SCHIEBEL SMARTCON Manual

actuators.schiebel.com
Actuator-control unit
SMARTCON ®
Short instruction
Operation
Set-up of travel-end limits
SCHIEBEL Antriebstechnik GmbH
Josef-Benc-Gasse 4
1230 Wien
Your success is our actuator

POSITION SELECTOR-SWITCH DESCRIPTION CONTROL-SWITCH FUNCTIONS
OFF The „OFF“ position of the red Selector-switch
serves the black Control-switch for browsing
through the menus. The bigger the angle of the
switch is the faster you can browse through the
menu.
+ Browsing up: Status-Info S1 to S6
History-information H1 to H20
- Browsing down: Parameters P1 to P20
The angle respectively the speed of the switches is
being shown by a thin line at left and right border of
the display.
With the red switch you activate the edit-mode and
you save or dismiss the adjustments.
In the edit-mode you change values of parameters
with the black switch.
LOCAL
If the red Selector-switch is engaged in “LOCAL”
the black Control-switch serves as OPEN-STOP-
CLOSE switch.
+ up: actuator opens the valve (left turning)
- down: actuator close the valve (right turning)
REMOTE
If the red Selector-switch is engaged in “REMOTE”
the control system operates the actuator.
With the black Control-switch it is still possible to
browse through the menu to view Status-informa-
tion or parameter adjustments.
Parameters can only be changed when the red
Selector-switch is in „OFF“ position.
SELECTOR-SWITCH
LOCAL-OFF-REMOTE
Status-info
History data
Parameters
P1 to P20
Open
Close
General overview/functions/handling of control unit SMARTCON ®
LOCAL-control
Dismiss
Infrared-Interface
Confirm
REMOTE-control
Browsing through the menu (status/History-
information)
Open-valve
Symbols
Symbols
Symbols
Close-valve
Browsing through the menu (parameters)
Symbols
Valve position indication
LED glows: Valve is opened or closed
LED blinks: Valve is being opened or closed
Status indication:
LED’s glows:Actuator is ready
LED’s blinking or not glowing: Failure (actuator is not ready)
Display
Status-info
History data
Parameters
P1 to P20
Confirm
Save
Dismiss
Main Display
Practice hints:
- Hold and operate the switches always with thumb , middle- and trigger finger.
- While browsing through the menu change the angle off the switch slowly and constantly until you reach the parameter, then let the
switch rebound.
- The higher the angle of the switch is the faster you can browse through the menu.
- Pay attention to the lines with the speed indication on both sides of the display. To browse through the menu it is enough to have a short line
( 3 speeds)
- The most important parameters are at the beginning of the parameter menu.
- For the activation of the edit mode respectively to save changed parameters push the red switch up (2-3 barlines) and let it rebound. Wait for
a moment (~1sec) if the value is saved (display changes from „Save?“ to „Edit?“ and vice versa.
- If you browsed too far in the menu , you can get very easy to the main display with a quick push on the black switch.
- In the „Stop“ position oft he black switch and a short push on the red switch you get also to the main display.
CONTROL-SWITCH
OPEN-STOP-CLOSE
Stop
Stop
Stop
Off
page 2
Optical
Indication
of
speed

STEP 1
For the adjustment of the
end positions the selector-
switch and the control-
switch have to be horizontal.
STEP 2 **
Push the hand leaver down
and move the hand wheel
while pushing. Close the
valve with the hand wheel.
After reaching the „CLOSE“
position of the valve turn 0,5
to 1 revolution back to con-
sider a possible over-run.
STEP 3
Unscrew the cover of signal
unit to get to the travel
device.
Travel-device
STEP 4
Go up with the black
control switch to the status
menu S4.
STEP 5
Turn the slotted screw
from travel device unit until
„Pos“-value is at 10.0.
1) If you have a mech.
position indicator turn at the
messing wheel.
STEP 6
Go with the black control
switch from menu S4 down
to parameter „1.2 End limit
CLOSE“.
You see on the display
„EDIT?“
STEP 7
Confirm the question
„EDIT?“ with a short pan of
the red selector switch to
get into the Edit-Mode.
You see on the display
„SAVE?“
STEP 8
Push the red selector
switch down until it locks.
You see on the display
„TEACHIN“(that means
the „Pos“ value which was
setted manually will be
automatically assumed)
STEP 9
Now let the red selector
switch spring back in the
„OFF“ position.
STEP 10
Now pan the red selector
switch up and let it rebound
to save the changed
parameter. You can see on
the display that „SAVE?“
changes to „EDIT?“ The
travel end position „CLOSE“
is now adjusted.The LED for
position „CLOSE“ is glowing.
STEP 11 ***
Push the red selector switch
down, lock it in „LOCAL“
position. Move the black
control switch up to open
the valve. Before the valve
is fully open let the black
control switch rebound in
„STOP“ position.After that
bring the red selector switch
back in „OFF“ position.
STEP 12 **
Both switches are in neutral
horizontal position. Push
the hand lever down while
moving the hand wheel.
Open the valve with the
hand wheel.After valve is in
„OPEN“ position turn 0,5 to
1 revolution back to consider
a possible over-run
STEP 13
Go with the black control
switch down to parameter
„1.1 End limit OPEN“.
You see on the display
„EDIT?“
STEP 14
Confirm the question
„EDIT?“ with a short pan of
the red selector switch to
get into the Edit-Mode.
You see on the display
„SAVE?“
STEP 15
Push the red selector
switch down until it locks.
You see on the display
„TEACHIN“.
STEP 16
Now let the red selector
switch rebound into the
neutral position „OFF“
STEP 17
Now pan the red selector
switch up and let it rebound
to save the changed
parameter. You can see on
the display that „SAVE?“
changes to „EDIT?“ The
travel end position „OPEN“
is now adjusted.The LED for
position „OPEN“ is glowing.
STEP 18
Push the red selector switch
short down the get back to
the main display. Mount the
cover of the signal unit and
fasten the screws.ATTEN-
TION: Pay attention that the
sealing is mounted correct.
OPEN and CLOSE the
valve to make a test drive.
1)
Adjustment of the travel end positions for right closing valves
It is assumed that the actuator has been correctly assembled and electrically connected
CAUTION – use this short instruction always in combination with main instruction manual!
* This short instruction do not replace our main instruction!
* It is designed for skilled people who are acquaint with our main instruction in which safety instructions, mounting,
handling and start-up are described.
* The main instruction must be always available!
STEP 19: If the valve should be closed by torque the Parameter „P 1.4 End limit Switch off CLOSE“ must be changed to value „1 – by torque“ and saved.
** The hand lever de-clutchs automatically during electr. mode, so please DO NOT try to push the hand lever manually up!
*** Stop the drive early enough before reaching the limit position and pay attention to the over-run to avoid damages at the valve or the gearbox!
NOTE:
- During the adjustment of left hand closing valves proceed exactly as if the valve would be right closing. Turn the hand wheel right and adjust end limit CLOSE (though valve is
opened).At the end edit Parameter „P 1.5 End limit Closing direction“ to value „1“ – inverse (ccw). The cross-bonding of all signals and commands happens automatically by the
control unit.
- The LED indication of the valve positions CLOSE & OPEN can be changed in parameter „P 1.7“ (standard: CLOSE=GREEN, OPEN=RED)
page 3
Table of contents
Other SCHIEBEL Controllers manuals
Popular Controllers manuals by other brands

PRECISION DIGITAL
PRECISION DIGITAL Helios PD2-6310 instruction manual

blazer
blazer CWL623 owner's manual

Savant
Savant Director Lite HST-DIRECTORLITE Quick reference guide

Hanna Instruments
Hanna Instruments HI 8931 instruction manual

Parker
Parker AC30 series Technical manual

Rockwell Automation
Rockwell Automation Allen-Bradley AADvance T9110 System Build Manual