Schaffner MFO 650 Series User manual

Modula 6100
Operating Insutructions
Modula System 6100
Accessories

Modula 6100
2/61
Explanation of the symbols used in this manual
Please take note of the following explanations of the symbols used in order to achieve the optimum benefit
from this manual and to ensure safety during operation of the equipment.
The following symbol draws your attention to a circumstance where non-observation of the warning could
lead to inconvenience or an impairment in the performance.
Example:
This connection must not be confused with the EUT power input
The following symbol draws your attention to a circumstance where non-observation of the warning could
lead to component damage or danger to the operating personnel.
Example:
Never connect or disconnect the EUT while the test system is performing a test

Modula 6100
3/61
Safety advice
All accessories are intended for use with the Modula 6100 generator type. This generator produces high
voltage test pulses that have high energy. Therefore improper or careless handling can be fatal!
These operating instructions form an integral part of the equipment and must be available to the operating
personnel at all times. All the safety instructions and advice notes are to be observed.
Keeping responsibility to the instructions and recommendations that follow is imperative.
The safety advice referring to the generators also applies and must be complied with when using the
instruments together with all accessories.
Neither Schaffner EMV AG, Luterbach/Switzerland nor any of the associated sales organisations accept
any responsibility for personal injury or for material or consequential damage that results through
irresponsible or negligent operation of this equipment.
Safety measures
These operating instructions form an integral part of the instrument and must be studied carefully before
putting the device into use as well as being available at all times to the operating personnel.
The instrument must only be used by trained personnel.
Persons fitted with a heart pacemaker must not operate the instrument and should not be in the vicinity of
the test rig when pulses are triggered.
Arrange the working area in compliance with appropriate safety standards (e.g. VDE 104).
Connect an additional earth wire to the rear panel of the generator and to the coupling network.
The test rig must provide adequate insulation protection for up to 4.8kV. Particular care should be given to
the connections between the accessories and the equipment under test (EUT).
The EUT may only be tested when placed inside a suitable protective enclosure which should provide
protection against flying fragments, fire and electric shock.
The pulse voltage must not be able to find its way to unearthed metal objects in the event of the EUT
failing.
Only use the instrument in a dry room. Never leave the instrument unattended when it is switched on.
Do not open the instrument. Repairs and adjustments must only be carried out by qualified maintenance
personnel.

Modula 6100
4/61
Content
Safety measures........................................................................................................................................... 3
1
Manual step transformer INA 6501............................................................................................ 7
1.1
Circuit diagram INA 6501.............................................................................................................. 7
1.2
Technical specifications INA 6501................................................................................................ 8
1.2.1
Parts description ........................................................................................................................... 8
1.3
Installation - connection to Modula ............................................................................................... 8
2
Automatic step transformer INA 6502 .................................................................................... 10
2.1
Circuit diagram INA 6502............................................................................................................ 10
2.2
Technical specifications INA 6502.............................................................................................. 11
2.2.1
Parts description ......................................................................................................................... 11
2.2.2
Compatibility ............................................................................................................................... 12
2.3
Installation - connection to Modula ............................................................................................. 13
2.4
HW Detection.............................................................................................................................. 14
2.4.1
Operation .................................................................................................................................... 14
3
Automatic variable transformer VAR 6501............................................................................. 16
3.1
Circuit diagram VAR 6501 .......................................................................................................... 16
3.2
Technical specifications VAR 6501 ............................................................................................ 17
3.2.1
Parts description ......................................................................................................................... 17
3.2.2
Compatibility ............................................................................................................................... 18
3.3
Installation - connection to Modula ............................................................................................. 18
3.4
Using WinModula standard variation test................................................................................... 19
3.5
Specials using Winmodula and variation test............................................................................. 20
3.5.1
Operation .................................................................................................................................... 20
4
Automatic variable transformer VAR 6502............................................................................. 22
4.1
Circuit diagram VAR 6502 .......................................................................................................... 22
4.2
Technical specifications VAR 6502 ............................................................................................ 23
4.3
Variable transformer VAR 6502.................................................................................................. 23
4.3.1
Parts description ......................................................................................................................... 24
4.4
Compatibility ............................................................................................................................... 24
4.4.1
Installation - connection to Modula ............................................................................................. 25
4.4.2
Operation .................................................................................................................................... 25
5
Manual variable transformer VAR 6503.................................................................................. 27
5.1
Circuit diagram VAR 6503 .......................................................................................................... 27
5.2
Technical specifications VAR 6503 ............................................................................................ 28
5.2.1
Parts description ......................................................................................................................... 28
5.3
Installation - connection to Modula ............................................................................................. 28
6
Magnetic fields options MFO 650X ......................................................................................... 30
6.1
Magnetic field loops INA 701 and INA 702................................................................................. 30
6.2
Manual magnetic field option MFO 6501.................................................................................... 32
6.2.1
Circuit diagram MFO 6501.......................................................................................................... 33
6.2.2
Technical specifications MFO 6501............................................................................................ 33
6.2.3
Parts description ......................................................................................................................... 34
6.2.4
Installation................................................................................................................................... 34
6.2.5
Operation – adjustments............................................................................................................. 35
6.3
Automatic magnetic field option MFO 6502................................................................................ 36
6.3.1
Circuit diagram MFO 6502.......................................................................................................... 37
6.3.2
Technical specifications MFO 6502............................................................................................ 37
6.3.3
Parts description ......................................................................................................................... 38
6.3.4
Compatibility ............................................................................................................................... 38
6.3.5
Installation - connection to Modula ............................................................................................. 38
6.3.6
Operation .................................................................................................................................... 39

Modula 6100
5/61
6.4
Pulse wave shape adapter INA 752 ........................................................................................... 39
6.4.1
Technical specifications SRG 6501 – INA 752 – INA 701(2) ..................................................... 40
6.4.2
INA 752....................................................................................................................................... 40
6.4.3
Compatibility ............................................................................................................................... 41
6.4.4
Operation .................................................................................................................................... 41
7
Coupling Network CDN 133/153-M.......................................................................................... 43
7.1
Leakage current.......................................................................................................................... 43
7.2
EUT and mains supply protection............................................................................................... 43
7.3
Configuration for surge and burst coupling................................................................................. 44
7.4
Technical specifications.............................................................................................................. 45
7.4.1
General specification .................................................................................................................. 45
7.4.2
Electrical specifications of the CDN 133/153-M.......................................................................... 45
7.4.3
Mechanical specifications........................................................................................................... 46
7.5
Operation .................................................................................................................................... 46
7.5.1
Operating elements..................................................................................................................... 46
7.5.2
EUT wiring of the connectors...................................................................................................... 47
7.5.3
Earth connection......................................................................................................................... 47
7.5.4
Synchronisation supply connection ............................................................................................ 47
7.5.5
High voltage connections............................................................................................................ 47
7.6
Test rig........................................................................................................................................ 48
7.6.1
Layout of a test facility with Modula and CDN 133/153-M.......................................................... 48
7.7
Installation................................................................................................................................... 49
7.8
Operation of the instruments ...................................................................................................... 50
7.8.1
Using the WIN Modula Software................................................................................................. 50
7.8.2
Fuses .......................................................................................................................................... 51
7.9
Optional accessories................................................................................................................... 51
8
Maintenance and function check ............................................................................................ 52
8.1
Cleaning...................................................................................................................................... 52
8.2
Function check............................................................................................................................ 52
8.3
Calibration................................................................................................................................... 53
8.4
Warranty...................................................................................................................................... 53
9
CE conformity ........................................................................................................................... 54
10
Various Accessories................................................................................................................. 56
10.1
Additional equipment .................................................................................................................. 56
10.2
Measuring and calibration parts.................................................................................................. 57
10.3
Cables and plugs........................................................................................................................ 58
11
Addresses.................................................................................................................................. 61

Modula 6100
6/61
Manual step transformer INA 6501

Modula 6100
7/61
1 Manual step transformer INA 6501
The step transformer type INA 6501 is a standard accessory for the Schaffner Modula 6100 instru-
mentation series. It provides a convenient means for reducing the incoming supply voltage by pre-set
amounts. It is required for power quality testing (PQT) and is fully compliant with the latest revisions of IEC
61000-4-11:2004.
It is fitted with carrying handles as part of its overall good ergonomic design, which makes for ease of
handling. Further, the unit may be used in any of three operating positions; laying or standing on a work
bench, or for more permanent applications, it can be wall-mounted.
Care has to be taken in case of use in standing position, as the stability is
limited. The cabling connecting INA 6501 to mains and Modula presents a risk
of being unvoluntarly caught by the users which could cause the INA 6501 to
fall down.
The few control elements are readily accessible on the front panel. An EUT power on/off switch with a
power on indicator and a well-proportioned rotary switch to select the required voltage ensure easy and
intuitive operation.The unit has been designed for use in rugged industrial environments. Professional
quality connectors ensure user safety, additional system protection is provided by a 16A fuse located in the
front panel.
Thanks to the provision of an 80% voltage position and to the large overcurrent capabilities the step
transformer is fully compliant with the latest requirements called for in IEC 61000-4-11: 2004 standard.
1.1 Circuit diagram INA 6501

Modula 6100
8/61
1.2 Technical specifications INA 6501
Input voltage 0 to 250VAC (not suited for DC voltages)
Output voltage 4 steps: 0% - 40% - 70% - 80%
Accuracy
±
5%
Voltage change with load:
100% output; 0 to 16A
80% output; 0 to 20A
70% output; 0 to 23A
40% output; 0 to 40A
less than 5%
less than 5%
less than 5%
less than 5%
Output current capability at 230V
input voltage 16Arms at 100% output
20Arms at 80% output
23Arms at 70% output
40Arms at 40% output
Voltage selection Front panel rotary switch
EUT power on/off function Front panel switch with on indicator
Fuse 16A, slow blow
Connectors Harting type HAN3A, compatible with Modula safe linking concept
Size 150 x 180 x 360mm
Weight 12kg approx.
Cable length to Modula 2m
Input cable Modula standard cable to be used
1.2.1 Parts description
Part designation Function
EUT power in switch Switches on/off the EUT power supply
16AT fuse Protects the EUT power supply line
EUT power in plug This is where the EUT power needs to be applied – use Modula supplied
cable and conect it to power source (mains)
EUT power out cable Connect this cable to the EUT supply input port of Modula
Red selector To switch variable voltage to 0% or 40% or 70% or 80% of Uin
1.3 Installation - connection to Modula
The equipment should be switched off during installation and interconnection.
Connect INA 6501 - EUT power out to Modula - EUT power input
Connect INA 6501 - EUT power in to mains using EUT power in cable (delivered with Modula)
Because of the capacitors in the internal coupler of Modula CDN 6501, earth leakage
currents of up to 4A can occur in the EUT power supply network. The test system
must therefore be correctly earthed and be powered from a supply that is not
protected by a residual current detector (RCD).
Switch on EUT power on INA 6501 (red switch) when power for the EUT is required
Switch on the Modula 6100 generator
Select the required variable voltage using rotary switch on the INA 6501

Modula 6100
9/61
Automatic step transformer
INA 6502

Modula 6100
10/61
2 Automatic step transformer INA 6502
The step transformer type INA 6502 is a standard accessory for the Schaffner Modula 6100
instrumentation series. It provides a convenient means of reducing the incoming supply voltage by pre-set
amounts. It is required for power quality testing (PQT) and is fully compliant with the latest revision of IEC
61000-4-11 (2004).
Its control is fully automatic, driven from Modula master controller, using the mobile hand-held controller
MHC 6550 or WIN Modula software. Once detected by the Modula master controller and declared to the
driving software ModPDA or WIN Modula, the functions offered by INA 6502 are available in the software.
So the settings 0% - 40% - 70% - 80% will appear, as well as the possibility to switch EUT power on/off in
case an external switch (e.g. option INA 6581) is connectd to the circuit breaker option CIB is fitted in the
INA 6502.
INA 6502 comes fitted with carrying handles as part of it’s overall good ergonomic design, which makes for
ease of handling. Further, the unit may be used in any of two operating positions; laying on a work bench,
or for more permanent applications, it can be wall-mounted.
The unit has been designed for use in rugged industrial environments. Professional quality connectors
ensure user safety, additional system protection is provided by a 16A fuse located in the top panel.
Thanks to the provision of an 80% voltage position and to the large over current capabilities the step
transformer is fully compliant with the latest requirements called for in IEC 61000-4-11:2004 standard.
For proper operation of the plug and play detection mechanisms it is
strongly recommended to power on first the INA 6502 accessory and then
the Modula 6100 main frame. Powering on the Modula main frame before
the accessories may result in non-detection of accessories.
2.1
Circuit diagram INA 6502

Modula 6100
11/61
2.2
Technical specifications INA 6502
Input voltage 0 to 250VAC (not suited for DC voltages)
Output voltage 4 steps: 0% - 40% - 70% - 80%
Accuracy
±
5%
Voltage change with load:
100% output; 0 to 16A
80% output; 0 to 20A
70% output; 0 to 23A
40% output; 0 to 40A
less than 5%
less than 5%
less than 5%
less than 5%
Output current capability at 230V
input voltage: 16Arms at 100% output
20Arms at 80% output
23Arms at 70% output
40Arms at 40% output
Voltage selection Software driven from ModPDA or WIN Modula
EUT power on/off function Front panel switch with on indicator
Optional circuit breaker (CIB) software driven from ModPDA
or WIN Modula
Fuse 16A, slow blow
Connectors Harting type HAN3A compatible with Modula safe linking concept
Possible extensions Connection to remote EUT power on/off switch (INA 6581)
Interlock connection to door switch
Own supply Selectable 100-110V; 220-240V 15VA
Size 460 x 200 x 160mm
Weight 15kg approx.
Cable length to Modula 2m
Input cable Modula standard cable to be used
Control cable 2m - 25 way sub D – twisted pair - shielded (included in delivery)
2.2.1 Parts description
Part designation Function
Mains supply in socket
For instrument supply, includes plug, voltage selector (110V – 230VAC), on/off
switch and fuse
EUT power in switch Switches the EUT power supply on/off
16AT fuse Protects the EUT power supply line
EUT power in plug For feeding of the EUT power – use Modula supplied cable and connect it to
power source (mains)
EUT power out cable Connect this cable to the EUT supply input port of Modula

Modula 6100
12/61
Part designation Function
Plug X3
Remote TEST and EUT power o
ff: with shorting plug. Allows to conect external
door switch or equivalent (e.g. INA 6581)
Interrupts the 24V supply of the circuit breaker contactor which switches EUT
supply on/off
The information will be transmitted to Modula master controller which will stop
the test
Plug X2 Modula system interface out – to be terminated by Modula interlock plug or
linked to another accessory, to X1 plug
Plug X1 Modula system interface in –
to be connected to Modula master controller or to
another accessory, to X2 plug
Power LED (green) Shows if instrument is powered up
Error LED (red)
ERROR LED off:
No problem - acessory is ready to run
ERROR LED blinking:
Problem which may be solved by user intervention. Expl: Interlock is activated
– emergency button is pressed – overtemperature (for MFO 6502)
ERROR LED on:
Problem which needs module repair – please contact your nearest Schaffner
customer support center or sales representative
2.2.2 Compatibility
INA 6502 is supported by:
ModPDA version 2.4 and higher
WIN Modula version 2.31 and higher
Master controller firmware must be version 1.17 or higher
Master controller revision 2 (copper interface)
These versions are factory built into all Modula 6100 above serial number 34391.
For lower serial numbers please consult your local Schaffner support center for an upgrade.

Modula 6100
13/61
2.3 Installation - connection to Modula
The equipment should be switched off during installation and interconnection
Top view Bottom view
Verify the setting of input voltage selector and adjust it to the right mains voltage value if required
Connect instrument power from the mains
Remove 25 way Sub D plug at rear of Modula master controller
Connect this connector to X2 of INA 6502
Connect master controller 25 way output to INA 6502 X1 plug, using system interface cable
delivered with INA 6502
Connect INA 6502 - EUT power out to Modula – EUT power input
Connect INA 6502 - EUT power in to mains using EUT power in cable delivered with Modula
Because of the capacitors in the internal coupler of Modula CDN 6501, earth leakage
currents of up to 4A can occur in the EUT power supply network. The test system
must therefore be correctly earthed and be powered from a supply that is not
protected by a residual current detector (RCD).
Switch on INA 6502 first
Switch on Modula mainframe
Switch on EUT power (red switch) when power for the EUT is required

Modula 6100
14/61
2.4 HW Detection
The INA 6502 is automatically detected by the Modula firmware during
the booting process. Its presence is visualised in ModPDA settings
screen as PQT – supply.
In case several PQT sources (INA 6502 – VAR 6501 – etc.) are
connected on the system bus and get detected by the modula firmware,
it will be up to the user to tell the software which source is actually used.
This can be done by clicking the field indicating PQT – supply, the
various detected possibilities will scroll through.
2.4.1 Operation
The parameter Uvar gets active once an INA 6502 has been detected by
the software. The entry of Uin is by default 230V and may be set to other
voltages. Uvar consist one of the 4 available variable voltage levels: 0% -
40% - 70% - 80% and can be selected by the user by acting on the up or
down arrow key.
Selecting “T Event” or “Rep.Rate” and stay on the unit (e.g. s, ms, a.s.o)
then the unit will change for an easier time seting

Modula 6100
15/61
Automatic variable transformer
VAR 6501

Modula 6100
16/61
3 Automatic variable transformer VAR 6501
The automatic variable transformer type VAR 6501 is a standard accessory for the Schaffner Modula 6100
instrumentation series. It provides a convenient means for reducing the incoming supply voltage by
adjusting the incoming EUT supply voltage to arbitrary voltages. It is required for power quality testing
(PQT) and is compliant with the latest revision of IEC 61000-4-11 (2004).
Its control is fully automatic, driven from Modula master controller, using the mobile hand-held controller
MHC 6550 or WIN Modula software. Once detected by the Modula master controller and declared to the
driving software ModPDA or WIN Modula, the functions offered by VAR 6501 are available in the software.
So the settings of Uvar will be possible in Volts or % of Uin, as well as the possibility to switch EUT power
on/off in case an external switch (e.g. option INA 6581) is connected to the VAR 6501.
It is fitted with carrying handles as part of its overall good ergonomic design, which makes for ease of
handling. Further, the unit may be used in any of two operating positions; laying on a work bench, or for
more permanent applications, it can be wallmounted.
The unit has been designed for use in rugged industrial environments. Professional quality connectors
ensure user safety, additional system protection is provided by an 8A fuse located in the top panel.
For proper operation of the plug and play detection mechanisms it is strongly
recommended to power on first the VAR 6501 accessory and then the Modula 6100
main frame. Powering on the Modula main frame before the accessories may result
in a non detection of the accessories.
3.1 Circuit diagram VAR 6501

Modula 6100
17/61
3.2 Technical specifications VAR 6501
Input voltage 0 to 250VAC (not suited for DC voltages)
Output voltage Adjustable from 0 to 100% of input voltage
Accuracy
±
5%
Input and output current Max 7.5A approx. – protected by a 8A slow blow fuse
Voltage selection Software driven by ModPDA or WIN Modula
EUT power on/off function Front panel switch with on indicator
Optional circuit breaker (CIB) driven from ModPDA or WIN
Modula
Fuse 8A, slow blow
Connectors Harting type HAN3A, compatible with Modula safe linking concept
Possible extensions Connection to remote EUT power on/off switch (INA 6581)
Interlock connection to door switch
Own supply Universal power supply 90 – 264V, 100VA
Size 460 x 200 x 160mm
Weight 15kg approx.
Cable length to Modula 2m
Input cable Modula standard cable to be used
Control cable 2m - 25 way sub D – twisted pair - shielded (included in delivery)
3.2.1 Parts description
Part designation Function
Mains supply in socket For instrument supply, includes plug, voltage selector (110V – 230V), on/off
switch and fuse
EUT power in switch Switches on/off the EUT power supply
8AT fuse Protects the EUT power supply line
EUT power in plug This is where the EUT power needs to be applied – use Modula supplied
cable and connect it to your power source (mains)
EUT power out cable Connect this cable to the EUT supply input port of Modula
Plug X3
Remote TEST and EUT power off: with shorting plug. Allows to conect
external door switch or equivalent (e.g. INA 6581)
Interrupts the 24V supply of the circuit breaker contactor which switches
EUT supply on/off
The information will be transmitted to Modula master controller which will
stop the test
Plug X2 Modula system interface out – to be terminated by Modula interlock plug or
linked to another accessory, to X1 plug
Plug X1 Modula system interface in – to be connected to Modula master controller or
to another accessory, to X2 plug
Power LED (green) Shows if instrument is powered up
Error LED (red)
ERROR LED off:
No problem - accessory is ready to run
ERROR LED blinking:
Problem able to be solved by user. Expl.: Interlock is activated – emergency
button is pressed – overtemperature (for MFO 6502)
ERROR LED on:
Problem which needs module repair – please contact your nearest Schaffner
customer support center or sales representative.

Modula 6100
18/61
3.2.2 Compatibility
VAR 6501 is supported by:
ModPDA version 2.4 and higher
WIN Modula version 2.31 and higher
Master controller firmware must be version 1.17 or higher
Master controller revision 2 (copper interface)
These versions are factory built in to all Modula 6100 above serial number 34391.
For lower serial numbers please consult your local Schaffner support center for an upgrade.
3.3
Installation - connection to Modula
The equipment should be switched off during installation and interconnection
Connect instrument power from the mains
Remove 25 way Sub D plug at rear of Modula master controller
Connect this connector to X2 of VAR 6501
Connect master controller 25 way output to VAR 6501 X1 plug, using system interface cable
delivered with VAR 6501
Connect VAR 6501 - EUT power out to Modula - EUT power input
Connect VAR 6501 - EUT power in to mains using EUT power in cable delivered with Modula
Because of the capacitors in the internal coupler of Modula CDN 6501, earth
leakage currents of up to 4A can occur in the EUT power supply network. The test
system must therefore be correctly earthed and be powered from a supply that is
not protected by a residual current detector (RCD).
Switch on VAR 6501 first
Switch on Modula mainframe
Switch on EUT power (red switch) when power for the EUT is required

Modula 6100
19/61
3.4 Using WinModula standard variation test
Choosing a standard variation from the test library, following need mentioned:
Check first, if your system has recognized your automated variac correctly.
Load a variation test from the IEC 61000-4-11 test library

Modula 6100
20/61
As soon the test is loaded it will show up following message:
This happen because the original test was written with a VAR 6502 and this message only tells you this.
So just select the variac and the click accept. Once you have saved a test with your variac this message
will not appear anymore.
3.5 Specials using Winmodula and variation test
If you choose a Variation test given
3.5.1 Operation
The parameters Uin and Uvar get active once a VAR 6501 has been
detected by the software. The entry of Uin is by default 230 V and may be
set to other voltagtes. Uvar is setted in V. To change the units from V to
% tip on the parameter first, then stay on the unit until it will change.
Unom is the 100% referenz value for Uvar and can be adjusted as well.
Uin (click on the Unit of Uvar (V) to change from Volts to % Uin).
Using the arrow keys to change value or using the keypad (hold the
stylus longer time on the Uvar parameter to make appear the keypad).
This manual suits for next models
8
Table of contents
Other Schaffner Test Equipment manuals