Settings Procedure
Settings List
Settings
1. Hold the SET key to enter the settings menu. If password protection is active, enter the
correct password. The group of settings displays on the display.
2. Select the group by using the up and down keys and press the SET key to view the
selected group.
3. Using the up and down keys select the parameter you wish to adjust and press the SET
key to view the selected parameter. The adjustable parameter blinks.
4. With the up and down keys, adjust the parameter value. Press SET to enter the new
value and move to the next parameter.
5. Exiting the settings menu: hold down the SET key to move back one level. The anemom-
eter also returns to the main screen after 2 minutes of inactivity.
Max Alarm
Pre Alarm 2
Pre Alarm 1
No Signal/WD alarm
General
Relay 1, RED ALARM LIGHT
Relay 2, YELOW ALARM LIGHT
Relay 3
Relay 4
select to set Max Alarm parameters
select to set Pre Alarm 2 parameters
select to set Pre Alarm 1 parameters
select to set No Signal / Wind Direction alarm parameters
select to set general parameters
12-24V
RELAY
4
RELAY
3
RELAY
2
RELAY
1
DC
4-20 mA
4-20 mA
12-24V
DC
mA
mA
WS WD
Settings: Max Alarm (Relay 1, RED ALARM LIGHT, continuous sound)
Settings: Pre Alarm 2 (Relay 2, YELOW ALARM LIGHT, interrupted sound)
Settings: Pre Alarm 1 (Relay 3)
Wind Speed:
ON Delay:
OFF Delay:
Relay:
Wind Speed:
ON Delay:
OFF Delay:
Relay:
Factory preset:
72 km/h
0 s
0 min
Normal
Factory preset:
52 km/h
0 s
0 min
Normal
Setting range:
1 - 50 m/s
0 - 600 s
0 - 60 min
Normal/Inverted
Description:
Max Alarm limit
Minimum time for excess wind speed to activate the Max alarm
Alarm switch OFF delay after wind speed drops below preset level
Inverted operation of relay
Setting range:
1 - 50 m/s
0 - 600 s
0 - 60 min
Normal/Inverted
Description:
Pre Alarm 2 limit
Minimum time of exceed Wind speed to activate the Pre Alarm 2
Alarm switch OFF delay after wind speed drop below preset level
Inverted operation of relay
Wind Speed:
ON Delay:
OFF Delay:
Relay:
Factory preset:
42 km/h
0 s
0 min
Normal
Setting range:
1 - 50 m/s
0 - 600 s
0 - 60 min
Normal/Inverted
Description:
Pre Alarm 1 limit
Minimum time of exceed Wind speed to activate the Pre Alarm 1
Alarm switch OFF delay after wind speed drop below preset level
Inverted operation of relay
Settings: No Signal / Wind Direction Alarm (Relay 4)
Alarm:
Relay:
Zone1:
Zone2:
ON Delay:
OFF Delay:
Factory preset:
No Signal
Normal
315°-45°
135°-225°
0 s
0 min
Setting range:
No Signal / Direction
Normal/Inverted
0°-359°
0°-359°
0 - 600 s
0 - 60 min
Description:
Type of Alarm: No signal alarm or wind direction alarm
Inverted operation of relay
Zone of wind direction alarm ON
Zone of wind direction alarm ON
Minimum time of wind direction inside the alarm zone to activate
the alarm
Alarm switch OFF delay after wind direction leaves the alarm zone