotordrives(forrollershutters,blinds,cur-
tains, etc.)
• Recallingandsavingofscenes
• Sending on the bus of values (temperature, bright-
ness, etc.)
• Switchingtoforcedfunctioning(lock)
• Measuring of room temperature and light brightness
through integrated sensors
• Different functions programmable for short pressure /
longpressureofarocker
• Statusfeedbackororientationnightlightthrough2-co-
lorprogrammableLEDs
Three-positions rockers with central neutral position have
to be mounted on a pushbutton. Pushing one side of a
rocker(forexampletheupperone),thepushbuttonsen-
ds on the bus a telegram for switching on, increasing
the brightness of luminaires or raising the blinds, while
pushingtheotherside(forexamplethelowerone),itsen-
dsatelegramforswitchingoff,reducingthebrightnessof
luminairesorloweringtheblinds.Eachchannelisequip-
pedwithLEDswhichcanbefreelyprogrammedasstatus
feedbacksoftheloadsandasorientationnightlight.
i
TP1
S

2
Customization of rockers
Therockerscanbecustomizedwithsymbolsandtexts,
formoreinformationseethestandardlibraryontheeki-
nex®catalogorthewebsitewww.ekinex.com.Onrequest
itisalsopossibleacustomizationwithsymbolsandtexts
chosenbythecustomer.
Protection for construction site
Aprotectionforconstructionsiteisincludedinthedelivery
of the device. The protection is made of thermoformed
transparentplasticand avoidsthedirtyingof thedevice
causedbythepaintingofthewalls.Tworeliefsincorre-
spondenceofeachrockerallowtheoperationofthechan-
nelalsowhentheprotectionisappliedonthepushbutton.
If necessary the protection for construction site can be
orderedseparatelywiththecodegiveninthetable.
REAEKQFTQTP
Switching elements
• Pushbutton(2)forswitchingbetweenthenormaland
programming operating mode
• Mechanisms(4)forindependentswitchingofsingleor
groupofloads(tobecompletedwithsquarerockers)
DCEKEB2TP
Product
code Rockers Construction site
protection
EK-EB2-TP 6square EK-PPR 1
2
4
5
3
1)Rockers(tobeorderedseparately)
2)Frameoftheseriesformorank(tobeorderedseparately)
3)Screwstofastenthepushbuttononthemetallicsupport
4)Pushbutton6channels
5)Metallicsupportformountingwallbox
6)Screwsforxingthesupportonthewallbox
7)Wallbox
1) Programming LED
2)Programmingpushbutton
3)ConnectionterminalblockforKNXbusline
4)Seatformountingtherocker
5)LightguideforLED
Mounting
ThedevicehasdegreeofprotectionIP20,andistherefo-
resuitableforuseindryinteriorrooms.Theinstallationof
thedevicerequiresthefollowingsteps:
a) x the metallic support (5) with the screws supplied
(6)onthewallbox(7)providedwithsuitablexingholes;
b)snaparectangularframe(2)oftheformorankseries,
insertingitfromtherearofthedevice(4);
c)enterthebusterminal,previouslyconnectedtothebus
cableinitssloton the rear side(seealso:“Connection
oftheKNXbusline”).Atthispointitisrecommendedto
carryoutthecommissioningofthedevice(seealso“Con-
gurationandcommissioning”)oratleastthedownload
ofthephysicaladdress;
d) mounting the device on the metallic support supplied
(5)withthescrews(3).Thecorrectmountingofthede-
viceoccurswhenthebusterminalislocatedinthelower
part; for mounting the device follow also the indication
TOP(arrowtippointingup)ontherearsideofthedevice.
e)snapthesixrockers(1)onthedevice.
The6-channelpushbuttoncanbemountedonaround,
asquareorarectangularwallushmountingbox.Ifne-
cessary,themetallicsupportformountingonthewallbox
canalsobeorderedseparatelyusingthecodeshownin
thetable.
Product
code
Number
and type of
rockers
Modularity of
rockers Frame
EK-EB2-TP 6square 40x40mm rectangular,form
orankseries
Switching, display and connection elements
Thedeviceisequippedwithmechanismsforswitching,2
LEDsforeachchannel,aprogrammingLEDandapro-
grammingpushbuttonandaterminalblockforconnection
ofthebusline.
Product
code
Wall ush
mounting box
Dist. between
xing holes [mm]
Support
EK-EB2-TP round/rectangular 60/85mm EK-SMR
ESEKEB2TP
123457
6

3
Note. Programming pushbutton and LED are only
accessible from the rear side of the device. It is bet-
ter addressing the device before the nal assem-
bly of rockers and frame. Once the addressing has
been performed, the device conguration can be la-
ter downloaded without pressing the programming
pushbutton.
Elementidisegnalazione
• LEDred(1)forindicationoftheactiveoperatingmode
(on=programming,off=normaloperation)
• Green and blue LED freely programmable e.g. for
feedbackstatusandorientationnightlight
Connection of the KNX bus line
TheconnectionoftheKNXbuslineismadewiththeter-
minalblock(black/red)includedindeliveryandinserted
intotheslotofthehousing.
CharacteristicsoftheKNXterminalblock
• springclampingofconductors
• 4seatsforconductorsforeachpolarity
• terminal suitable for KNX bus cable with single-wire
conductorsanddiameterbetween0.6and0.8mm
• recommendedwirestrippingapprox.5mm
• color codication: red = + (positive) bus conductor,
black=-(negative)busconductor
Conguration and commissioning
Conguration and commissioning of the device require
theuseoftheETS®(EngineeringToolSoftware)program
V4orlaterreleases.Theseactivitiesmustbecarriedout
accordingtothedesignofthebuildingautomationsystem
donebyaqualiedplanner.
Commissioning
Forcommissioningthedevicethefollowingactivitiesare
required:
• maketheelectricalconnectionsasdescribedabove;
• turnonthebuspowersupply;
• switch the device operation to the programming mode
by pressing the programming pushbutton located on
therearsideofthehousing.Inthismodeofoperation,
theprogrammingLEDisturnedon;
• download into the device the physical address and the
congurationwiththeETS®program.
At the end of the download the operation of the device
automatically returns to normal mode; in this mode the
programming LED is turned off. Now the bus device is
programmedandreadyforuse.
Dimensions [mm]
Conguration
Forthecongurationofthedeviceparametersthecorre-
spondingapplicationprogram orthewholeekinex®pro-
ductdatabasemustbeloadedintheETSprogram.For
detailedinformationoncongurationoptions,refertothe
applicationmanualofthedeviceavailableonthewebsite
www.ekinex.com.
122,0
77,6
28,5 6,3
34,8
53,0
DQEKEB2TP
Marks
• KNX
• CE:thedevicecomplieswiththeLowVoltageDirecti-
ve(2006/95/EC)andtheElectromagneticCompatibility
Directive(2004/108/EC).Testscarriedoutaccordingto
EN 50491-5-1:2010, EN 50491-5-2:2010
Maintenance
Thedeviceismaintenance-free.Tocleanuseadrycloth.
Itmustbeavoidedtheuseofsolventsorotheraggressive
substances.
i
Note. The conguration and commissioning of KNX
devices require specialized skills. To acquire these
skills, you should attend the workshops at KNX cer-
tied training centers.
i
ELEKEB2TP
Warning! The electrical connection of the device
can be carried out only by qualied personnel. The
incorrect installation may result in electric shock or
re. Before making the electrical connections, make
sure the power supply has been turned off.
+
-
Bus
KNX
Warning! In order to supply the KNX bus lines use
only KNX bus power supplies (e.g. ekinex EK-AB1-
TP or EK-AG1-TP). The use of other power supplies
can compromise the communication and damage
the devices connected to the bus.
!
!
Product
code
Application program
(## = release)
Communica-
tion objects
(max nr.)
Group
adresses
(max nr.)
EK-EB2-TP
APEKEB2TP##.knxprod
232 254

4
Documentation
ThisdatasheetreferstothereleaseA1.0oftheekinex®
deviceEK-EB2-TP,andisavailablefordownloadatwww.
ekinex.comasaPDF(PortableDataFormat)le.
File name Device release Updating
STEKEB2TP_EN.pdf A1.0 03/2014
Warnings
• Installation, electrical connection, conguration and
commissioningofthedevicecanonlybecarriedoutby
qualied personnel in compliance with the applicable
technicalstandardsandlawsoftherespectivecountri-
es
• Openingthehousingofthe device causestheimme-
diateendofthewarrantyperiod
• Incaseoftampering,thecompliancewiththeessential
requirementsoftheapplicabledirectives,forwhichthe
devicehasbeencertied,isnolongerguaranteed
• ekinex®KNXdefectivedevicesmustbereturnedtothe
manufactureratthefollowingaddress:SBSS.p.A.Via
Circonvallaziones/n,I-28010Miasino(NO)Italy
Other information
• This datasheet is aimed at installers, system integra-
tors and planners
• Forfurtherinformationontheproduct,pleasecontact
the ekinex®technical support at the e-mail address:
[email protected]orvisitthewebsitewww.ekinex.
com
• ekinex®isaregisteredtrademarkofSBSS.p.A.
• KNX®and ETS®areregisteredtrademarksofKNXAs-
sociationcvba,Brussels
© SBS S.p.A. 2014. The company reserves the right to make changes to
this documentation without notice.
Warning! Incorrect disposal of this product may
cause serious damage to the environment and hu-
man health. Please be informed about the correct
disposal procedures for waste collecting and pro-
cessing provided by local authorities.
Disposal
Attheendofitsusefullifetheproduct
describedinthisdatasheetisclassied
aswastefromelectronicequipmentin
accordance with the European Direc-
tive 2002/96/EC (WEEE), and cannot
bedisposedtogetherwiththemunici-
palundifferentiatedsolidwaste.
!
Other Ekinex Control Unit manuals
Popular Control Unit manuals by other brands

ProMinent
ProMinent DHV-UR Assembly and operating instructions

Dyna-Flo
Dyna-Flo 361 Operation, Parts, and Instruction Manual

EOS
EOS Farblichtmodul Assembly instruction

Wildlife Acoustics
Wildlife Acoustics Echo Meter Touch 2 manual

Velleman
Velleman Velbus VMB1RY manual

Helvest
Helvest FleX GAW400 quick start guide