SCC OCI415.30 User manual

SCCInc.
InstallationInstructions
DocumentNo.LV5‐6100
February12,2018
SCCInc.
LMV5Series
OCI415.30
forusewithLMV5...LinkagelessBurnerManagementSystems
OCI415.30
Description
TheOCI415.30providestheLMV5...familyofflamecontrollers
withaModbusRTUorBACnetMS/TPinterface.Thisallowsthe
interconnectionofoneormoreLMV5...toaPLCorbuilding
managementsystem(BMS).

InstallationInstructions LMV5Series
DocumentNo.LV5‐6100
Page2SCCInc.
TableofContents
CompatibleControls...................................................................................................................3
LinkagelessBurnerManagementSystems.........................................................................3
PhysicalConnections..................................................................................................................4
Power..................................................................................................................................4
ConnectiontoLMV5...........................................................................................................4
ConnectiontoBMS.............................................................................................................5
StatusLED...........................................................................................................................5
Tx/RxLED............................................................................................................................5
RequiredLMV5Configuration....................................................................................................6
ModbusRTUConnectionDetails................................................................................................7
BACnetMS/TPConnectionDetails.............................................................................................8
ConfigurationUtility...................................................................................................................9
UsingtheConfigurationUtility...........................................................................................9
UpdatingFirmware...........................................................................................................11
ModbusRTUMapping..............................................................................................................12
BACnetMS/TPMapping...........................................................................................................13

LMV5SeriesInstallationInstructions
DocumentNo.LV5‐6100
SCCInc. Page3
CompatibleControls
LinkagelessBurnerManagementSystems
LMV51...
LMV52...

InstallationInstructions LMV5Series
DocumentNo.LV5‐6100
Page4SCCInc.
PhysicalConnections
Power
PowertotheOCI415.30mustbeeither9‐24VDCor9‐24VAC(nominal).Powerconsumptionis
2.5Worless.SCCpartnumberAGA15‐24isavailableasasuitablepowersupply.
Terminaldesignations:
Label Function
L+DC+
/
AC~
N‐ DC‐
/
AC~
ConnectiontoLMV5...
TheconnectionfromtheOCI415.30totheLMV5…shouldbemadewiththesuppliedcable.
TheconnectionattheLMV5…istotheAZLX72(COM2)port.Maximumallowedcablelength
is5meters.

LMV5SeriesInstallationInstructions
DocumentNo.LV5‐6100
SCCInc. Page5
PhysicalConnections(continued)
ConnectiontoBMS
TheconnectionfromtheBMStotheOCI415.30isviaterminalblock.Thephysicalmediumis
RS‐485.MultipleRS‐485nodesmaybeconnectedinadaisy‐chain.Forlongruns(typically
greaterthan1000feet)ornoisyenvironments,terminationmayberequiredontheendnode.
Terminaldesignations:
Label Function
ARS‐485Data(+)
BRS‐485Data(‐)
GRS‐485CommonGround
StatusLED
ThestatusLEDannunciatesthestatusoftheOCI415.30andtheconnectiontotheLMV5…
ColorStatus
GreenFlashing NoConnectiontoLMV5…
Green
/
RedAlternating CommunicatingwithLMV5…
RedFlashing InternalErrorOCI415.30
Tx/RxLED
TheLEDwillflashredtoindicateincomingcommunicationontheRS‐485connection.TheLED
willflashgreentoindicateoutgoingcommunication.Withnormalcommunication,theLEDwill
rapidlyalternatebetweengreenandred.NOTE:Ifthepollrateisfasttheflashesmaybevery
briefandhardtonotice.

InstallationInstructions LMV5Series
DocumentNo.LV5‐6100
Page6SCCInc.
RequiredLMV5Configuration
UsetheSelect<andSelect>buttonstonavigateupanddownthescreenandtheEnterbutton
whenthedesiredoptionisselectedwiththecursor.UseEsctogobacktothepreviousmenu.
Whenaparameterneedstobechanged,theSelect<andSelect>buttonsallowthevaluetobe
changedandEnterconfirmsthechange.PresstheEscbuttontoreturnafterthechangeis
made.
First,activatetheModbusportontheAZL(nopasswordrequired):
1. Operation>OptgModeSelect>TypeofGateway=Modbus
2. Operation>OptgModeSelect>GatewayBASon
Note:OlderAZLunitsmayread'GatewayDDCon'instead.
3. TheAZLshouldnowread'GatewayModeactive'.
Next,setuptherequiredparametersthroughtheAZL(nopasswordrequired):
1. Params&Display>Accessw‐outPW>AZL>Modbus>Address=1
2. Params&Display>Accessw‐outPW>AZL>Modbus>Baudrate=19200bit/s
3. Params&Display>Accessw‐outPW>AZL>Modbus>Parity=no
4. Params&Display>Accessw‐outPW>AZL>Modbus>Timeout=30s
Ifremoteoperationisdesiredtheloadcontrolleroperatingmodemustbechangedto“IntLC
Bus”usingthefollowingprocedure(nopasswordrequired):
1. Params&Display>Accessw‐outPW>LoadController>Configuration>LC_OptgMode=
IntLCBus
Thechangestakeeffectimmediately(norebootrequired).

LMV5SeriesInstallationInstructions
DocumentNo.LV5‐6100
SCCInc. Page7
ModbusRTUConnectionDetails
ModbusRTUprotocolselectionandaddressingisdoneusingthePCtoolOCIConfiguration
Utility(seenextsection).
Supportedaddresses:1‐247
Supportedbaudrates:2400,4800,9600,19200,38400,57600,and115200
Supporteddatabits:8
Supportedparityandstopbits:none(1or2stopbits),odd(1stopbit),andeven(1stopbit)
Supportedfunctioncodes:3(readholdingregisters),4(readinputregisters),6(writesingle
holdingregister),and16(writemultipleholdingregisters)
Maximumreadlength:125(ifbeginningandendingregistersarevalidaddresses)

InstallationInstructions LMV5Series
DocumentNo.LV5‐6100
Page8SCCInc.
BACnetMS/TPConnectionDetails
BACnetMS/TPprotocolselectionandaddressingisdoneusingthePCtoolOCIConfiguration
Utility(seenextsection).
Supportedaddresses:0‐127
Supportedbaudrates:9600,19200,38400,57600,76800,and115200
Supporteddatabits:8
Supportedparityandstopbits:none(1stopbit)
Supporteddeviceinstances:0‐4194302

LMV5SeriesInstallationInstructions
DocumentNo.LV5‐6100
SCCInc. Page9
ConfigurationUtility
UsingtheConfigurationUtility
1. Double‐clicktheicontoopentheconfigurationutility.
2. TheutilitywillopenandshowtheconnectionstatusoftheOCI415.30.

InstallationInstructions LMV5Series
DocumentNo.LV5‐6100
Page10SCCInc.
ConfigurationUtility(continued)
3. Useamini‐USBcabletoconnecttheOCI415.30tothecomputer,suchasSCCpart
numberAGA5‐05M.Adrivermayself‐installthefirsttimeaconnectionismade.The
connecteddevicewillthenbeindicatedonthescreen.
4. TheprotocolcanbechangedbetweenModbusRTUandBACnetMS/TPfromthis
screen.Seetheprevioussectionsforfurtherdetailsontheprotocol‐specificsettings
thatcanbechanged.Oncethedesiredsettingshavebeenentered,clickSubmitto
apply.ClickReloadtorefreshthedisplayedsettings.

LMV5SeriesInstallationInstructions
DocumentNo.LV5‐6100
SCCInc.Page11
ConfigurationUtility(continued)
UpdatingFirmware
1. FromtheOCI415.30ConfigurationUtility,clickFile‐>UpdateDevice…
2. Locatethesuppliedupdatefilewitha.dufextensionandclickOpen.
3. ThedevicewillautomaticallyrebootandreconnectwiththeOCI415.30Configuration
Utilityoncethefirmwareupdateiscomplete.Whenadeviceisconnected,the
firmwareversionisshownasoneoftheread‐onlyparameters.

InstallationInstructions LMV5Series
DocumentNo.LV5‐6100
Page12SCCInc.
ModbusRTUMapping(continued)
RefertoDocumentNo.LV5‐1000(LMV5TechnicalInstructions)forcompleteModbusmapping
information.

LMV5SeriesInstallationInstructions
DocumentNo.LV5‐6100
SCCInc.Page13
BACnetMS/TPMapping
PointNameTypeInstanceUnitsActiveTextInactiveText
PHASEANALOGINPUT1NOUNITS‐ ‐
FUELACTUATORANALOGINPUT2ANGDEG‐ ‐
GASACTUATORANALOGINPUT3ANGDEG‐ ‐
OILACTUATORANALOGINPUT4ANGDEG‐ ‐
AIRACTUATORANALOGINPUT5ANGDEG‐ ‐
AUX1ACTUATORANALOGINPUT6ANGDEG‐ ‐
AUX2ACTUATORANALOGINPUT7ANGDEG‐ ‐
AUX3ACTUATORANALOGINPUT8ANGDEG‐ ‐
VSDANALOGINPUT9PERCENT‐ ‐
CURRENTOUTPUTANALOGINPUT10PERCENT‐ ‐
CURRENTSETPOINTANALOGINPUT11NOUNITS‐ ‐
ACTUALVALUEANALOGINPUT12PERCENT‐ ‐
FLAMESIGNALANALOGINPUT13PERCENT‐ ‐
FUELFLOWANALOGINPUT14NOUNITS‐ ‐
CURRENTO2VALUEANALOGINPUT15PERCENT‐ ‐
SENSORTYPE(SEENOTE1)ANALOGINPUT16NOUNITS‐ ‐
STARTCOUNTERANALOGINPUT17NOUNITS‐ ‐
HOURCOUNTERANALOGINPUT18NOUNITS‐ ‐
ERRORCODEANALOGINPUT19NOUNITS‐ ‐
DIAGNOSTICCODEANALOGINPUT20NOUNITS‐ ‐
ERRORCLASSANALOGINPUT21NOUNITS‐ ‐
ERRORPHASEANALOGINPUT22NOUNITS‐ ‐
SUPPLYAIRTEMPERATUREANALOGINPUT23NOUNITS‐ ‐
FLUEGASTEMPERATUREANALOGINPUT24NOUNITS‐ ‐
COMBUSTIONEFFICIENCYANALOGINPUT25PERCENT‐ ‐
PROGRAMSTOP(SEENOTE2)ANALOGVALUE26NOUNITS‐ ‐
LCOPERMODE(SEENOTE3)ANALOGVALUE27NOUNITS‐ ‐
AZLOPERMODE(SEENOTE4)ANALOGVALUE28NOUNITS‐ ‐
LOCALREMOTE(SEENOTE5)ANALOGVALUE29NOUNITS‐ ‐
TIMEOUTANALOGVALUE30SECONDS‐ ‐
REMOTEMODE(SEENOTE5)ANALOGVALUE31NOUNITS‐ ‐
REMOTESPW3(SEENOTE5)ANALOGVALUE32NOUNITS‐ ‐
REMOTEFIRERATE(SEENOTE4)ANALOGVALUE33PERCENT‐ ‐
SETPOINTW1 ANALOGINPUT34NOUNITS‐ ‐
SETPOINTW2ANALOGINPUT35NOUNITS‐ ‐
DAYOFWEEK(0=SUNDAY) ANALOGINPUT36NOUNITS‐ ‐
YEAR2‐DIGITANALOGINPUT37NOUNITS‐ ‐
MONTH ANALOGINPUT38NOUNITS‐ ‐
DAYANALOGINPUT39NOUNITS‐ ‐
HOUR ANALOGINPUT40NOUNITS‐ ‐
MINUTEANALOGINPUT41NOUNITS‐ ‐
SECOND ANALOGINPUT42NOUNITS‐ ‐
HOURSGASRESET(SEENOTE6)ANALOGVALUE43HOURS‐ ‐
HRSOILS1RESET(SEENOTE6)ANALOGVALUE44HOURS‐ ‐
HRSOILS2RESET(SEENOTE6)ANALOGVALUE45HOURS‐ ‐

InstallationInstructions LMV5Series
DocumentNo.LV5‐6100
Page14SCCInc.
BACnetMS/TPMapping(continued)
PointNameTypeInstanceUnitsActiveTextInactiveText
HRSOILS3RESET(SEENOTE6)ANALOGVALUE46HOURS‐ ‐
HOURSRUNRESET(SEENOTE6)ANALOGVALUE47HOURS‐ ‐
HOURSRUNTOTALANALOGINPUT48HOURS‐ ‐
HOURSPOWEREDANALOGINPUT49HOURS‐ ‐
STARTSGASRESET(SEENOTE6)ANALOGVALUE50NOUNITS‐ ‐
STARTSOILRESET(SEENOTE6)ANALOGVALUE51NOUNITS‐ ‐
STARTSRESET(SEENOTE6)ANALOGVALUE52NOUNITS‐ ‐
STARTSTOTALANALOGINPUT53NOUNITS‐ ‐
FUELVOLUMEF0(SEENOTE6)ANALOGVALUE54PERCENT‐ ‐
FUELVOLUMEF1(SEENOTE6)ANALOGVALUE55NOUNITS‐ ‐
NUMBEROFFAULTSANALOGINPUT56NOUNITS‐ ‐
EXTRATEMPSENSORANALOGINPUT57NOUNITS‐ ‐
MINIMUMFIRERATEGASANALOGINPUT58PERCENT‐ ‐
MAXIMUMFIRERATEGASANALOGINPUT59PERCENT‐ ‐
MINIMUMFIRERATEOILANALOGINPUT60PERCENT‐ ‐
MAXIMUMFIRERATEOILANALOGINPUT61PERCENT‐ ‐
LOADLIMITMODULATINGANALOGVALUE62PERCENT‐ ‐
LOADLIMITSTAGINGANALOGVALUE63PERCENT‐ ‐
P‐VALUEANALOGVALUE64PERCENT‐ ‐
I‐VALUEANALOGVALUE65NOUNITS‐ ‐
D‐VALUEANALOGVALUE66NOUNITS‐ ‐
LOCKOUTCODE(SEENOTE7)ANALOGINPUT(20*x)+100PERCENT‐ ‐
LOCKOUTDIAG(SEENOTE7)ANALOGINPUT(20*x)+101NOUNITS‐ ‐
LOCKOUTCLASS(SEENOTE7)ANALOGINPUT(20*x)+102NOUNITS‐ ‐
LOCKOUTPHASE(SEENOTE7)ANALOGINPUT(20*x)+103NOUNITS‐ ‐
LOCKOUTOUTPUT(SEENOTE7)ANALOGINPUT(20*x)+104PERCENT‐ ‐
LOCKOUTYEAR(SEENOTE7)ANALOGINPUT(20*x)+105NOUNITS‐ ‐
LOCKOUTMONTH(SEENOTE7)ANALOGINPUT(20*x)+106NOUNITS‐ ‐
LOCKOUTDAY(SEENOTE7)ANALOGINPUT(20*x)+107NOUNITS‐ ‐
LOCKOUTHOUR(SEENOTE7)ANALOGINPUT(20*x)+108NOUNITS‐ ‐
LOCKOUTMINUTE(SEENOTE7)ANALOGINPUT(20*x)+109NOUNITS‐ ‐
LOCKOUTSECOND(SEENOTE7)ANALOGINPUT(20*x)+110NOUNITS‐ ‐
LOCKOUTSTART(SEENOTE7)ANALOGINPUT(20*x)+111NOUNITS‐ ‐
LOCKOUTHOUR(SEENOTE7)ANALOGINPUT(20*x)+112NOUNITS‐ ‐
ERRORCODE(SEENOTE7)ANALOGINPUT(10*x)+280NOUNITS‐ ‐
ERRORDIAG(SEENOTE7)ANALOGINPUT(10*x)+281NOUNITS‐ ‐
ERRORCLASS(SEENOTE7)ANALOGINPUT(10*x)+282NOUNITS‐ ‐
ERRORPHASE(SEENOTE7)ANALOGINPUT(10*x)+283NOUNITS‐ ‐
ERROROUTPUT(SEENOTE7)ANALOGINPUT(10*x)+284PERCENT‐ ‐
ERRORSTART(SEENOTE7)ANALOGINPUT(10*x)+285NOUNITS‐ ‐
CURRENTFUELBINARYINPUT1‐ OILGAS
UNITTYPEBINARYINPUT2‐STANDARDMETRIC
CONTROLSWITCHBINARYINPUT3‐ ONOFF
FANCONTACTORBINARYINPUT4‐ONOFF
OILSELECTEDBINARYINPUT5‐ ONOFF
GASSELECTEDBINARYINPUT6‐ONOFF

LMV5SeriesInstallationInstructions
DocumentNo.LV5‐6100
SCCInc.Page15
BACnetMS/TPMapping(continued)
PointNameTypeInstanceUnitsActiveTextInactiveText
HIGHOILSWITCHBINARYINPUT7‐ONOFF
LOWOILSWITCHBINARYINPUT8‐ ONOFF
VALVEPROVINGBINARYINPUT9‐ONOFF
SAFETYLOOPBINARYINPUT10‐ ONOFF
LOWGASSWITCHBINARYINPUT11‐ONOFF
HIGHGASSWITCHBINARYINPUT12‐ ONOFF
AIRSWITCHBINARYINPUT13‐ONOFF
OILRELEASEBINARYINPUT14‐ ONOFF
HEAVYOILSTARTBINARYINPUT15‐ONOFF
ALARMBINARYINPUT16‐ ONOFF
IGNITIONBINARYINPUT17‐ONOFF
STARTSIGNALBINARYINPUT18‐ ONOFF
FANOUTPUTBINARYINPUT19‐ONOFF
OILPUMPBINARYINPUT20‐ ONOFF
OILVALVESVBINARYINPUT21‐ONOFF
OILVALVEV1BINARYINPUT22‐ ONOFF
OILVALVEV2BINARYINPUT23‐ONOFF
OILVALVEV3BINARYINPUT24‐ ONOFF
GASVALVESVBINARYINPUT25‐ONOFF
GASVALVEV1BINARYINPUT26‐ ONOFF
GASVALVEV2BINARYINPUT27‐ONOFF
GASVALVEPVBINARYINPUT28‐ ONOFF
FUELSELECTBINARYVALUE29‐OILGAS
LOCKOUTFUEL(SEENOTE7)BINARYINPUT30+x‐ OILGAS
ERRORFUEL(SEENOTE7)BINARYINPUT39+x‐OILGAS
Note1–Sensortype.
0:Pt100
1:Pt1000
2:Ni1000
3:Temperature(4‐20mA,0‐10V)
4:Pressure(4‐20mA,0‐10V)
5:Pt100Pt1000
6:Pt100Ni1000
7:Nosensor
Note2–LMVprogramstop.
0:deactivated
1:prepurgephase24
2:ignitionpositionphase36
3:interval1phase44
4:interval2phase52

InstallationInstructions LMV5Series
DocumentNo.LV5‐6100
Page16SCCInc.
BACnetMS/TPMapping(continued)
Note3–Loadcontroloperatingmode.
0:ExtLCX5‐03
1:IntLC
2:IntLCBus
3:IntLCX62
4:ExtLCX62
5:ExtLCBus
Note4–AZLoperatingmode.
0:Automatic
1:Burneron
2:Burneroff
Note5–Setlocal/remote(AV29)to1forremote.Onceinremotethedesiredmodecanbeset
usingAV31(0=local/automatic,1=burneron,2=burneroff).IfAV31issettoautomatic,
writethedesiredsetpointusingAV32.IfAV31issettoburneron,writethedesiredfiringrate
usingAV33.Thefiringratemustbebetween0%and100%toremainvalid.AV29mustbe
activelywrittenatleastonceduringthetimeoutperiodtoresetthetimeoutcounter.Oncethe
timeoutcounterreachesthetimeoutvaluelocal/remotewillreverttolocal(failsafeoperation).
Note6–Countervaluescanonlyberesettozero.
Note7–Thereare9lockoutsinmemory(currentplus8history).Thereare21errorsin
memory(currentplus20history).Theaddressesforthehistoricaldataareallinthesame
formatasshowninthemapping.Usetheformulatofindthecorrectinstance.Forexample,
theanaloginputinstancefortheERRORCODEhistoryindex4wouldbe(10x4)+280=320,or
AI320.TheanaloginputinstancefortheLOCKOUTOUTPUThistoryindex7wouldbe(20x7)+
104=244,orAI244.
Informationinthispublicationisbasedoncurrentspecifications.Thecompanyreservestherighttomakechanges
inspecificationsandmodelsasdesignimprovementsareintroduced.Productorcompanynamesmentioned
hereinmaybethetrademarksoftheirrespectiveowners.©2017SCCInc.