SCC MAM-200 User manual

Compressor Controller
MAM – 200
OPERATION MANUAL
Revision 1.0
04.08.2017

04.08.2017 Operation Manual MAM - 200 V1.0
2
Notice
Please read all the operation manual before operating the set and keep this manual for further reference.
Installation of MAM—8** compressor controller can be performed only by professional technicians.
RC snubber must be connected to the two terminals of coil (such as AC contactor, valve, etc),which are controlled
by relay output.
Port connection shall be inspected carefully before power on.
PARAMETER is not allowed to be modified in running and stop delay status. Only user
parameter is allowed to be changed at running status

04.08.2017 Operation Manual MAM - 200 V1.0
3
Contents
1. Basic Operations ......................................................................................................................................................... 4
1.1 Button Explanation .................................................................................................................................................. 4
1.2 Status Display and Operations ................................................................................................................................ 6
1.3 Operating Parmeter and Menu ............................................................................................................................... 7
1.4 Calendar .................................................................................................................................................................. 7
1.5 Custom parameter .................................................................................................................................................. 8
2 Controller Function and Technical Parameter ............................................................................................................ 13
3 Model and Specification ............................................................................................................................................. 14
4 Alarm Function ........................................................................................................................................................... 16
5 Controller Protection .................................................................................................................................................. 17
6 Troubleshooting .......................................................................................................................................................... 18
7 Sequence Mode Control and Network ....................................................................................................................... 20
7.1 Sequence Mode Control .................................................................................................................................... 20
7.2 Sequence Mode Setting ..................................................................................................................................... 21
7.2.1 Set as Master .................................................................................................................................................. 21
7.2.2. Set as Slave .................................................................................................................................................... 22
7.3 Start, Stop Sequence Control: ............................................................................................................................ 22
7.4 Sequence Communication Receiving and Sending Message: ............................................................................ 22
7.5 Network ............................................................................................................................................................. 23
8 Copyright .................................................................................................................................................................... 24

04.08.2017 Operation Manual MAM - 200 V1.0
4
1. Basic Operations
1.1 Button Explanation
Start button
When compressor is at stop status, press this button to start the compressor
When compressor is set as main (No. 1) in block mode, press this button to start the compressor and activate
block mode function at the same time
Stop button
When the compressor is at running status, press this button to stop the compressor
When compressor is set as main (No. 1) in block mode, press this button to stop compressor and block mode
as well
Loading / Unloading button
When the compressor is at running status, press this button to load or unload
Set button
When the compressor is at setting mode, press this button after modification to confirm and save the
modified data
Press this button after input password to verify the password

04.08.2017 Operation Manual MAM - 200 V1.0
5
Move down button / Decreasing button
When viewing the menu, press this button to move downward the cursor
When modifying data, press this button to decrease the data at current position
Move up button / Increasing button
When viewing the menu, press this button to move upward the cursor
When modifying data, press this button to increase the data at current position
Shift button / Enter button
When modifying data, press this button to move to the next data bit
When select menu, press this button to switch to sub menu. If no sub menu available, the controller will shift
to data setting mode
Return button / Reset button
When modifying data, press this button to exist data setting mode
When viewing the menu, press this button to return to prevorious menu
When the controller is at failure stop status, long press this button to reset

04.08.2017 Operation Manual MAM - 200 V1.0
6
1.2 Status Display and Operations
The Display screen will show as below after powered on:
After 5 seconds the menu will switch as below:
Press to enter into selection menu:
RUN PARAMETER
CALENDAR
CUSTOMER PARAMETER
FACTORY PRAMETER

04.08.2017 Operation Manual MAM - 200 V1.0
7
1.3 Operating Parmeter and Menu
Press or to move the cursor to “RUN PARAMETER”, then press to switch to secondary menu:
Move the cursor to “HOST, FAN CURR”, press to switch to secondary menu:
Press to return to the prevorious menu or main menu. If no operation at the current menu for 120seconds,
controller will automatically return to the main menu and turn off the back light simultaneously.
According to above method, use move down button , move up button , enter button ,
and return button to check TOTAL RUN TIME, THIS RUN TIME, VSD PARAMETER,
MAINTENANCE PARAMTER, FAULT RECORD, PROD DATE, SERIAL NUMBER, THIS FAULT and returnto previous
menu.
1.4 Calendar
Check and set time of controller
HOST、FAN CURRENT
TOTAL RUN TIME
CURRENT RUN TIME
MAINTENANCE PARAMETER
CUR(A):R S T
HOST: 56.1 56.2 56.0
FAN: 4.1 4.1 4.1
DATE AND TIME
2017 - 2 - 22
WEEK 0
12 H 46 M 59 S

04.08.2017 Operation Manual MAM - 200 V1.0
8
1.5 Custom parameter
1.5.1 Customer Parameter View and Modification
CUSTOMER PARAMETER and FACTORY PARAMETER
are not allowed to be modified in running and stop delay status.
When modifying Customer parameter please refer to run parameter modification method. The modification
process of LOADING P is showing as an example below:
Press or to move the cursor to “CUSTOMER PARAMETER”, then press to switch to secondary
menu
Move the cursor to “SET P, T”, press to switch to secondary menu:
User can check the CUSTOMER PARAMETER in this menu or press to switch to the following menu which
requires an user password input
NOTE: Customer password can be set in CUSTOMER PARAMETER
and FACTORY PARAMETER is fixed as ____________
SET P、T
ON/OFF DELAY PRESET
OP. MODE PRESET
BLCK PARA PRESET
LOADING P: 0.8MPa
UNLOADING P: 0.6MPa
FAN START T: 80
℃
FAN STOP T: 70
℃
ENTER PASSWORD
****

04.08.2017 Operation Manual MAM - 200 V1.0
9
In this menu the first data bit of password blinking, press or to modify the first bit of password.
Press move the cursor to the next data bit, modify the second data bit of password in accordeance with the above.
Modify the the third and fourth data of password in sequence, press to confirm the input data and the menu will
switch to the following menu after verification.
The upper right corner with “*”
indicates the system verification
of the password
In the menu above press , the first data of LOADING P start to blink, user can press or to modify the
present data in accordance with the above method. Press to move to next data bit and modify the target data in
sequence. When finished press to confirm and save the data. Other CUSTOMER PARAMETER share the similar way for
modification.
BLOCK LOAD P: 0.8MPa *
BLOCK UNLOAD P: 0.6MPa
FAN START T: 80
℃
FAN STOP T: 70
℃

04.08.2017 Operation Manual MAM - 200 V1.0
10
1.5.2 Customer Parameter Table and Function
First
Submenu
Second
Submenu Preset Value
Functions
Set P / T / VF
LOADING P 0,65 MPa
1
.
In AUTO LOADING status, compressor will load if pressure is below this
set data
2. In STANDBY mode, compressor will start if the pressure below this set
data
UNLOAD P 0,80 MPa
1
.
Compressor will unload automatically if air
pressure is above this set
data
2.This data should be set above LOADING P, also should be set below UNLD
P LIM
FAN START 0080
℃
Fan will start if AIR T is above this set data
FAN STOP 0070
℃
Fan will start if AIR T is above this set data
VF WORKING 0,70MPa
Set AIR P for VSD compressor to keep running
stable, when pressure is
fluctuated around this data, controller will adjust operation frequency of
inverter to control the pressure close to this data
RATED POWER 015kW Set RATED POWER in order to calculate actual power
RATED SPEED 2600RPM Set RATED SPEED at 50HZ in order to calculate the actual speed in variable
frequency
SET TIME
HOST START TIME 0008s
Set the HOST START TIME. Record time
when motor is activated, controller
will not start overload protection during this time to avoid impulse starting
current stopping the motor.
FAN START TIME 0003s
Set the FAN START TIME. Record time when fan is activated, controller will
not start overload protection during this time to avoid impulse starting
current stopping the fan
STAR DELAY TIME 0006S Interval time from star to delta
LOAD DELAY TIME 0002S Unloading in this set time after enter delta running
EMPTY DELAY TIME 0600S When unloading continuously, compressor will automatically stop and
enter to standby status if over this set time
STOP DELAY TIME 0010S For NORMAL STOP operation, compressor will stop after it continuously
unloading over this set time
START DELAY TIME 0100S Machine cannot be restarted before this set time (stop and over time load
free stop till this time)
VSD UP SPEED 0100 Restrict PID calculations in case the frequency increasing too fast which
cause motor speeding up too fast
VSD DN SPEED 0100 Restrict PID calculations in case the frequency decreasing too fast which
cause motor slowing down too fast
Operation mode
preset
ON/OFF MODE Near / Far
NEAR: only the button on the controller can turn on and turn off the
machine.
FAR: both the button on the controller and
the remote-control button can turn on and turn off the machine;
LOAD MODE Auto/
Manual
Manual
:
O
nly when the pressure is above
Unload P, compressor will
unload automatically. For any other case, the Load/Unload function can
only be executed by pressing “load/unload” key.
AUTOMATICAL: the load/unload function can be executed by the
fluctuation of AIR P automatically
COM MODE
Computer
Block
Prohibited
Prohibited: communication function is
not
activated.
COMPUTER: compressor can communicate with computer or DCS as slave
according to MODBUS-RTU.
BLOCK: compressors can work in a net
COM ADRESS 0255 Communication address
Blocking
parameter
preset
BLOCK STATE Main/
Slave
1.When service as m
aster in BLOCK, master
controls slave; the COM ADD should be set as No.1
2.When service as slave in BLOCK, slave is
controlled by master

04.08.2017 Operation Manual MAM - 200 V1.0
11
BLOCK ON/OFF Alone/
Order
TURN TIME 99 Hours
When master pressure is between BLOCK LOAD P and BLOCK UNLD P,
master determines slave to work alternatively after
working over this set time
BLOCK NUMBER 0016 Number of air compressors in block net
BLOCK LOAD P *.**MPa In BLOCK mode, one compressor will start or load when master AIR P is
below this set data
BLOCK UNLOAD P *.**MPa In BLOCK mode, one compressor will stop or unload when master AIR P is
above this set Data
BLOCK DELAY 200S In BLOCK mode, when master sends two commands continuously, second
command signal delays for this set data
Maintenance
parameter
preset
OIL FILTER RESET 0000 HOURS Record total running time of OIL filter. If changing new oil filter, the data
should be reset by manual operation.
O/A RESET 0000Hours Record total running time of O/A filter. If changing new O/A separator, the
data should be reset by manual operation.
AIR FILTER RESET 0000Hours Record total running time of AIR filter. If changing new air filter, the data
should be reset by manual operation.
LUB OIL RESET 0000Hours Record total running time of LUB OIL. If changing new lubricating oil, the
data should be reset by manual operation.
LUB GREASE RESET 0000Hours Record total running time of LUB GREASE. If changing new grease, the data
should be reset by manual operation.
Max. life time
preset
OIL FILTER 9999Hours
1. Alarm prompt when total running time of oil filter is above the set data
2. Set this data to “0000”, alarm function for
oil filter running time is not activated
O/A SEPARATOR 9999Hours
1
.
Alarm prompt when total running time of
O/A separator is above the
set
data.
2. Set this data to “0000”, alarm function for O/A separator running time is
not activated
AIR FILTER 9999Hours
1. Alarm prompt when total running time of air filter is above the set data.
2. Set this data to “0000”, alarm function for air filter running time is not
activated
LUB. OIL 9999Hours
1
.
Alarm prompt when total running time of
lubricant is above the set
data.
2. Set this data to “0000”, alarm function for lubricant running time is not
activated.
LUB GREASE 9999Hours
1. Alarm prompt when total running time of grease is above the set data.
2. Set this data to “0” , alarm function for grease running time is not
activated
Language
display English Change the display language.
User password
modification
****
User could modify the us
er password by old
user password or factory
password

04.08.2017 Operation Manual MAM - 200 V1.0
12
1.5.3 Factory Parameter
The view and modification of factory parameter requires a factory password, The modification step is
same as customer parameter modification. Main function is as below:
Menu Initial Value
Functions
HOST RATED CURRENT After the starting delay time, when the motor current is greater than 1.2 times of the set
value and less than 4 times of the set value, the unit will jump as per overload feature.
FAN RATED CURRENT Same as above
PRE-ALARM T 105
℃
Pre-alarm when the temperature reaches this set value
STOP T 110
℃
Alarm when the air exhausting temperature reaches this set value.
STOP P 1.00MPa Alarm and stop the machine when the air supply temperature reaches this set value
UNLOAD P. UPPER LIMIT 0.80MPa The Unload Limit Pressure in the Customer Parameter must be set lower than this value.
LOAD TIME ****Hours Total load time
TOTAL TIME ****Hours Total run time
HISTORY FAULT RESET **** Input the history failure password to clear all the history failures.
UNBALANCE SCOPE 0006
When (the max. phase current / min. phase current) is greater than (1+set value), the
unbalance protection will stop the machine. If the set value is greater than 15, the
unbalance protection will be unavailable.
LACK PHASE PROTECTION 0005 Set the LACK PHASE TIME ≥20S, the Lack phase protection will be disabled
RUN MODE VF
Commercial F
VF: Inverter will run
Commercial F: Star-delta will run

04.08.2017 Operation Manual MAM - 200 V1.0
13
1.6 Operating Authorization and Password
Controller provides multiple passwords and access management. According to different levels of passwords,
controller provides different levels of operating authorization. Details are as following:
Customer Password: factory set ____________
Permissions: Allows to modify all Customer Parameter
Factory Password: fixed ____________
Permissions: Allows user to modify all Parameter
2 Controller Function and Technical Parameter
Phase sequence protection:
When compressor is at stop mode an detects open phase, response time <2ms
Open phase protection
When any phase opens, the response time equals to set time: This fuinction is not activated when OPEN PHASE
PROTECTION time iss et over 20s
Motor protection: This control unit has the following 5 basic protection functions to the motor and fan.
o Rotor lock protection: After the starting oft he motor, if the working current reaches 4 or 8 times oft he set
value, the protection activates. The activate time is less than 0,2s.
o Short.circuit protection: If the detected current reaches 8times or more above the set value, the protection
activates, the activate time is less then 0,2s
o Lack phase protection: Any oft the phase lack, the protection activates and theactivate time ist he setting
time
o Unbalance protection: The current difference between any of the two phases reaches the percentage of the
setting value, the protection activates and the activate time is less than 5s.
o Protection features of overload, please see following table for your reference. Multiple=Iactual/Iset ,
response time is shown in following table according to overload multiples from 1.2 times an 3.0times.
Iact/Iset
Time Para
≥1.2 ≥1.3 ≥1.5 ≥1.6 ≥2.0 ≥3.0
response time (s) 60 48 24 8 5 1

04.08.2017 Operation Manual MAM - 200 V1.0
14
3 Model and Specification
Main controller model description
MAM - KY02 S (40) (B) (T)
T:RS—485 communication
B:Transformer; K:Pressure Switch
Matched Host Maximum nominal working current
S:Screw type Air compressor
02 type air compressor controller(LCD)
Products Series
Power consumption table for corresponding motor
Parameter
Spec. Current Range
(A)
Adopted H
ost
Motor Power
(KW)
Remarks Descriptions
MAM—KY02S(20) 8~20 4~10
Fan has three levels of
current. Such as 0.2-2.5A,
1-5A and 4-10A,
determined by current of
motor.
MAM—KY02S(40) 16~40 8~20
MAM—KY02S(100) 30~100 15~50
MAM—KY02S(200) 80~200 40~100
MAM—KY02S(400) 160~400 80~200
MAM—KY02S(600/5) 100~600 50~300 Connect to
CT

04.08.2017 Operation Manual MAM - 200 V1.0
15
Electrical basic wiring installation
Attention: the magnetic coil must be connected to the surging absorber when wiring

04.08.2017 Operation Manual MAM - 200 V1.0
16
4 Alarm Function
4.1 Monitor text
4.1.1 Air Filter Alarm
1. Use switching signal to detect alarm
The monitor displays AIR FILTER BLOCK by checking air filter differential pressure switch
2. Set AIR filter max. time
The monitor displays AIR LIFE END when the run time of air filter exhausts
4.1.2 Oil Filter Alarm
1. Use switching signal to detect alarm
The monitor displays OIL FILTER BLOCK by checking oil filter differential pressure switch
2. Set OIL filter max. time
The monitor displays OIL LIFE END when the run time of the oil filter exhausts
4.1.3 O/A Alarm
1. Use switching signal to detect alarm
The monitor displays O/A BLOCK by checking O/A filter differential pressure switch
2. Set O/A max. time
The monitor displays O/A LIFE END when the run time of the O/A separator exhausts
4.1.4 Lubricating Oil Alarm
The monitor displays LUBE LIFE END when run time of lubrication oil exhausts
4.1.5 Grease Alarm
The monitor displays GREASE LIFE END when run time of the grease exhausts

04.08.2017 Operation Manual MAM - 200 V1.0
17
5 Controller Protection
5.1 Motor Protection
MAM-200 compressor controller provides short circuit, block, overload, lack phase and unbalance protection on
motor.
Electronic
Failure Failure Display Reasons
Short circuit Display “MOTOR / FAN OVERLOAD” Short circuit or wrong current set
Current block Display “MOTOR / FAN BLOCK” Overload, bearing wear off or other mechanical failures
Overload Display “MOTOR / FAN OVERLOAD” Overload, bearing wear off or other mechanical failures
Lack phase Display “MOTOR / FAN LACK PHASE” Power supply, contactor and open phase of motor
Unbalance Display “MOTOR / FAN UNBALANCE” Poor contact of contactor, inside open-loop of motor
5.2 Protection of Air Temperature High
When AIR T is above the STOP DISC T, the controller will alarm and stop the machine.
This fault displays DISC T HIGH
5.3 Protection of Air Compressor Reversal
When the phase sequence of the power connected to the air compressor is not conforming to the set of the
controller, the local failure displays “Wrong phase sequence” and as a result the controller cannot start the motor.
It is needed to check and alternate any two of the phase sequence and investigate the motor rotation direction.
5.4 Protection of Air Pressure High
When the AIR P is above the STOP P, the controller will send out the alarm to shut down the machine and this
fault displays AIR P HIGH
5.5 Protection of Sensor Failure
When the cable of the pressure sensor or the temperature sensor is broken, the controller will alarm and stop the
machine and the local failure displays “** sensor failure”.
5.6 Interlock Protection
The Motor is running and the air exhaust temperature reaches the fan starting temperature but the fan does not
run, the controller alarm, the local failure displays “FAN is stopped”.

04.08.2017 Operation Manual MAM - 200 V1.0
18
6 Troubleshooting
Failure stop caused by the external parts of controllers may be removed by checking this fault or history fault,
method is shown as below.
Press or to move the cursor to “RUN PARAMETER”, then press to switch to secondary menu
Press to move the cursor to “CURRENT FAULT”
Then press to reach the following failure cause:
Check the temperature sensor to confirm if there is any line broken or damage.
MOTORS CURRENT
TOTAL RUN TIME:
CURRENT RUN TIME
MAINTENANCE
HISTORY FAULT
PROD. DATE/NUM
CURRENT FAULT
Temperature sensor Failure
170
℃

04.08.2017 Operation Manual MAM - 200 V1.0
19
User can reset the error according to the following information:
Failure Causes Measurement to take
AIR T HIGH Bad vent condition, Oil lacking etc. Check the vent condition and lubricant amount etc.
AIR T SENSOR FAULT Cable off or PT1OO damaged Checking the wiring and PT100
AIR P HIGH The pressure too high or the pressure
sensor failure Check the pressure and the pressure sensor
AIR P SENSOR FAULT Cable off, Sensor damaged or the cable
connected reversed Check the wiring and sensor transformer
LACK WATER Water Pressure switch damaged Check the water pressure switch
LACK PHASE Power phase lacking or the Contactor
terminal damaged Check the power and contactors
OVERLOAD
Voltage too low, tubes blocked, bearing
wear off or other mechanical failure or
wrong set data etc.
Check the set data, Voltage, bearings, tubes and other
mechanical system.
UNBALANCE Power unbalance, contactor damaged
or the internal open of the motor Check the power, contactors and the motor
BLOCK
Voltage too low, tubes blocked, bearing
wear off or other mechanical failure or
wrong set data etc.
Check the set data, Voltage, bearings, tubes and other
mechanical system.
SHORT CIRCUIT Wrong cable connection, wrong set
data Checking the wiring and set the data correctly
WRONG PHASE SEQUENCE Reversed Phase sequence or phase off Check the wiring
Fan stopped Fan damaged, Contactor damaged, no
control output Check the wiring and control output
Overload or Rotor locking
during starting process
Start time set too less than the star
delta time delay
Reset the host starting time to be longer than star delta delay
+ load delay time
Main Contactor activate time
to time The emergency button loose Check the wiring

04.08.2017 Operation Manual MAM - 200 V1.0
20
7 Sequence Mode Control and Network
7.1 Sequence Mode Control
MAM-860 controller can operate with other MAM series compressor (with communication function). 16 pcs
compressors are allowed in the net at most. The cable connection for block mode is as below….
A B A B A B A B A B
Compressors with net communication address 0001 is master, others are slave. Any one MAM-series compressors can
be set as master or slave
Master 1 Slave 2 Slave 3 Slave 4 Slave 16
Table of contents
Other SCC Controllers manuals
Popular Controllers manuals by other brands

ICON
ICON ProCon C400 Series operating manual

digitalview
digitalview SGX-1920L instructions

KiWi Lighting
KiWi Lighting TopLedLight BY-CON-TC6B-BK manual

Crestron Electronics
Crestron Electronics C2N-SDC Operations & installation guide

CS-Lab
CS-Lab CSMIO IP-S user guide

Oriental motor
Oriental motor AZX Series operating manual