SBT L450U User manual

User Manual
L450U/L450S

3
SBT Electric AC Drive
SBT- L450U / L450S User Manual
SBT-L450 is a general AC drive produced by Sana Barque Tavan company, capable of driving AC
motors up to 24A. The drive provides necessary functions to ensure smooth and reliable operation of
the motor at various speeds. In this manual, all functions are introduced and explained in detail. The
first chapter is dedicated to the initial settings and Auto-tuning, which calculates control parameters
required to drive the AC motor. The second chapter explains the drive parameters and features. In the
third chapter, procedures required to set the drive for elevator applications are explained. Fault
diagnosis is also included in this chapter. Please read the manual carefully to tune the drive correctly.

5
Chapter 1: Initial Settings
L450U / L450S Overview
Properties
Description
Motor Power (kW)
5.5
7.5
11
15
Input
Voltage (V)
3-phase 380V / 50 -60 Hz
Output
Voltage (V)
3-phase 0~380V / 0 ~ 100 Hz
Rated Current (A)
14
18
24
31
Weight (Kg)
5.3
5.4
5.7
6.0
Mechanical Installation
■ Dimensions:
The drive dimensions needed for mechanical installation are mentioned in Table 1.1.
Figure 1.1: Drive box from different views
Table 1.1: Drive dimensions
Dimension
A
205mm
B
287mm
D
215mm
H
300mm
W
217mm

6
Standard Connection Diagram
Figures 1.2 (a) and 1.2 (b) show the connection between the power connector and drive control
circuits in SBT L450U and L450S models, respectively. In L450S model, the drive can be used in a
single phase. It is also possible to set and run the drive via the digital operator without connecting
digital I/O wiring. Refer to chapter 2 for further details.
Figure 1.2 (a): SBT-L450U I/O block diagram

7
Figure 2.2 (b): SBT-L450S I/O block diagram

8
Digital Operator
Use the digital operator to enter Run and Stop commands, edit parameters, and display data including
fault and alarm information.
Figure 1.3: Keys and displays on the Digital Operator
No.
Display
Name
Function
1
Function Key (F1, F2)
Functions assigned to F1 and F2 vary depending on
the currently displayed menu. The name of each
function appears in the lower half of the display
window.
2
ESC Key
• Returns to the previous display.
• Moves the cursor one space to the left.
3
RESET Key
• Moves the cursor to the right.
• Resets the drive to clear a fault situation.
4
RUN Key
Run the motor when the drive is in the LOCAL
mode.
5
Up Arrow key
Scrolls up to display the next item, select parameter
numbers, and increment setting values.
6
Down Arrow Key
Scrolls down to display the previous item, select
parameter numbers, and decrements setting values.
7
STOP Key
Stops drive operation.
8
ENTER Key
• Enters parameter values and settings.
• Selects a menu item to move between displays.
9
LO/RE Selection Key
Switches drive control between the operator
(LOCAL) and the control circuit terminals
(REMOTE) for the Run command and speed
reference. The LED is on when the drive is in the
LOCAL mode (operation from keypad). [Not
available in SBT-L450]
10
LO/RE Light
Lit while the operator is selected to run the drive
(LOCAL mode). This feature is not available in this
version.
11
FWD Light
Lit while the drive runs in the forward direction.
12
REV Light
Lit while the drive runs in the reverse direction.
13
MOD Light
Lit when the energy injected by the drive is
negative.
14
RDY Light
Lit when the drive is ready to operate.
15
BB Light
Lit when the drive is in the base block status.
16
ALM Light
Blinks when an alarm occurs.
LO/RE
FWD
REV
MOD
RDY
BB
ALM

9
LCD Display
Figure 1.4: Panel monitoring menu
No.
Name
Display
Content
1
Operation Mode Menus
MODE
Displayed when in the main menu.
MONITOR
Displayed when in Monitor Mode.
VERIFY
Indicates the Modified Parameters Menu.
PRMSET
Displayed when in Parameter Setting Mode.
A.TUNE
Displayed during Auto-Tuning.
2
Mode Display Area
DRV
Displayed when in Drive Mode.
PRG
Displayed when in Programming Mode.
3
Ready
Rdy
It indicates the drive is ready to run.
4
Data Display
-
Displays specific data and operation data.
6
Function Key 1 (F1)
HELP
Pressing displays the Help menu.
←
Pressing scrolls the cursor to the left.
HOME
Pressing returns to the top menu (Monitor
Menu).
ESC
Pressing returns to the previous display.
7
FWD/REV
FWD
During Up command
REV
During Down command
8
Function Key 2 (F2)
FWD/REV
Pressing switches between Up and Down
when the Up/Down command is set using the digital
operator.
DATA
Pressing scrolls to the next display.
→
Pressing scrolls the cursor to the right.
RESET
Pressing resets the existing drive fault or
error.
Menu structure
The drive panel has four display screens that cover user-accessible drive features. Hereafter, these
menus are explained:
■ Monitoring:
Monitor parameters let the user view various aspects of drive performance using the digital operator
display. The values are updated online according to the drive condition.
■ Auto-tuning
Based on the required motor parameters shown in this menu, the drive is capable of calculating
necessary control parameters to run the motor efficiently.
■ Setting
In the setting menu, the user can edit and verify parameter settings. The number of accessible
parameters is based on the control method set in A1-02.

10
■ Modified Parameters
The parameters which have been modified and changed since the startup of the panel are shown in
this menu. If the driver turns off or the panel resets, the list will be cleared.
Auto-Tuning
The drive offers Auto-Tuning for induction motors. The type of Auto-Tuning used differs further
based on the control mode and other operating conditions.
Note: The drive will only show Auto-Tuning parameters that are valid for the control mode which has
been set in A1-02.
■ Auto-Tuning for Induction Motors
This feature automatically sets the motor parameters E1-** and E2-** for an induction motor.
Table 1.2 Types of Auto-Tuning for Induction Motors
Type
Setting
Requirements and Benefits
V/f (0)
OL(2)
CLV (3)
CLVPM (7)
Stationary Auto-
tuning
T1-01=3
• Automatically calculates motor parameters needed
for open-loop and V/f control.
Yes
Yes
Yes
No
Encoder Offset
Calculation
T1-01=10
Automatically calculates Encoder offset.
No
No
No
Yes
Table 1.3 lists the data that must be entered for Auto-Tuning. Make sure this data is available before
starting Auto-Tuning. The necessary information is usually listed on the motor nameplate or in the
motor test report provided by the motor manufacturer.
Table 1.3 Auto-Tuning Input Data
Input Value
Input
Parameter
Unit
Tuning Type (T1-01)
3
Stationary
10
Encoder offset calculation
Motor Rated Power
T1-02
kW
Yes
Yes
Motor Rated Voltage
T1-03
Vac
Yes
Yes
Motor Rated Current
T1-04
A
Yes
Yes
Motor Rated Frequency
T1-05
Hz
Yes
Yes
Number of Motor Poles
T1-06
-
Yes
Yes
Motor Rated Speed
T1-07
rpm
Yes
Yes
Encoder resolution
T1-08
PPR
No
Yes
■ Basic Auto-Tuning Preparations and Precautions
WARNING! Electrical Shock Hazard. Do not touch the motor during Auto-Tuning. Lethal
voltages may be present on the motor case. Failure to comply may result in serious injury from
electrical shock.
WARNING! Electrical Shock Hazard. When executing Stationary Auto-Tuning for motor data,
the motor does not rotate, however, power is applied. Do not touch the motor until Auto-Tuning
is completed. Failure to comply may result in death or serious injury from electrical shock.
Note: In the automatic calculation of encoder offset, although the test is in static mode, the
mechanical brake must be in open condition and if the motor is connected to a load, it must be
adjusted to be balanced on both sides. ( Do not move to the desired position by opening the brakes )
• When using a motor contactor, make sure it remains closed during the Auto-Tuning process.
• Ensure Base_Block signal is ON when performing Auto-Tuning.
• Ensure the motor is securely mounted and bolted in place prior to Auto-Tuning.
• To cancel Auto-Tuning, press the STOP key on the digital operator.

11
• Make sure motor nameplate data is readily available before Auto-Tuning the drive. Auto-
Tuning requires the user to input data from the motor nameplate or motor test report.
Auto-Tuning Operation Example
Selecting the Type of Auto-Tuning
The example below shows how to select the type of Auto-Tuning.
Step
Display/ Result
1.
Turn on the power to the drive. The initial display
appears.
2.
Press or until the Auto-Tuning display
appears.
3.
Press to begin setting parameters.
4.
Press to select the value for T1-01.
5.
Save the setting by pressing
6.
The display automatically returns to the display
shown in Step 3.
■ Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Step
Display/ Result
1.
Press to access the motor output power
parameter T1-02.
2.
Press to view the default setting.
3.
Press , , , and to
enter the motor power nameplate data in kW.
4.
Press to save the setting.

12
5.
The display automatically returns to the display in
Step 1.
6.
Repeat Steps 1 through 5 to set the following
parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
• T1-05, Motor Base Frequency
• T1-06, Number of Motor Poles
• T1-07, Motor Base Speed
• T1-08, Encoder Resolution
■ Starting Auto-Tuning
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary
Auto-Tuning is performed even with the motor stopped, which could result in death or serious
injury. Do not touch the motor until Auto-Tuning has been completed.
Step
Display/Result
1.
After entering the data listed on the motor nameplate,
press to confirm.
2.
Press to activate Auto-Tuning.
3.
Auto-Tuning finishes in approximately five seconds.
Parameter Settings during Induction Motor Auto-Tuning: T1
The T1-** parameters are used to set the Auto-Tuning input data for induction motor tuning.
■ T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used.
No.
Parameter Name
Setting Range
Default
T1-01
Auto-Tuning Mode Selection
3
3
Setting 3: Stationary Auto-tuning

13
■ T1-02: Motor Rated Power
It sets the motor rated power according to the motor nameplate value.
No.
Parameter Name
Setting Range
Default
T1-02
Motor Rated Power
0 to 10
5.3 kW
■ T1-03: Motor Rated Voltage
It sets the motor rated voltage according to the motor nameplate value.
No.
Parameter Name
Setting Range
Default
T1-03
Motor Rated Voltage
0 to 380
380 V
■ T1-04: Motor Rated Current
It sets the motor rated current according to the motor nameplate value. Enter the current at the motor
base speed.
No.
Parameter Name
Setting Range
Default
T1-04
Motor Rated Current
2 to 24 A
12 A
■ T1-05: Motor Base Frequency
It sets the motor rated frequency according to the motor nameplate value.
No.
Parameter Name
Setting Range
Default
T1-05
Motor Base Frequency
0 to 50 Hz
50 Hz
■ T1-06: Number of Motor Poles
It sets the number of motor poles according to the motor nameplate value.
No.
Parameter Name
Setting Range
Default
T1-06
Number of Motor Poles
2 to 48
4
■ T1-07: Motor Base Speed
It sets the motor rated speed according to the motor nameplate value.
No.
Parameter Name
Setting Range
Default
T1-07
Motor Base Speed
300 to 3000 rpm
1380 rpm
■ T1-08: Encoder resolution (pulses per revolution)
It sets the number of pulses from the PG encoder. Set the actual number of pulses for one full motor
rotation.
No.
Parameter Name
Setting Range
Default
T1-08
Encoder number of Pulses Per Revolution
0 to 30000 ppr
2048

14
Chapter 2: Parameter Details
A: Initialization
The initialization group contains parameters associated with the initial setup of the drive. Parameters
involving the initialization and control method are located in this group.
■ A1-02: Control Method Selection
Selects the Control Method (also referred to as the control mode) that the drive uses to operate the
motor.
No.
Parameter Name
Setting range
Default
A1-02
Control Method Selection
0,2,3
2
Setting 0: V/f Control for Induction Motors
Use this mode for simple speed control. This method sets the output voltage based on the motor
voltage-frequency curve.
Setting 2: Open-Loop Control
Use this mode for general applications that require more precise speed control and quicker torque
response than V/f.
Setting 3: Closed-Loop Control
Use this mode to drive an induction motor with encoder feedback. This mode offers high-performance
control down to 0 rpm motor speed.
■ A1-03: Factory Reset
Resets parameters back to their default values.
No.
Parameter Name
Setting range
Default
A1-03
Factory Reset
0,1
0
Setting 0: No Function
Setting 1: Factory Reset
b: Application
b1: Operation Mode Selection
■ b1-02: Up/Down Command Selection
Determines the Up/Down command source in the REMOTE mode. Wire the motor so the elevator
goes up when an Up command is issued.
No.
Parameter Name
Setting Range
Default
b1-02
Up/Down Command Selection
0 to 1
1
Setting 0: Operator
Allows the user to enter Up/Down commands from the digital operator. Use this setting when
performing a test run only. In this mode, the speed reference is determined by d1-01.

15
Setting 1: Control Circuit Terminal
Up/Down commands are issued from the control circuit terminals. This is the standard setting used in
most elevator applications.
■ b1-08: Up/Down Command Selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Up/Down command input when the
digital operator is being used to adjust a parameter in the Programming Mode (Verify Menu, Setup
Mode, and Auto-Tuning Mode). If required by the application, set b1-08 to allow the drive to run
while in the Programming Mode.
No.
Parameter Name
Setting Range
Default
b1-08
Up/Down Command Selection while in
Programming Mode
0 to 2
0
Setting 0: Disabled
A Up/Down command is not accepted while the digital operator is in the Programming Mode.
Setting 1: Enabled
A Up/Down command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The
Programming Mode cannot be displayed during Run.
■ b3-01: Detection light load direction
Enable or disable light load experiment
No.
Parameter Name
Setting Range
Default
b3-01
Detection light load direction
0 , 1
1
Setting 0: Disable
If this parameter is set to 0, the drive will move in the direction that has been issued from the control
center, while the drive itself is in rescue mode and the light load orientation detection test no longer
will be performed by the drive in this situation.
Setting 1: Enable
If this parameter is set to 1, the driver will perform a light load direction test in rescue mode. Any
direction command issued from the control center will be ignored by the driver.
C: Tuning
C parameters are used to set the acceleration and deceleration characteristics, as well as jerk. Other
parameters in this group cover setting for torque compensation and PI controller in closed-loop
control.
C1: Acceleration and Deceleration Ramps
■ C1-01 to C1-04 and C1-09: Accel, Decel Ramps 1 and 2 and Fast Stop Ramp
Five parameters can be set in the drive for tuning acceleration and deceleration ramp. Acceleration
ramp parameters always set the ramp or time to accelerate from 0 to the maximum speed.
Deceleration ramp parameters always set the ramp or time to decelerate from the maximum speed to
0.
In this version (SBT-L450U), C1-01 is used for acceleration time. C1-02 is used when the motor
decelerates from any speed to any other speed (except nominal and leveling speed to zero speed). C1-

16
04 is used when the motor decelerates from leveling speed to zero speed. C1-09 determines the
deceleration ramp from nominal speed to zero speed.
Note 1: If C1-02=0, drive coast to stop
Note 2: If C1-04=0, deceleration from leveling speed will be set according to the value set in
C1-02.
Note 3: By setting C1-09 to zero, if the motor speed shifts from its nominal speed, the drive
immediately applies the brake and coasts to stop.
No.
Parameter Name
Application
Setting Range
Default
C1-01
Acceleration Ramp 1
Any speed to any speed
0.00 to 180.00 s
4
C1-02
Deceleration Ramp 1
Any speed to any speed
(Except nominal and
leveling speed to zero
speed)
2
C1-04
Deceleration Ramp 2
Leveling speed to zero
speed
2
C1-09
Fast Stop Ramp
Nominal speed to zero
speed
0
C1-15: Inspection Deceleration Ramp
Sets the deceleration ramp during Inspection Run. If this parameter is set to 0s, the drive coasts to
stop.
No.
Parameter Name
Setting Range
Default
C1-15
Inspection Deceleration Ramp
0.00 to 2.00 s
0.00 s
C2: Jerk Settings
Jerk settings set the transition between acceleration rates. Adjust them to smooth out jerks or shocks
that occur when the speed is changing.
■ C2-01 to C2-05: Jerk Settings
C2-01 through C2-05 set separate jerks for each section of the acceleration or deceleration.
No.
Parameter Name
Setting Range
Default
C2-01
Jerk at Accel start
0 to 7
4
C2-02
Jerk at Accel end
C2-03
Jerk at Decel start
C2-04
Jerk at Decel end
C2-05
Jerk at leveling speed
Figure 2.1: Jerk Settings

17
The transition time between accelerating and decelerating ramps is expressed by discrete numbers in
SBT-L450U. Eight S-curve settings are available, and are expressed as below:
0: No S Curve
1: Very low
2: Low
3: Intermediate 1
4: Intermediate 2
5: Intermediate 3
6: High
7: Very high
Adjusting low numbers leads to shock while high numbers slow the operation. The optimum
operation can be obtained by setting these parameters to 3 or 4.
C4: Torque Compensation
The torque compensation function compensates for insufficient torque production at start-up or when
a load is applied.
Note: Set the motor parameters (E2-**) and V/f pattern properly before setting torque compensation
parameters.
C4-01: Torque Compensation Gain
Sets the gain for the torque compensation function.
No.
Parameter Name
Setting Range
Default
C4-01
Torque Compensation Gain
0.00 to 5.00
1.5
Adjustment
Although this parameter rarely needs to be changed, it may be necessary to adjust the torque
compensation gain in small steps of 0.05 in the following situations:
• Increase this setting when using a long motor cable, or when the starting torque is not high enough
to accelerate the motor.
• Decrease this setting when motor oscillation occurs.
Adjust C4-01 so that the output current does not exceed the drive rated current.
■ C4-02: Torque Compensation Primary Delay Time
It Sets the delay time used for applying torque compensation.
No.
Parameter Name
Setting Range
Default
C4-02
Torque Compensation Primary Delay Time
0.0 to 2000.0 ms
600.0 ms
Adjustment
Although C4-02 rarely needs to be changed, adjustments may be necessary in the following situations:
• Increase this setting if the motor vibrates.
• Decrease this setting if the motor responds too slowly to changes in the load.
C5: Speed Control Loop
These parameters are accessible only in the closed-loop control mode (A1-02=3).
The Speed control Loop Controls the motor speed in CLV and CLV/PM control modes. It adjusts
torque reference in order to minimize the difference between speed reference and actual motor speed.
The speed control block diagram has been shown in fig2.2.

18
Figure 2.2: Speed Control Block Diagram
■ C5-01, C5-03, C5-13 / C5-02, C5-04, C5-14: Speed Control Loop Proportional Gain 1,
2, 3 / Speed Control Loop Integral Time 1, 2, 3
These parameters can be used to adjust the responsiveness of the Speed Control Loop.
No.
Parameter Name
Setting Range
Default
C5-01
Speed Control Loop Proportional Gain 1
0 to 255
2
C5-02
Speed Control Loop Integral Time 1
0 to 8191ms
1000ms
C5-03
Speed Control Loop Proportional Gain 2
0 to 255
15
C5-04
Speed Control Loop Integral Time 2
0 to 8191ms
1000ms
C5-13
Speed Control Loop Proportional Gain 3
0 to 255
15
C5-14
Speed Control Loop Integral Time 3
0 to 8191ms
1000ms
It is important to change the coefficients of the speed controllers properly in order to drive the motor
in a soft and smooth way. The accelerating procedure of P and I coefficients for start and stop modes
are shown in Fig. 2-3, (a) and (b) respectively.
(a)
(b)
Figure 2.3 Settings at Low and High Speed during Acceleration
■ C5-06: Speed Control Loop Primary Delay Time Constant

19
This parameter sets the filter time constant for the time from the speed loop to the torque command
output. Increase this setting gradually in increments of 0.01 for loads with low rigidity, or when
oscillation is a problem. The excessive increase of this parameter will cause problems.
No.
Parameter Name
Setting Range
Default
C5-06
Speed Control Loop Primary Delay Time Constant
0 to 500ms
30ms
■C5-19, C5-20: Speed Control Loop P Gain Time, I Time during Position Lock
These two parameters are used to adjust the responsiveness of Speed Control Loop during Position
Lock. Incorrect adjustment causes a rollback after the brake releases or motor oscillation.
No.
Parameter Name
Setting Range
Default
C5-19
Speed Control Loop Proportional Gain Time during Position
Lock
0 to 255
3
C5-20
Speed Control Loop Integral Time during Position Lock
0 to 8191ms
300ms
d: Reference Settings
The d family parameters determine the speed of the elevator including the speed reference.
d1: Speed Reference
The parameters of this family adjust the reference speed of the drive in different conditions.
d1-01 to d1-08: Speed References 1 to 8
The drive lets the user switch between 8 preset frequency references during run by using the digital
input terminals.
No.
Parameter Name
Setting Range
Default
d1-01
Speed Reference 1
0.00 to E1-04 Hz
10 Hz
d1-02
Speed Reference 2
0 Hz
d1-03
Speed Reference 3
d1-04
Speed Reference 4
d1-05
Speed Reference 5
d1-06
Speed Reference 6
d1-07
Speed Reference 7
d1-08
Speed Reference 8
Multi-Step Speed Selection
To use several speed references for a multi-step speed sequence, set the H1-** parameters to 0,1,2.
Reference
Multi-step Speed
1
H1-
**
=0
Multi-step Speed
2
H1-
**
=1
Multi-step Speed
3
H1-
**
=2
Frequency Reference 1
OFF
OFF
OFF
Frequency Reference 2
ON
OFF
OFF
Frequency Reference 3
OFF
ON
OFF
Frequency Reference 4
ON
ON
OFF
Frequency Reference 5
OFF
OFF
ON
Frequency Reference 6
ON
OFF
ON
Frequency Reference 7
OFF
ON
ON
Frequency Reference 8
ON
ON
ON
■ d1-17: JOG Speed Selection
This parameter adjusts the speed that is related to JOG.
No.
Parameter Name
Setting Range
Default
d1-17
JOG Speed
0 to E1-04
0Hz

20
■ d1-18: Speed Reference Selection Mode
This parameter sets the priority of the speed reference inputs.
NOTICE: Always turn off the RUN command before changing the setting of parameters d1-18 (Speed Reference
Selection Mode), d1- 01 (Speed Reference Selection).If the RUN command is on, when changing any of these
settings, the motor may unexpectedly start running and could result in injury.
No.
Parameter Name
Setting Range
Default
d1-18
Speed Reference Selection Mode
0 to 2
1
Setting 0: Use multi-speed references d1-01 to d1-08
These parameters set speed references 1 through 8. Each of these speed reference values can be
selected using digital inputs programmed for multi-speed selection(H1-**).
Setting 1: High-speed reference has priority
Four different speed parameters (d1-19, d1-20, d1-24, d1-26) can be programmed. If any of these
speed parameters and leveling speed, activated at the same time, speed parameters have priorities over
leveling speed parameter.
Setting 2: Low-speed reference has priority
Four different speed parameters (d1-19, d1-20, d1-24, d1-26) can be programmed. If any of these
speed parameters and leveling speed, activated at the same time, the leveling speed has priority over
speed parameters.
■ d1-19: Nominal Speed
Sets the nominal speed, and it is used as the motor reference speed when a digital command for the
Nominal input terminal is issued(H1-**=6).
No.
Parameter Name
Setting Range
Default
d1-19
Nominal Speed
0.00 to E1-04
47 Hz
■ d1-20: Intermediate Speed
Sets intermediate speed.
No.
Parameter Name
Setting Range
Default
d1-20
Intermediate Speed
0.00 to 50.00 Hz
30.00 Hz
■ d1-24: Inspection Operation Speed
It sets the inspection speed, and it is used as the motor reference speed when a digital command for
the Inspection input terminal is issued.
No.
Parameter Name
Setting Range
Default
d1-24
Inspection Operation Speed
0.00 to 50.00 Hz
15.00 Hz
■ d1-25: Rescue Operation Speed
While digital input has been set to rescue mode (H1-**=10), this parameter determines the speed
during Rescue Operation.
No.
Parameter Name
Setting Range
Default
d1-25
Rescue Operation Speed
0 to E1-04
5Hz
■ d1-26: Leveling Speed
It sets the Leveling speed, and it is used as the motor reference speed when a digital command for the
Leveling input terminal is issued.
No.
Parameter Name
Setting Range
Default
d1-26
Leveling Speed
0.00 to 50.00 Hz
5.00 Hz
E: Motor Parameters
E parameters cover V/f pattern and motor data settings.

21
NOTICE: In closed-loop mode (A1-02=3),
only frequency and nominal voltage (E1-04, E1-05) are Customizable,
which after the auto-tuning, they will be adjusted by the drive automatically.
E1: V/f Pattern
■ E1-02: V/f Mode
No.
Parameter Name
Setting Range
Default
E1-02
V/f Mode
0 to 3
3
Setting 0: Normal V/f
In this mode, the drive uses V/f curve based on Maximum Voltage (E1-05) and Maximum frequency
(E1-04). In all reference speeds, this ratio is kept constant.
Setting 1: Torque Compensation
In this mode, the torque is increased to prevent motor stall under heavy loads.
Setting 2: Manual Curve
In this mode, the user can adjust the voltage-speed curve by setting parameters E1-05 through E1-13.
Be careful to set these parameters correctly, otherwise, the motor will show unexpected behavior or
overload fault will occur due to the saturation of the motor magnetic core.
Setting 3: Boost Manual Curve (Recommended)
In this mode, the voltage-speed curve is set according to parameters E1-05 through E1-13, and
starting torque is increased to prevent motor stall under heavy loads. Besides, voltage offset could be
added to all points in the curve by using E1-03. The voltages-speed curve will be according to Fig.
2.2. Use this option when the motor is under heavy loads, or high starting torque is required.
■ E1-03: Voltage Offset
No.
Parameter Name
Setting Range
Default
E1-03
Voltage Offset
0V to 50V
0V
The voltage-speed curve set by parameters E1-05 through E1-13 could be further modified by adding
a constant voltage. The amount of added voltage could be set in E1-03. If the motor stalls, increase
voltage offset to increase the torque. Note that E1-03 is used when E1-02 is set to 3 or 1.
■ V/f Pattern Settings E1-04 to E1-13
No.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
0 to 50Hz
50 Hz
E1-05
Maximum Voltage
0.0 to 380.0 V
380.0 V
E1-06
Voltage at 16/32 Max Frequency
0.0 to 380.0 V
167V
E1-07
Voltage at 12/32 Max Frequency
0.0 to 380.0 V
121 V
E1-08
Voltage at 10/32 Max Frequency
0.0 to 380.0 V
92 V
E1-09
Voltage at 8/32 Max Frequency
0.0 to 380.0 V
75 V
E1-10
Voltage at 6/32 Max Frequency
0.0 to 380.0 V
55 V
E1-11
Voltage at 5/32 Max Frequency
0.0 to 380.0 V
45 V
E1-12
Voltage at 4/32 Max Frequency
0.0 to 380.0 V
35 V
E1-13
Voltage at 3/32 Max Frequency
0.0 to 380.0 V
25V

22
Figure 2.2 Manual V/f curve
E2: Motor Parameters
These parameters contain the motor data for induction motors. They are set automatically when Auto-
Tuning is performed.
■ E2-01: Motor Rated Current
Used to protect the motor and calculate drive control parameters. Set E2-01 to the full load amps
(FLA) stamped on the motor nameplate. If Auto-Tuning completes successfully, the value entered to
T1-04 will automatically be saved to E2-01.
No.
Parameter Name
Setting Range
Default
E2-01
Motor Rated Current
2 to 18A
14A
■ E2-02: Motor Rated Slip
Sets the motor rated slip in Hz to protect the motor and calculate drive control parameters. This value
is automatically set during Auto-Tuning.
No.
Parameter Name
Setting Range
Default
E2-02
Motor Rated Slip
0.00 to 20.00 Hz
4 Hz
■ E2-03: Motor No-Load Current
Sets the no-load current for the motor in amperes when operating at the rated frequency. The drive
sets E2-03 during the Auto-Tuning process. Please note that if this parameter is set to 0, output phase
loss fault detection will be disabled.
No.
Parameter Name
Setting Range
Default
E2-03
Motor No-Load Current
0 to18A
4A
■ E2-04: Number of Motor Poles
Sets the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to
T1-06 will automatically be saved to E2-04.
No.
Parameter Name
Setting Range
Default
E2-03
Number of motor poles
2 to 48
4
■ E2-05: Motor Line-to-Line Resistance
Sets the line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully,
this value is automatically calculated. Enter this value as line-to-line and not for each motor phase.
No.
Parameter Name
Setting Range
Default
E2-05
Motor Line-to-Line Resistance
0.000 to 5.000 Ω
2.7 Ω
Voffset (E1-03)
E1-13
E1-12
E1-11
E1-10
E1-09
E1-08
E1-07
E1-06
E1-05
E1-04
(fmax)
16/3212/32 10/328/32
6/32
5/32
4/32
3/32
Voltage(V)
f (Hz)
This manual suits for next models
1
Table of contents