Programmable S81-HS system Installation and user manual
Page 1of 3
S81-F7009-1
Description
Control card for addressable devices using XP95/Discovery Apollo protocol. This card can
control up to a maximum of 127 fire detection devices including : smoke, heat, combined
detectors, alarm buttons, control modules, visual and audible alarm devices.
Technical features
Redundancy: No
Number of devices per loop 127
Loop maximum current 400mA
Supply voltage: 22-29Vdc
Quiescent current: 90mA
Operating temperature: -5 / +50 °C
Storage temperature: -30 / +80 °C
Maximum humidity: 95% (RH) non condensing
Hot swap capability: yes
Status Indications
The front panel includes 8 LEDs with the following functions:
Steady on if an input is under alarmed/activated condition
Steady on if an input or an output is disabled
Flashing in case of Fault condition
Flashing in case of loop short circuit or open loop
Flashing in case of difference between the detected devices and the programmed ones.
Flashing in case of in case of smoke detectors with dirty lenses
It lights up every time data are transmitted from the module to loop devices.
It lights up every time data from loop devices are received
Configuration
By using the configuration program ProS81, the following parameters can be set for each point of the single
devices, according to the relevant type:
Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-
NC
5 sensitivity levels to be selected
Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Continuous-Normally Energised, Continuous-Normally De-
energised, Intermittent, Pulsing
1 to 15 seconds
(only for pulsing and intermittent modes)
Normal / Sounder
15 selectable tones
7 selectable volume levels
Enable/Disable LED lighting up during polling
Enable/Disable status export to
Hosts
Enable/Disable commands
from Hosts on the channel