SDC EA-728 Quick start guide

INSTALLATION INSTRUCTIONS
EA SERIES –DOOR PROP/EXIT ALARM
801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 •
www.sdcsecurity.com • E-mail: [email protected]
Any suggestions or comments to this instruction or
product are welcome. Please contact us through
our website or email engineer@sdcsecurity.com
EA SERIES TECHNICAL SPECIFICATIONS
P:\INSTALLATION INST\Accessories\INST-DOOR PROP.vsd Rev A 07-17 Page 1
Model EA-SN Model EA-728 Model EA-708
(cylinder not included)
The SDC EA Series offers Exit Alarm, Forced Door Alarm, and Door Propped/Held Open Alarm monitoring
capabilities to any controlled opening. It may be used as a standalone device or easily integrates with any
access control system. Units are typically mounted adjacent to the opening, and provide local visual and
audible alarm annunciation. An integral key switch is available for local bypass & alarm reset controls. A
built-in alarm relay is also included for remote monitoring.
FEATURES
Exit alarm on door opening
Manual or automatic alarm reset
Integral LED status indicator
Local 85dB Piezo buzzer alarm
Door prop alarm after adjustable timed delay
Main relay output for remote alarm notification
Auxiliary relay output for door position status or
bypass/alarm status
Optional key reset/bypass switch
Compact universal mounting
Input Power: 60mA @ 12 or 24VDC (Auto-sensing)
Mounting: EA-SN: Single Gang, 1/4" Thick aluminum plate w/ security screws
(2-1/8" depth recommended) EA-708, -728: Double Gang, 1/4" Thick aluminum plate w/ security screws
Alarm Sound Level: 85dB @ 3ft, Piezo Buzzer
Status Indicator: Bi-color LED
Trigger (DPS) Input: Dry, N/C or N/O, field selectable
Reset/Bypass (Control) Input: Dry, N/O or N/C, field selectable
Alarm (Main) Output: Form C, 2A @ 30VDC (Resistive)
Auxiliary Output: Form C, 2A @ 30VDC (Resistive)
Wiring: Screw terminals
EA-SN: 5"h x 3.25"w x 1.625" d
EA-708, -72
8
: 5"h x 5"w x 1.875"d
Overall Dimensions:

EA Series Board Layout (Back View):
1Configuration Jumpers – Numbered 1 through 5. By default, all jumpers have been set to OFF. Use the (5)
supplied jumpers, as required. See the table below for a functional description of each jumper.
2Adjustable Alarm Timer – Determines the amount of time a door can be propped open before an alarm is
activated. Adjustable from 1 to 60 seconds. Turn clockwise to increase time.
3Input Power Terminals – Requires a 12 or 24VDC +/- 10% power supply (auto-sensing).
4Control Input Terminals – Dry input used for bypass & alarm reset. Field-selectable as normally open
(default) or normally closed. In a secure state, a held input will bypass the unit. In an alarm state, a
momentary input will reset the alarm providing the door is closed.
This input is factory pre-wired for key switch model EA-728.
5Door Contact Input – Required for all models. Monitors the open/closed status of the door. Field-
selectable as normally open or normally closed (default).
6
7
Alarm Relay Output – Relay is energized when the unit is powered. An alarm state or loss of power will
de-energize the relay.
PWR (-)
PWR (+)
NO
NO
NC
NC
C
C
1
2
3
4
5
1s 60s
}
}
}
1
2
3
4
5
6
7
*The state of the Main & Aux. relays are
shown when the unit is not powered.
Auxiliary Relay Output – Relay may be configured to follow the DPS input OR to follow a bypass/alarm state.
P:\INSTALLATION INST\Accessories\INST-DOOR PROP.vsd Rev A 07-17 Page 2
Configuration Jumpers Jumper OFF Jumper ON
1= Latching Alarm
Disabled (Alarm resets on
door closure) Enabled. (Requires use of Control Input to reset an alarm OR Jumper #2)
2= Alarm Auto Reset Disabled Auto-reset 60 sec. after door closure. (Requires Jumper #1 to be ON)
3= Control Input Polarity Normally Open Normally Closed
4= DPS Input Polarity Normally Closed Normally Open
5= Aux. Relay Function Follows DPS Input Follows Bypass/Alarm State

EA Series Operational Modes:
Wiring Example #1 – Non-latching (auto-resetting) Exit Alarm or Door Prop Alarm.Opening
the door will initiate the pre-alarm timer. Closing the door before the timer expires resets the
timer. If the door remains open and the timer expires, an audible alarm will sound and the
Main Relay will trigger. Alarm resets on door closure. Bypass the alarm by activating the
integral key switch or via remote bypass switch.
(a) All jumpers are set OFF (default)
(b) Adjust the alarm delay timer (1-60 seconds), as required.
(c) Install & terminate a N/C door contact.
(d) Install & terminate optional output relays, as needed. See page 2 for relay descriptions.
(e) Apply power & test.
12 or 24VDC
P.S.
Key Switch Operation (EA-708 or 728 only):
Bypass (Maintained) –
90° Counter-clockwise.
Key may be removed. Return to
vertical position to re-secure.
Alarm Reset (Momentary) –
45° Clockwise. Key returns to
vertical position upon release.
Bypass
Reset
Bypass
Reset
EA-728 EA-708
See Page 5 for Mortise Key Cylinder
installation
Bypass (Maintained) –
Turn counter-clockwise until ON/OFF
switch is activated. Reactivate the
switch to re-secure.
Alarm Reset (Momentary) –
Turn clockwise until momentary
switch is activated.
NOTE: Unit must be Secure to be Bypassed. Door must be closed to reset an alarm condition.
LED Status Indicator:
N/C
N/O EA-SN: Optional Remote Bypass;
Pre-wired for model EA-728
Door Contact:
SDC Model MC-4 or similar
Alarm Relay for
remote monitoring
Power Supply:
SDC Model TR-12, TR-24, or 600 Series
Auxiliary Relay follow DPS input
P:\INSTALLATION INST\Accessories\INST-DOOR PROP.vsd Rev A 07-17 Page 3
G
G
R
G
G
Door Status Unit Condition LED Status Main Relay
Aux. Relay*
(Jumper 5 OFF)
Aux. Relay
(Jumper 5 ON)
Closed Secure Solid Green Energized De-energized Energized
Open Pre-alarm (1-60 sec.) Solid Green Energized Energized Energized
Open Alarm Solid Red De-energized Energized De-energized
Closed Bypassed Flashing Green Energized De-energized De-energized
Open Bypassed Flashing Green Energized Energized De-energized
*Relay state shown with N/C Door Contact

Wiring Example #2 – Latching (Manually Reset) Exit Alarm/Door Prop Alarm.Opening the door
will initiate the pre-alarm timer. Closing the door before the timer expires resets the timer. If the
door remains open and the timer expires, an audible alarm will sound and the Main Relay will
trigger & latch. Alarm must be reset by using the integral key switch (EA-708 or EA-728 only), or by
remote control switch. Bypass the alarm by activating the integral key switch or via remote switch.
(a) Jumpers 1 & 5 are installed. Jumpers 2, 3, & 4 are set OFF.
(b) Adjust the alarm delay timer (1-60 seconds), as required.
(c) Install Remote reset switch. Required for EA-SN; Optional for EA-708 or EA-728.
(d) Install & terminate a N/C door contact.
(e) Install & terminate optional output relays, as needed. See page 2 for relay descriptions.
(f) Apply power & test.
12 or 24VDC
P.S.
N/C
N/O
Door Contact:
SDC Model MC-4 or similar
Alarm Relay for
remote monitoring
Power Supply:
SDC Model TR-12, TR-24, or 600 Series
Auxiliary Relay changes state when the unit
enters bypass mode or alarm mode
P:\INSTALLATION INST\Accessories\INST-DOOR PROP.vsd Rev A 07-17 Page 4
PWR (-)
PWR (+)
NO
NO
NC
NC
C
C
1
2
3
4
5
1s 60s
EA-SN: Requires Remote Reset Switch;
Pre-wired for model EA-728
Wiring Example #3 – Double-Door Latching Exit Alarm/Door Prop Alarm with Timed Reset.
Opening the door will initiate the pre-alarm timer. Closing the door before the timer expires resets
the timer. If the door remains open and the timer expires, an audible alarm will sound and the
Main Relay will trigger & latch. The alarm will automatically reset 60 seconds after door closure.
The alarm may also be reset by using the integral key switch (EA-708 or EA-728 only), or by remote
control switch. Bypass the alarm by activating the integral key switch or via remote bypass switch.
12 or 24VDC
P.S.
N/C
N/O
Door Contacts:
SDC Model MC-4 (x2)
Alarm Relay for
remote monitoring
Power Supply:
SDC Model TR-12, TR-24, or 600 Series
EA-SN: Requires Remote Reset Switch;
Pre-wired for the EA-728
(a) Jumpers 1, 2 & 5 are installed. Jumpers 3 & 4 are set OFF.
(b) Adjust the alarm delay timer (1-60 seconds), as required.
(c) Install Remote reset switch. Required for EA-SN; Optional for EA-708 or EA-728.
(d) Install & terminate N/C door contacts in series.
(e) Install & terminate optional output relays, as needed. See page 2 for relay descriptions.
(f) Apply power & test.
N/C
PWR (-)
PWR (+)
NO
NO
NC
NC
C
C
1
2
3
4
5
1s 60s
Auxiliary Relay changes state when the unit
enters bypass mode or alarm mode

P:\INSTALLATION INST\Accessories\INST-DOOR PROP.vsd Rev A 07-17 Page 5
EA-708 Mortise Key Cylinder Installation:
Adjustable
Switch
Assembly
Locknut
Faceplate
Key Cylinder
SDC Part# CYL-KD
Switch
Mounting
Bracket
ASSEMBLY DETAIL
SOUND DAMPENER
All Exit Alarm Assemblies are shipped with a
sound dampening cap loose in the box.
Install the unit without the cap for full volume.
Install the unit with the cap as shipped for
complete dampening.
Install the unit with the center hole punched
out for partial dampening
triangular
tabs
Ensure that the cam makes
contact with the center of
the switch plunger
4. Complete the wiring connections by carefully routing the
(2) white & (2) yellow wire leads behind the board. Terminate
the (2) yellow wires to Control terminal “A”. Terminate the (2)
white wires to Control terminal “B”.
Or supply compatible 1” to
1-3/8” standard or
interchangeable core
mortise key cylinders (not
included)
Use tailpiece supplied with
SDC Part# CYL-KD, or Ilco
863G-00-10 Standard Cam
equivalent.
NO
(Reset)
SWITCH WIRING
YEL
WHT
COM
NO
YEL
WHT
COM
(Bypass)
WHT
WHT
YEL
YEL
A
B
CENTER HOLE
PUNCHED
CENTER HOLE
AS SHIPPED
This manual suits for next models
2
Table of contents
Other SDC Security System manuals
Popular Security System manuals by other brands

Vega Absolute
Vega Absolute M200 user manual

Morrison Bros. co.
Morrison Bros. co. 918AC Series Installation, operation and maintenance instructions

Esse-ti
Esse-ti HELPY COMPACT quick guide

Viking
Viking VS 1125 Installation & operation guide

Dräger
Dräger Bodyguard 1000 quick start guide

Tyco
Tyco Visonic MC-302EL PG2 installation instructions