Schaudt Electrobloc EBL 99 G User manual

© 2005 Schaudt GmbH, Elektrotechnik & Apparatebau, Daimlerstraße 5, 88677 Markdorf, Germany, Phone +49 7544 9577-0, Telefax +49 7544 9577-29, www.schaudt-gmbh.de
SDT-0054-00EN Situation: 15.06.2005
0 Instruction Manual Electrobloc EBL 99 G
Instruction manual
Electrobloc EBL 99 G
Type no. 911.417
Table of contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
3 Description and appropriate use . . . . . . . . . . . . . . . . . . . . . . . . . .3
4 Suitable accessories (not supplied) . . . . . . . . . . . . . . . . . . . . . . . .4
5 Electrical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
6 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
7 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
8 Shutting down the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
9 Changing the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
10 Technical faults, possible causes and remedies . . . . . . . . . . . . . .9
11 Customer service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
12 Block diagram - for specialist workshop only. . . . . . . . . . . . . . . .11
13 Fault report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

2Situation: 15.06.2005 SDT-0054-00EN
Instruction Manual Electrobloc EBL 99 G
1 Introduction
This instruction manual contains important information for safe operation of
the Electrobloc. It is essential to read and to follow the given safety informa-
tion.
The instruction manual should always be kept in the motorhome/caravan. All
safety information must be passed on to other users.
The reproduction, translation and duplication of this manual, even in parts, is
not allowed without written authorization.
2 Safety information
The design of the Electrobloc is state-of-the-art and according to approved
safety technology. Nevertheless, if the safety information in this instruction
manual is not closely followed, persons might get injured or the Electrobloc
might be damaged.
Do not use the Electrobloc if it is not in technically good order and condition.
The instruction manual must be followed.
Any technical faults affecting the safety of persons or of the Electrobloc must
be dealt with immediately by qualified personnel.
W
Failure to comply with this sign may lead to the endangerment of per-
sons.
W
Failure to comply with this sign may damage the device or the connected
consumers.
W
This sign indicates recommendations or special features.
W
The electrical system of the motorhome or the caravan has to meet
current DIN, VDE and ISO regulations. Manipulations of the electrical
system will endanger the safety of persons and the vehicle, and are
therefore prohibited.
W
Never make any modifications to the Electrobloc.
W
The electrical connection may only be established by qualified person-
nel and must be carried out according to the Schaudt installation
instructions.
W
Connection work is to be carried out in tensionless condition only.
W
Risk of fatal injury due to electric shock or fire in the case of a defective
mains cable or incorrect connection!
W
Risk of fatal injury!
Never perform maintenance on the Electrobloc when it is live.
W
Blown fuses must only be replaced when the cause of the fault is
known and eliminated.
W
Never bridge or repair fuses.
W
Danger of burning! Blown fuses must only be changed on a zero-cur-
rent Electrobloc.
W
Only use original fuses rated as specified in the instruction manual.

SDT-0054-00EN Situation: 15.06.2005 3
Instruction Manual Electrobloc EBL 99 G
3 Description and appropriate use
The Electrobloc EBL 99 G is designed as a main power distributor for
motorhomes/caravans. The Electrobloc is a permanent installation. The Elec-
trobloc is for charging batteries and supplying 12 V appliances with power.
The electrical management system Electrobloc EBL 99 G consists of:
P
The LAS 1218 charger module
P
The 12 V distribution
P
Fuses for the 12 V circuits
P
A battery monitor module
P
Other control and monitoring functions
The charger module is a primary controlled switch-mode power supply. This
modern switching technology achieves high charging performance at a com-
pact size and low weight.
A control and switch panel has to be connected for operation. This control and
switch panel controls the electrical functions in the living area of in the
motorhome, including accessories.
W
Danger of burning! During operation the back of the Electrobloc gets
hot. Do not touch.
W
Danger of explosion from formation of detonating gas due to an incor-
rectly set battery selector switch, defective batteries, defective Elec-
troblocor an excessively high battery working temperature (more than
30 °C).
W
The AES refrigerator fuse may only be used if a AES refrigerator is con-
nected. Otherwise, the living area battery may get totally discharged. Bat-
tery damage is possible.
W
An incorrectly set battery selector switch damages the living area battery.
W
Disconnect the Electrobloc from the mains before adjusting the battery
selector switch.
W
If the living area battery is separated from the Electrobloc using the 12 V
main switch at the control and switch panel, the frost protection valve of
the heater system opens. Water may be lost. For more information, see
the instruction manual of the heater system.
W
Before and after shutdown, the living area battery must be fully recharged
to avoid battery damage. For this purpose the vehicle must be connected
to mains supply for a minimum of 12 hours with an 80 Ah battery and
24 hours with a 160 Ah battery.
W
Do not operate the Schaudt solar charge regulator without a battery. This
might damage the solar charge regulator or any connected consumers. If
the battery is going to be changed or removed, please first take off the pos-
itive lead "+ Solarzelle" (+ Solar Module) on the solar charge regulator.
W
To avoid voltage peaks during warm-up, do not connect the generator until
it is running in a stable manner. Otherwise, the Electrobloc, the 12 V con-
sumers or other connected equipment might get damaged. It is essential
that the generator complies with the mains supply specifications.
W
The mains supply on board car ferries might not always be perfect. There-
fore, never connect the Electrobloc to the mains on car ferries. Otherwise,
the Electrobloc, the 12 V consumers or other connected equipment might
get damaged.

4Situation: 15.06.2005 SDT-0054-00EN
Instruction Manual Electrobloc EBL 99 G
There are connections for an auxiliary charging unit and a solar charge regu-
lator.
Fig. 1 Electrobloc EBL 99 G, front view
1 Mains connection
2 Connections for refrigerator
3 Connections for refrigerator power supply, D+ and sensor/control wires
4 Connections for frost protection valve, heater and floor light/step
5 Connections for control and switch panel
6 Spare connections
7 Connections for solar charge regulator
8 Connections for auxiliary charging unit
9 Connections for TV, pump and other consumers
10 Battery selector switch
11 Flat vehicle fuses
12 Battery cut-off switch
4 Suitable accessories (not supplied)
Control and switch panel
P
IT 20-2, IT 20-3, IT 95, IT 901, IT 991, IT 992, IT 993
P
LT 410, LT 99, LT 993
and their variants
Auxiliary charging unit Schaudt battery charging unit type LAS... with up to 18 A charge current
Additional 2-pin charging cable, lengths supplied on request
Solar charge regulator Schaudt solar charge regulator type LR... for solar modules with a total cur-
rent of 14 A with 3-pin connector plug, including 0.5 m cable
5 Electrical data
SDT00266
1 2 3 4
12
5 6 9 10
11
7 8
Mains connection 230 V AC ± 10 %, 47 to 63 Hz sinusoidal, protection class I
Suitable batteries 6-cell lead acid or lead gel batteries of at least 55 Ah
Current-carrying capacity 12 V outputs No more than 90 % of the rated current
of the appropriate fuse may be drawn,
see the block diagram.

SDT-0054-00EN Situation: 15.06.2005 5
Instruction Manual Electrobloc EBL 99 G
6 Operation
6.1 Operating controls
Flat vehicle fuses
The flat vehicle fuses protect the various circuits.
Battery cut-off switch The battery cut-off switch "Batterie Ein/Aus" (battery on/off) disconnects the
following connections from the living area battery:
P
All 12 V consumers
P
The frost protection valve
P
The control and switch panel
This prevents the living area battery from slowly discharging due to closed cir-
cuit current while the vehicle is not in use.
The batteries can still be charged using the Electrobloc, the alternator, an
auxiliary charging unit or the solar charge regulator, even when the battery
cut-off switch is switched off.
Start up the system Set the battery cut-off switch on the Electrobloc to "Batterie Ein" (battery
on).
After switching on the battery cut-off switch or after changing batteries:
Switch on the 12 V main switch on the control and switch panel briefly to
start up the consumers.
Shutting down the system Set the battery cut-off switch to "Batterie Aus" (battery off).
W
Blown fuses must only be replaced when the cause of the fault is
known and eliminated.
W
Never bridge or repair fuses.
W
Danger of burning! Blown fuses must only be changed on a zero-cur-
rent Electrobloc.
W
Only use original fuses rated as specified in the instruction manual.
W
Before starting up:
P
Make sure the living area battery is connected.
P
Make sure the battery selector switch is set for the correct type of bat-
tery.
P
Make sure the AES fuse is only used if the AES refrigerator is connect-
ed. Otherwise, the living area battery may get totally discharged. Bat-
tery damage is possible.
W
When the living area battery is separated from the Electrobloc by the bat-
tery cut-off switch, the frost protection valve of the heater system opens.
Water may be lost. For more information, see the instruction manual of the
heater system.

6Situation: 15.06.2005 SDT-0054-00EN
Instruction Manual Electrobloc EBL 99 G
Battery selector switch
Theswitchingoptionprovidedbythebatteryselectorswitchensuresoptimum
charging of the two different types of battery, lead acid and lead gel. The
switch must be set to the correct battery type: lead acid or lead gel.
Use a thin object (e. g. a ballpoint pen cartridge) to move the battery selector
switch.
Set lead gel battery: Set the battery selector switch to "Blei-Gel" (lead gel).
Set lead acid battery: Set the battery selector switch to "Blei-Säure" (lead
acid).
12 V main switch (on the
control and switch panel) The 12 V main switch on the control and switch panel switches all consumers
and the panel on and off.
Exceptions:
P
Heater
P
Floor light/step
P
Frost protection valve
P
AES/compressor refrigerator
P
Spare 4
For more information, see the instruction manual of the control and switch
panel.
6.2 Additional functions
Automatic switch function
for AES/compressor
refrigerator
7KLVUHOD\VXSSOLHVWKH$(6FRPSUHVVRUUHIULJHUDWRUZLWKSRZHUIURPWKH
VWDUWHUEDWWHU\ZKHQWKHYHKLFOHHQJLQHLVUXQQLQJDQGWKH'FRQQHFWLRQLV
OLYHAn AES/compressor refrigerator is powered by the living area battery
when the vehicle engine is switched off.
Mains charging of starter
battery This feature provides an automatic float charge for the starter battery at up to
2 A when the 230 V mains is connected to the Electrobloc.
W
Danger of explosion from formation of detonating gas due to an incor-
rectly set battery selector switch, defective batteries, defective Electro-
bloc or an excessively high battery working temperature (more than
30 °C).
W
An incorrectly set battery selector switch damages the living area battery.
W
Disconnect the Electrobloc from the mains before adjusting the battery
selector switch.

SDT-0054-00EN Situation: 15.06.2005 7
Instruction Manual Electrobloc EBL 99 G
6.3 Battery monitor
Automatic disconnector The battery monitor compares the voltage of the living area battery to a refer-
ence voltage. As soon as the battery voltage falls below 10.5 V, all 12 V con-
sumers are switched off via the main switch relays 1 and 2. Only the frost pro-
tection valve is still powered. The automatic disconnector is not triggered by
short-term low voltage (less than 2 seconds), caused by high current when
switching on consumers.
If an overload or an insufficiently charged living area battery causes the volt-
age to fall so low that the automatic disconnector is triggered, any consumers
which are not essential should be switched off.
You may be able to switch on the 12 V power supply for a short time. To do
this, switch on the 12 V main switch on the control and switch panel.
However, if the battery voltage remains below 11.0 V, you cannot switch the
12 V power supply back on.
Fully charge up the living area battery as soon as possible. For more informa-
tion see the description of battery voltage.
7 Maintenance
The Electrobloc requires no maintenance.
Cleaning Clean the Electrobloc with a soft, slightly damp cloth and mild detergent.
Never use spirit, thinners or similar substances.
Do not allow fluid to penetrate the inside of the Electrobloc.
8 Shutting down the system
Disconnecting the living
area battery from the 12 V
power supply
Disconnect the living area battery from the 12 V power supply if you are not
going to use the motorhome for a lengthy period (for example during the
winter).
Switch off the 12 V main switch on the control and switch panel.
Set the battery cut-off switch on the Electrobloc to "Batterie Aus" (battery
off).
Remove the plug "+ Solarzelle" (+ Solar Module) on the solar charge reg-
ulator, if the battery is going to be removed.
Pull out the fuse for the AES refrigerator.
W
Before and after shutdown, the living area battery must be fully recharged
to avoid battery damage. For this purpose the vehicle must be connected
to mains supply for a minimum of 12 hours with an 80 Ah battery and
24 hours with a 160 Ah battery.
W
Do not operate the Schaudt solar charge regulator without a battery. This
might damage the solar charge regulator or any connected consumers. If
the battery is going to be changed or removed, please first take off the pos-
itive lead "+ Solarzelle" (+ Solar Module) on the solar charge regulator.
W
When the living area battery is separated from the Electrobloc by the bat-
tery cut-off switch, the frost protection valve of the heater system opens.
Water may be lost. For more information, see the instruction manual of the
heater system.

8Situation: 15.06.2005 SDT-0054-00EN
Instruction Manual Electrobloc EBL 99 G
9 Changing the battery
Only use batteries of the same type and capacity and those installed by the
manufacturer.
You can change from lead acid to lead gel batteries.
You cannot change from lead gel to lead acid batteries. Ask your dealer for
advice.
Theswitchingoptionprovidedbythebatteryselectorswitchensuresoptimum
charging of the two different types of battery, lead acid and lead gel. The
switch must be set to the correct battery type: lead acid or lead gel.
Use a thin object (e. g. a ballpoint pen cartridge) to move the battery selector
switch.
Set lead gel battery: Set the battery selector switch to "Blei-Gel" (lead gel).
Set lead acid battery: Set the battery selector switch to "Blei-Säure" (lead
acid).
Starting up the system Set the battery cut-off switch on the Electrobloc to "Batterie Ein" (battery
on).
After switching on the battery cut-off switch or after changing batteries:
Switch on the 12 V main switch on the control and switch panel briefly to
start up the consumers.
W
The living area battery can also be charged using the internal charger
module, an auxiliary charging unit, the solar charge regulator and the alter-
nator when the battery cut-off switch is switched off.
W
Batteries may only be changed by qualified personnel.
W
Follow the instructions of the battery manufacturer.
W
To disconnect the battery from the Electrobloc, all you need to do is set the
battery cut-off switch on the Electrobloc to "Batterie Aus" (battery off).
W
Charging unsuitable types of battery may irreparably damage them.
W
Only use the Electrobloc for connecting the 12 V power supply to 6-cell
lead gel or lead acid batteries.
W
Danger of explosion from formation of detonating gas due to an incor-
rectly set battery selector switch, defective batteries, defective Electro-
bloc or an excessively high battery working temperature (more than
30 °C).
W
An incorrectly set battery selector switch damages the living area battery.
W
Disconnect the Electrobloc from the mains before adjusting the battery
selector switch.

SDT-0054-00EN Situation: 15.06.2005 9
Instruction Manual Electrobloc EBL 99 G
10 Technical faults, possible causes and remedies
If you are unable to solve a fault using the following tables, please contact our
customer service address.
If this is not possible, e. g. if you are abroad, you can have the Electrobloc
repaired at a specialist workshop.
Inexpert repairs invalidate the guarantee for the Electrobloc and Schaudt
GmbH takes no liability for any resulting damage.
Fault Possible cause Remedy
Living area battery is not
charged during 230 V
operation (battery voltage
constantly below 13.3 V)
No mains voltage Switch on the automatic
fuse in the vehicle
Have the mains voltage
checked
Defective Electrobloc Call customer service
Living area battery is over-
charged during 230 V
operation (battery voltage
constantly above 14.5 V)
Defective Electrobloc Call customer service
Starter battery is not
charged during 230 V
operation (battery voltage
constantly below 13.0 V)
No mains voltage Switch on the automatic
fuse in the vehicle
Have the mains voltage
checked
Defective Electrobloc Call customer service
Living area battery is not
charged during mobile
operation (battery voltage
below 13.0 V)
Defective alternator Have the alternator
checked
No voltage at D+ input Have the fuse and wiring
checked
Defective Electrobloc Call customer service
The living area battery is
overchargedduringmobile
operation (battery voltage
constantly above 14.3 V)
Defective alternator Have the alternator
checked
The refrigerator does not
work during mobile opera-
tion
No power supply to the
refrigerator Have the fuse and wiring
checked
Defective Electrobloc Call customer service
Defective refrigerator Have the refrigerator
checked
Solar charger does not
work (power supply and
engine are off)
Solar charge regulator not
plugged in Plug in the solar charge
regulator
Defective fuse or wiring Have the fuse and wiring
checked
Defective solar charge reg-
ulator Have the solar charge reg-
ulator checked

10 Situation: 15.06.2005 SDT-0054-00EN
Instruction Manual Electrobloc EBL 99 G
11 Customer service
Customer service address Schaudt GmbH, Elektrotechnik & Apparatebau
Daimlerstraße 5
88677 Markdorf
Germany
Phone: +49 7544 9577-16
Email: kundendienst@schaudt-gmbh.de
Sending in the device Returning a defective device:
Always use well-padded packaging.
Fill in and enclose the fault report, see section 13.
Send it to the addressee delivered free.
Disposal instruction When the productservice lifeisover, disposeofthe device in accordancewith
the applicable regulations.
12 V power supply in the
living area does not work 12 V main switch for theliv-
ing area battery is
switched off
Switch on the 12 V main
switch for the living area
battery
Battery cut-off switch is
switched off Switch on the battery cut-
off switch
Defective fuse or wiring Have the fuse and wiring
checked
Defective Electrobloc Call customer service
Fault Possible cause Remedy
W
If the device becomes too hot due to excessive ambient temperature or
lackof ventilation,thechargingcurrentisautomatically reduced.However,
always prevent the device from overheating.
W
If the automatic shutdown mechanism of the battery monitor is triggered,
fully charge up the living area battery.
Opening hours Mon to Thu
Fri 8 to 12 a.m., 1 to 4 p.m.
8 to 12 a.m.

SDT-0054-00EN Situation: 15.06.2005 11
Instruction Manual Electrobloc EBL 99 G
12 Block diagram - for specialist workshop only
Fig. 2 Block diagram of Electrobloc EBL 99 G
SDT00233
&KDUJLQJUHOD\
6%
01/VRFNHWFDS[EORFN
$X[LOLDU\FKDUJLQJXQLW
1HJDWLYHFKDUJLQJXQLW
0DLQV 9a+]VRFNHW
6ZLWFKEHWZHHQ
OHDGJHO
OHDGDFLG %DWWHU\FXWRIIUHOD\
7KHQHJDWLYHSROHRIWKHOLYLQJDUHDEDWWHU\PXVWEH
FRQQHFWHGH[WHUQDOO\WRWKHQHJDWLYH SROHRI
WKH VWDUWHU EDWWHU\
0DLQVZLWFKUHOD\$ 0DLQVZLWFKUHOD\$
6%EDWW
6KXQW /$%EDWW
1HJDWLYH/$%
05SLQFDS[EORFN
0DLQVLQGLFDWRU
6KXQWEDWWHU\
6KXQWFRQVXPHU
9RQ
9RII
9LQGLFDWRU
1HJDWLYHVHQVRU/$%EDWW
6HQVRU/$%EDWW
6%EDWW
%DWWHU\FXWRIIVZLWFK2II 5HIULJHUDWRUUHOD\ 1RWDVVLJQHG
1RWDVVLJQHG
1RWDVVLJQHG
&LUFXLWERDUG.3/(%/D
7\SHQR
5HIULJHUDWRUUHOD\ 01/VRFNHWFDS[EORFN
01/VRFNHWFDS[EORFN HDFK
PPð
PD[P
6HQVRU/$%
1HJDWLYHVHQVRU/$%
)URVWSURWHFWLRQYDOYH $ 6%IRUUHIULJHUDWRU
+HDWHU 'LQSXW
$ 1HJDWLYH6%IRUUHIULJHUDWRU
)ORRUOLJKW
VWHS 01/VRFNHWFDS[EORFN
&RPSUHVVRU$(6UHIULJHUDWRU
01/VRFNHWFDS [EORFN $EVRUEHUUHIULJHUDWRU
'EDVH
$
6RODUFKDUJH
UHJXODWRU
/56
1HJDWLYHUHIULJHUDWRU
01/VRFNHWFDS[EORFN
/$% OLYLQJDUHDEDWWHU\
6% VWDUWHUEDWWHU\
5HIULJHUDWRUOLQHVPXVWEHOHDGWRWKH
EDWWHU\SROHVZLWKRXWEHLQJFRQQHFWHGWR
RWKHUEDWWHU\VXSSOLHV
01/VRFNHWFDS[EORFN 79
6RODUPRGXOH
RQO\IRU/5 3XPS
PD[$
&LUFXLW
6SDUH
&LUFXLW
PD[$ PD[$
6SDUH
PD[$
6SDUH
6SDUH
PD[$ PD[$
6SDUH 6SDUH
1RWDVVLJQHG

12 Situation: 15.06.2005 SDT-0054-00EN
Instruction Manual Electrobloc EBL 99 G
13 Fault report
In the event of damage, please return the defective device together with the
completed fault report.
There is the following defect:
(please tick)
Other remarks:
Device type:
Type no.: EBL 99 G
911.417
Battery not
being charged
during power
operation
Battery not
being charged
during mobile
operation
The following
electrical con-
sumers do not
work:
Malfunction of
control and
switch panel Tank Voltage Current
Constant fault
Temporary
fault/loose con-
tact
This manual suits for next models
1
Table of contents
Other Schaudt Controllers manuals
Popular Controllers manuals by other brands

SIPOS
SIPOS Seven Aktorik Ecotron Series Operation instructions

Franklin Electric
Franklin Electric SubStart SC Assembly and operation instructions

BridgIoT
BridgIoT Geasy MK6 instruction manual

Auber Instruments
Auber Instruments AW-SYL-2352 instruction manual

Hayward
Hayward OmniPL Retrofit Kit Operation manual

GE
GE IC697GDC701 manual

Adaptec
Adaptec 39320D user guide

ADB Safegate
ADB Safegate IDM 8000 user manual

SSV Works
SSV Works BMC Installation and user guide

Lightronics
Lightronics SR517D manual

Infineon Technologies
Infineon Technologies ICE2PCS Series Design guide

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series Configuration manual