SDC S6000-101 User manual

DELAYED EGRESS SYSTEM
S6000-101 DEVICE (ALL-IN-ONE DEVICE)
Code Compliance
IFC International fire Code
IBC International Building Code
NFPA 101 Life Safety Code
NFPA 1 Uniform Fire Code
California Building Code with the exception of Sec. 11B-309.4 2013 edition.
Field selectable automatic or manual power up after emergency release or power loss.
Use of manual power up complies with California Building Code (OSHPD) requirements.
UL 294, 6th Ed performance Level I – Line Security, Destructive Attack, Standby Power
and Level IV Endurance
P:\INSTALLATION INST\Delayed Egress\INST-S6000-101.vsd Rev D.1 10-19 Page 1
When unauthorized egress is initiated by depressing the push pad of the S6000-101, an audible alarm will sound and an
irreversible unlock delay period of 15 seconds will begin. Meanwhile, the person exiting must wait to egress, allowing
personnel or security time to respond to the alarm. After the delay period has expired, the device unlocks, permitting
egress until the device is reset. In a life safety emergency, the device will immediately unlock upon loss of power or
when powered by a fire control supervised power supply. The included signage provides clear and comprehensive
instructions of the door egress operation for persons without prior knowledge of the exit delay, including the sight and
hearing impaired.
Standard Features:
Egress Delay
15 second exit delay
1 or 2 second nuisance delay
Optional 30 second delay with AHJ approval
Control Inputs
Field-selectable 1 to 30 second request-to-exit with anti-tailgate
and door prop alarm.
Bypass
Reset
Remote trigger (for Pairs of Doors)
DPS (Required for Door Forced, Prop and Anti-Tailgate)
Built-In Visual & Audible Annunciation
Armed mode
Nuisance mode
Irreversible egress mode
Release mode
Monitoring Outputs
Secure/Unsecure status
Egress initiation status
Released/Bypass status
Trigger Modes
Egress alarm triggered by Push Bar
Trigger input from external device (Pair of Doors)
Door opened in secure mode (Door Forced or Prop)
801 Avenida Acaso, Camarrillo, Ca. 93012 ▪(805) 494-0622
600 Series Power Supply
(sold separately)
S6000-101 Applications include:
Restricting the egress of wandering patients for their own safety.
Restricting the egress of commercial center patrons for security application needs.
Controlling pedestrian traffic in transportation facilities, including airport jetways and tarmacs.
Reducing shoplifting and employee theft.
Compatible with access control for entry using Electrified Trim for rim and vertical rod devices.
When using mortise devices the mortise case is electrified to control entry.
Recommended Accessories
S6000DES Series – Delayed Egress Slave Exit Device
(for Pair of Doors)
600 Series regulated & filtered power supply –
602RF (1 Amp) or 631RF (1.5 Amp)
Door contact (included) – MC-4 recessed magnetic switch
Power Transfer Device – PTH-10, PTM-10 Series, PT-5
FWAX
SPECIAL LOCKING
ARRANGEMENTS
Rim Mount, Vertical Rod, or Mortise Exit Device
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
*NOT COMPATIBLE WITH
ELECTRIC RIM STRIKES

S6000-101 Series – Operational Description
The door is normally closed and secured by the S6000-101 Delayed Egress Exit Device. The on-board status LED
illuminates Green indicating that the unit is secured. The integral Reset/Bypass key switch is in the center position.
Activation/Alarmed Release:Pressing the push pad of the S6000-101 device initiates the irreversible 15 second
unlock delay cycle. To prevent false alarms, a pre-alarm audible warning tone is activated during the short nuisance
delay period. Releasing the push pad during the nuisance delay period will silence the pre-activation warning tone,
reset the unlock delay cycle, and keep the door locked.
Once the nuisance delay period has been exceeded, the S6000-101 continues its irreversible door release cycle. An
audible tone and Yellow status LED inform the person intending to exit of the door release cycle activation. An alarm
output is activated to alert personnel of an unauthorized exit. After the delay cycle has expired, the status LED
illuminates Red, and power is removed from the locking device, allowing free egress by pressing the push pad. A second
output is activated indicating that the door is unsecure.
Reset/Relock (from an Alarm, REX, or Bypass state): The S6000-101 can be manually reset by authorized
personnel by closing the door and turning the integral key switch to the reset position, or by momentarily activating a N/O
switch connected to the remote Reset/REX control input.
Request-to-Exit (from a Secure state): A timed Request-to-Exit (REX) cycle is initiated by authorized personnel by
momentarily turning the integral key switch to the reset position, or by momentarily activating a N/O switch connected to
the remote Reset/REX control input. The power will be removed from the locking device allowing free egress by pressing
the push pad. The on-board status LED will rapidly flash Green (2x / sec) during the REX cycle. After the REX cycle has
expired, the S6000-101 will automatically re-apply power to the locking device to re-secure the door. If an external door
position switch is connected to the DPS input, the door will automatically relock on door closure.
Authorized Maintained Bypass (from a Secure state): Unlocking the door for an extended period of time is
accomplished by momentarily turning the integral key switch to the Bypass position, or by momentarily activating a N/O
switch connected to the remote Bypass control input. The power will be removed from the locking device allowing free
egress by pressing the push pad. The on-board status LED will slowly flash Green (1x / sec) during Bypass mode. The
S6000-101 may be re-secured using the Reset procedure described above.
(BOCA/Chicago)
The S6000-101 operation complies
with BOCA National Building Code
and the Chicago Building Code: UL
Listed, Special Locking Arrangements
and Auxiliary Locks.
Option
Code Delay Release
Time Nusiance
Time Reset after
Alarm Lock Status on
Power-Up
Auto/Manual
BD 15 sec
Fixed 1 sec or 2 sec
Selectable Locked or Unlocked
Selectable
Auto/Manual
BH 30 sec
Fixed 1 sec or 2 sec
Selectable Locked or Unlocked
Selectable
Auto/Manual
BC 15 sec
Fixed 0 sec
Fixed Locked or Unlocked
Selectable
Per BOCA compliance, the S6000-101 is manually reset by authorized personnel after an alarm by closing the door and
turning the integral key switch to the reset position, or by momentarily closing a contact connected to the remote Reset/
Bypass control inputs. In addition, a reset will be automatically be initiated once the door has been opened, then closed,
and remains closed for 30 consecutive seconds.
(NFPA-101)
The S6000-101 operation complies
with the following building and fire
codes: NFPA 101; NFPA 1-UFC;
UBC; IBC; IFC; SBC; California
Building Code. Listings: UL Listed:
Special Locking Arrangements and
Auxiliary Locks; California State Fire
Marshal (CSFM) Listed.
Option
Code Delay Release
Time Nusiance
Time Reset after
Alarm Lock Status on
Power-Up
Manual
ND 15 sec
Fixed 1 sec or 2 sec
Selectable Locked or Unlocked
Selectable
Manual
NH 30 sec
Fixed 1 sec or 2 sec
Selectable Locked or Unlocked
Selectable
Manual
15 sec
Fixed 1 sec or 2 sec
Selectable Unlocked
Fixed
NC
(CBC Compliant)
P:\INSTALLATION INST\Delayed Egress\INST-S6000-101.vsd Rev D.1 10-19 Page 2
(AHJ Approval)
(AHJ Approval)

P:\INSTALLATION INST\Delayed Egress\INST-S6000-101.vsd Rev D.1 10-19 Page 3
631RF
Power
Supply
AC Mains
4 to 10
conductors
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
2
conductors
2
conductors
3
conductors
4
Conductors
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
2
conductors
J-Box
2 to 10
conductors
602RF
Power
Supply
AC Mains
2 to 10
Conductors
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
Power Transfer
Device or Hinge
DPS
2
conductors
2
conductors
3
conductors
Single Door Pair of Doors
WARNING!
CONTACT THE AUTHORITY HAVING JURISDICTION
FOR APPROVAL PRIOR TO SELECTING NUSIANCE
TIME OR PWR-UP SETTINGS
DIP SWITCH SETTINGS
1s 2s
15s 20s 30s 1s
ON
[ON]
[OFF]
1234
NUISANCE
DELAY
REX
PERIOD
PWR UP
STATE
MONITOR RELAY JUMPER SETTINGS*
UNLOCKED LOCKED
J6 = GRN RELAY (Active when device is secure)
J7 = RED RELAY (Active upon alarm initiation)
2 Left Pins = N/O
2 Right Pins = N/C
S6100-101 RIM DEVICE S6200-101 SURFACE
VERTICAL ROD DEVICE
DPS DPS
S6000-101 Board Layout (LR Device shown)
1234
ON
*Individually sets the polarity of the GRN & RED
relays when the relay is in an ACTIVE state.
FACP
Power Transfer
Device or Hinge Power Transfer
Device or Hinge
FACP

P:\INSTALLATION INST\Delayed Egress\INST-S6000-101.vsd Rev D.1 10-19 Page 4
Device Wiring Pigtail
THIS PRODUCT MUST BE POWERED BY A 600 SERIES POWER SUPPLY:
Single Door – 602RF 1 AMP
Double Door – 631RF 1.5 AMP
3
A DOOR CONTACT IS REQUIRED FOR ANTI-TAILGATE, BOCA AND DOOR PROP FUNCTIONS.
4
WIRING SHALL BE CONNECTED TO AN ACCESSORY WITHIN THE PROTECTED AREA AND UNUSED WIRE MUST BE CAPPED OFF.
2
Max Operating Temperature: 0 C to 70 C
Tested to 85% RH @30 C
Enviromental:
Input Voltage : 24VDC +/- 10%
Slave Output : 24VDC @250ma
Monitor Relays: 1 Amp contacts @12/24vdc
Input Current : 540ma Max
Electrical Specifications:
GRY = DPS1,4
ORG = Slave Out1
VIO = Remote Trigger1
BRN = Red Relay1
GRN = Green Relay1
YEL = Relay Common1
BLU = Reset / REX1
WHT = Bypass1
RED = Power In (+) 3
BLK = Power In (-) 3(24VDC)
(For pairs of doors)
(24vdc @ 250ma)
Wire Color Wire Designation Description
Usedforapairofdoors(master&slave).Thisisavoltageoutput(24VDC@250mA).
Connectthiswireto+24VDC(Redwire)oftheslavebar.
See"TypicalWiringforSingleorDoubleDoorInstallation".
Usedforapairofdoors(master&slave).Thisisadryinput.Connectthiswireto
onelegoftheSlaveTriggeroutput.TheotherlegoftheSlaveTriggeroutputis
connectedtoground(‐VDC).Closingtheswitchshortsthiswiretogroundand
initiatesthealarmsequence.
See"TypicalWiringforSingleorDoubleDoorInstallation".Thetwowhitewires
ontheslavebararetheNormallyOpentriggerswitch.
Brown RedRelay
ThisistheAlarmRelayOutput(Dry,1A@12/24VDC).ItisnormallyINACTIVEwhen
thedoorissecure.Itchangesstatewhenthebarispressedbeyondthenuisance
delayandplacedintoanAlarmstate.ItmaybeconfiguredasNormallyOpenOR
NormallyClosedusingJumperJ7.TheYELLOWwireistherelaycommon.
Green GreenRelay
ThisistheDoorSecureRelayOutput(Dry,1A@12/24VDC).ItisnormallyACTIVE
whenthedoorissecure.Itchangesstatewhenthebarunlocksafter(a)the
delayedegresscountdownexpires,(b)anauthorizedRequest‐to‐Exit(REX)signal,
or(c)thebarisBypassed.ItmaybeconfiguredasNormallyOpenORNormally
ClosedusingJumperJ6.TheYELLOWwireistherelaycommon.
Yellow RelayCommon ThisisthesharedrelaycommonforboththeRed&GreenRelay.
Grey DoorPositionSwitch(DPS)
Thisisadryinput.ConnectthiswiretoonelegofaDoorContactswitch.Theother
legoftheDoorContactswitchisconnectedtoground(‐VDC).TheDoorContact
polaritymustbeOPENwhenthedoorisclosed.Adoorcontactisrequiredforanti‐
tailgateanddoorpropalarmfunctions.
Thisisamomentary,dryinput.ConnectthiswiretoonelegofaNormallyOpen
switch.TheotherlegoftheNormallyOpenswitchisconnectedtoground(‐VDC).
Whenthebarisinasecurestate,shortingthisinputwillresultinanauthorized
unlock(REX).TheREXperiodisconfiguredbythedipswitchsettings.
Whenthebarisinanalarm,authorizedunlockstate,orinabypassedstate,
shortingthisinputwillreset(secure)thebar.
White Bypass
Thisisamomentary,dryinput.ConnectthiswiretoonelegofaNormallyOpen
switch.TheotherlegoftheNormallyOpenswitchisconnectedtoground(‐VDC).
Whenthebarisinasecurestate,shortingthisinputwillunlockthedevice
indefinitely,untilthebarisReset.
Red PowerIN(+)24VDC
Black PowerIN(‐)24VDC
InputVoltage:24VDC+/‐10%;InputCurrent:540mA(max).TheRed&Blackwires
aretheminimumrequiredconnectionsforasingledoorapplication.
Blue Reset/REX
Orange SlaveOut
RemoteTriggerViolet
MAXIMUM CONNECTED WIRING LENGTH PERMITTED IS 98.5 FT. (30).
1

BLU (Reset)
WHT (Bypass)
RED (+)
BLK (-)
Power
Transfer
24VDC
101-1AK
REMOTE ANNUNCIATOR
BYPASS/RESET
(OPTIONAL)
TYPICAL WIRING FOR SINGLE OR DOUBLE DOOR INSTALLATION
YEL (Rly – COM)
631RF
POWER
SUPPLY
GRN
BRN
MASTER
Power
Transfer
SLAVE
PIGTAIL
WHT
WHT
BLK
RED
VIO (Remote Trig)
ORG (+24VDC Out)
MC-4**
Door
Contact
(Master)
MC-4**
Door
Contact
(Slave)
GRN
WHT
GRY
(DPS)
GRN
WHT
**Door Contact connection MC-4
is provided with every Master
Unit. Use for anti-tailgate, BOCA,
door prop alarms and added
security.
NOTE: Red & Blk pigtail wires are
the minimun required connections for
a single door application.
KEY CYLINDER INSTALLATION & OPERATION
Key cylinder is in the normal, center
position. LED is solid green when the
device is secure.
To bypass the device for an extended
period of time, momentarily turn the
key cylinder towards “Bypass” and
return to the center position. LED will
flash slowly.
When the device is in a secure state, momentarily
turning the key cylinder towards “Reset” will result
in a timed authorized unlock (REX).
When the device is in an alarm, authorized
unlock, or bypassed state, momentarily turning
the key cylinder towards “Reset” will re-secure the
device.
P:\INSTALLATION INST\Delayed Egress\INST-S6000-101.vsd Rev D.1 10-19 Page 5
SDC S6000-101
SDC S6000-DES
INSTALL 1-1/8" MORTISE
CYLINDER (NOT SUPPLIED)
INTO DEVICE COVER AS
SHOWN ON PAGE 7.
SDC P/N: CYL-6KDQ

P:\INSTALLATION INST\Delayed Egress\INST-S6000-101.vsd Rev D.1 10-19 Page 6
BLU (Reset/REX)
WHT (Bypass)
RED (+)
BLK (-)
Power
Transfer
24VDC
YEL (Rly – COM)
SDC 600 Series
REGULATED & FILTERED
POWERSUPPLY
GRN
BRN
MASTER
MC-4**
Door
Contact
GRN
WHT
GRY
(DPS)
**Door Contact connection MC-4 is provided with
every Master Unit. Use for anti-tailgate, BOCA,
door prop alarms and added security.
ORG
VIO
NOTE: 24VDC VOLTAGE CONFIGURATION W/ NO OPTIONS
4' - Conductor Cable
standard 24vdc @ .3 AMP
RED (+)
BLK
BLU
WHT (-)
SDC ELECTRIC TRIM
EKE03/GKE03 SERIES
ACCESS
CONTROL
SYSTEM
C
N/C
N/O
Installation Note: Cap any unused leads.
+(‐)
MOV*
TYPICAL WIRING FOR SINGLE DOOR WITH SDC ELECTRIC TRIM
SDC S6000-101
*Install MOV across
coil to protect device
electronics.
J6 = GRN RELAY (Active when device is secure)
2 Left Pins = Set for Fail-Secure Electric Trim
2 Right Pins = Set for Fail-Safe Electric Trim
NOTE: SDC Electric Trim not available for S6300 Mortise Device
STATUS LED INDICATIONS
Status DeviceMode
OFF NoPower
GREEN(Solid) Secure
YELLOW IrreversibleDelayinProgress
RED(Solid) Alarmed&Unlocked
GREEN(SlowFlash) Bypassed
GREEN(FastFlash) AuthorizedUnlock(REX)
RED(FastFlash) Alarmed,Unlocked,&DoorOpened
ELELCTRIC TRIM WIRES
MUST BE WIRED THRU THE
DOOR RACEWAY NOT
THROUGH THE EXIT DEVICE

Use the supplied Clover Tailpiece or equivalent.
P:\INSTALLATION INST\Delayed Egress\INST-S6000-101.vsd Rev D.1 10-19 Page 7
1 Install Key Cylinder as shown and secure with locking nut provided.
2 Remove and position Tailpiece as shown.
ILCO equivalent tail pieces:
863D
863S
3 Insert Key and check for proper operation.
(863J)
Table of contents
Other SDC Security System manuals
Popular Security System manuals by other brands

Safety Technology International
Safety Technology International STI-34150 Installation and operation manual

Honeywell
Honeywell TCPA1BS installation instructions

Buffalo filter
Buffalo filter BOWA Operator's manual

EISST
EISST H500-CE user manual

Interlogix
Interlogix DC108 Series Installation sheet

Johnson Pump
Johnson Pump SPXFLOW Bilge Alert instruction manual