Sea-Fire 131-740 User manual

SEA-FIRE MARINE –USA SEA-FIRE EUROPE, LTD
Baltimore, Maryland Hampshire, United Kingdom
Your Onboard Safe Choice www.sea-fire.com www.sea-fire.co.uk
A Division of Metalcraft, Inc. 123-652 REV -
Machinery Shutdown Restart
System (MSRS)
Installation Instructions
Owner’s Manual
PN: 131-740 (4 Relay Circuits), PN: 131-745 (6 Relay Circuits), and PN: 131-750 (8 Relay Circuits)
Warning: This Sea-Fire Machinery Shutdown Restart System has been designed and tested for use with Sea-Fire automatic and manual
Fire Suppression Systems. Installation must be accomplished by or under the supervision of a qualified marine electrician who is familiar
with American Boat and Yacht Council (ABYC) or other recognized and accepted marine standards and practices.
Caution: Do not install this device in fuel storage compartments. See the installation section of this manual for further details.
Read this manual thoroughly and comply with all instructions, warnings, and cautions prior to installation.
THIS MANUAL IS AN INTEGRAL PART OF THE SYSTEM AND AS SUCH, THE SYSTEM MUST BE INSTALLED AND MAINTAINED
ACCORDINGLY.
RETAIN THIS MANUAL FOR REFERENCE

Page 2of 11 123-652 Rev -
1GENERAL SPECIFICATIONS
Operating Voltage: 12 - 32 VDC
Backup Power Supply: 12 - 32 VDC
Power Supply Protection: 3A Fuses
Internal Voltage Protection - 3 diodes
Pressure Switch - 2 normally closed inputs
Visual Indications - POWER - Green
PS1 - Red
PS2 - Red
Buzzer: 85 dB @ 10 cm
Standby Power Consumption (All three Models)
13 VDC, 100 mA
28 VDC, 100 mA
Discharged Power Consumption
PN: 131-740: 13 VDC, 370 mA
28 VDC, 180 mA
PN: 131-745: 13 VDC, 570 mA
28 VDC, 260 mA
PN: 131-750: 13 VDC, 750 mA
28 VDC, 350 mA
Enclosure Material: Grey flame retardant ABS
Flame Rating: UL94-5VA (with textured cover)
Enclosure Protection level: Ingress protection 66 (IP66)
Operating Temperature: -7oC/20oF to 54oC/130oF
Storage Temperature: -7oC/20oF to 54oC/130oF
Display Connection: CAT-5 VIA RJ45 Socket
Relays: 5 VDC Form C –Normally Open (N/O) 20A
Normally Closed (N/C) 10A
Connectors - Wago 739, Max wire size 12AWG/2.5 mm
Dimensions: 7.29 (W) x 4.72(H) x 2.37(D) inch
185.17(W) x 119.89(H) x 60.20(D) mm
Weight: .6 kg / 1.3 lb.
Mounting: Surface
Compliant: RoHS, CE
1.1 Features
Fully automatic machinery shutdown system
Shutdown override mode
Power-On visual indication
Pressure Switch (PS1) Visual and audible indication (Agent Discharge)
Pressure Switch (PS2) Visual and audible indication (Sensor Switch Warning)
Compact construction
Optional Time Delay reset function
2OPERATION
The Machinery Shutdown Restart unit is a low voltage microcontroller unit designed to integrate with the Sea-Fire Fire
Suppression System to shut down the engine(s), blower(s), generator(s), damper(s) and other machinery in the protected
space should fire or extreme overheating cause the Sea-Fire automatic Fire suppression system to discharge. The
machinery shutdown will ensure that the fire suppression agent, in its proper concentration, will remain in the enclosed
compartment and not be ingested or reduced by the running machinery.
Immediately upon agent discharge, the MSRS PS1 closed loop circuit opens, activating the alarm and energizing all the
relays. Energizing the relays will change the state of the internal contacts and shut down all the machinery connected to
the MSRS unit. The PS1 LED on the Unit and the DISCHARGE LED on the Display Panel illuminate. The activated alarm can
be silenced by pressing the SILENCE button on the MSRS unit or on the connected Display Panel.
After a discharge or loss in cylinder pressure resulting in an opened PS1 loop, simultaneously pressing the SILENCE and the
“ ” buttons will put the MSRS into override enabling all the machinery connected to the MSRS to restart. The MSRS can
only be properly reset after the discharged agent cylinder has been refilled/replaced and then the SHUTDOWN RESET
buttons pressed to put the unit back into the standby mode. In the standby mode, only the green POWER LED on the MSRS
and the Display Panel will remain on.

Page 3of 11 123-652 Rev -
If there is a High-Temperature, Low-Pressure or an Auxiliary Discharge sensor switch connected to the PS2 terminals, when
the sensor switch opens, the alarm activates and both the PS2 LED on the unit and the Second Zone LED on the Display
Panel illuminate. There will be no change to the relays’state. The activated PS2 circuit alarm can be silenced by pressing
the SILENCE button on the MSRS box or on the connected Display Panel. Reset the unit after the PS2 circuit condition has
been remedied by pressing the SHUTDOWN RESET buttons. The unit is now in standby mode.
3MSRS INSTALLATION
CAUTION: Make sure all power sources are shut down before installation.
Install the MSRS unit in a conveniently accessible and well-ventilated location. The MSRS should not be exposed to environmental
temperatures (in excess of 54oC/130oF) for an extended period. This will affect the service life of the MSRS unit and may cause
premature failure.
3.1 Installation Location
It is important that the MSRS unit be installed in a location that will not build up heat or be exposed to external heat sources.
If installed in a box or cabinet, the enclosure should have sufficient ventilation.
When installed in the engine room, the MSRS should be installed with sufficient protection from the hazards of that space,
but must still have a way to dissipate heat and not be overheated by other sources.
WARNING: Do not install the MSRS Unit in a sealed enclosure.
3.2 Mounting the MSRS Unit
Use the MSRS unit 4 mounting screw holes (screw not included) to mount the unit. Connect the Display Panel to the MSRS unit via
the RJ45 socket using the CAT-5 cable. Longer CAT-5 cables (10’, 20’, 50’, 100’ and 150’) are available to increase the distance
between the MSRS and the Display Panel. Refer to the Display Panel installation manual for the correct installation instruction.
3.3 MSRS Unit Wiring Installation
Use a minimum of 16 American Wire Gauge (AWG) (SAE J3788 or J1128) according to American Boat and Yacht Council (ABYC) [or
equivalent international standard] marine grade wire to connect all devices and power to the MSRS. Connect the wire to the MSRS
unit by pushing a 1/8” flathead screwdriver into the square opening on the top of the terminal block. This opens the spring cage
allowing a stripped wire to be installed into the round hole on the connector. See Figure 1.
Figure 1 Terminal Block Slot
Properly ground all the Machinery connected to the MSRS unit.

Page 4of 11 123-652 Rev -
3.3.1 ELECTRICAL INPUT/OUTPUT CONNECTIONS
1
2
3
4
VIN1 +
VIN1 -
VIN2 +
VIN2 -
VIN3 +
VIN3 -
DISPLAY
PANEL
Figure 2: Input/output Terminal Block
3.3.1.1 MSRS Pressure Switch (PS1) Terminals 1 and 2 connection
Install one of the wires from the Cylinder Low-Pressure Switch or from the Discharge Pressure Switch to
the terminals marked “1”and the other wire to the terminal marked “2”.See Figure 2.
3.3.1.2 MSRS Pressure Switch (PS2) Terminals 3 and 4 connection
The MSRS unit has a wire jumper installed across PS2 terminals from the factory. If the MSRS PS2
terminals are being used, remove the wire jumper. Leave the wire jumper in-place if the PS2 terminals are
not being used.
Install one of the wires from the High Temp Sensor or the Cylinder Low-Pressure Supervisory Switch to the
terminal marked “3”and the other wire to the terminal marked “4”. See Figure 2.
oLow-Pressure Switch/Auxiliary Cylinder Supervisory Switch - When the pressure in the cylinder drops
to an unserviceable (low) pressure, the switch shall open activating the early warning alarm.
oTemperature Sensor –When the temperature in the protected zone goes above the fixed temperature
of the sensor, the sensor shall open activating the early warning alarm.
3.3.1.3 Power Supply Terminals –Main Supply, Backup Supply, and Generator
The MSRS Unit has 3 diode-protected inputs but only one power source is needed to operate the MSRS
and should be connected to V IN1+ and V IN1-. See Figure 2.
oIf available, a backup power source should be connected to one of the additional power source inputs.
Connect the MSRS unit to the power source(s) using a 5A circuit breaker with an ON/OFF switch. Use the
breaker switch to turn the MSRS Unit OFF when all the machinery is OFF and to turn the MSRS Unit ON if
any machinery is ON.
3.3.1.4 RJ45 Port
The RJ45 socket connects the Display Panel to the MSRS unit via a supplied CAT-5 cable. Install one end of
the CAT-5 cable into the MSRS unit RJ45 socket and the other end into one of the Display Panel RJ45
socket.
oConnect Multiple Display Panels to the MSRS unit by using the available RJ45 socket on the back of the
Display Panel.
Check the Display Panel Installation Manual on how to correctly connect and use the Display Panel.

Page 5of 11 123-652 Rev -
Compatible Display Panels: “Fire Suppression System Monitor and Engine Shutdown Control”
Part Number
Display Panel indicators and shape
131-460
Power and Discharge Indication, Rectangle
131-461
Power and Discharge Indication, Round
131-462
Power, Discharge, and High Temp Indication, Rectangle
131-463
Power, Discharge, and High Temp Indication, Round
131-464
Power, Discharge, and Aux Zone Indication, Rectangle
131-465
Power, Discharge, and Aux Zone Indication, Round
131-466
Power, Discharge, and Low-Pressure Indication, Rectangle
131-467
Power, Discharge, and Low-Pressure Indication, Round
3.3.1.5 Multiple Cylinder Supervisory Switch Connection to the MSRS PS1
When connecting more than one pre-engineered cylinder supervisory pressure switch to the MSRS Unit,
connect all the supervisory pressure switches in series. Connect the leading switch wire to Terminal
marked “1”and the trailing wire of the last pressure switch to Terminal marked “2” (See Figure 2).
When connecting more than one Engineered System cylinder supervisory switch to the MSRS unit, connect
all the cylinder supervisory switches in series. Connect the leading switch wire to Terminal marked “3”
and the trailing wire of the last pressure switch to Terminal marked “4” (See Figure 2).
When connecting more than one Engineered System discharge pressure switch, reference the engineered
fire suppression manual and electrical circuit diagram provided as part of the system.
3.3.1.6 Engine or Machinery connection
Refer to the Original Equipment Manufacturers (OEM) Engine or the machinery Installation manual for the
correct method of connection to relays of the MSRS unit. Equipment manufacturers have a variety of
methods to control their equipment.
The following section provides the basic operation of the relays in the MSRS unit.
4Relay Operation:
This section provides the basic operation of the relays in the ESRS unit.
4.1. Relay Contact Specification
Table 1 Relay Contact Specification
Item
Value
Contact
SPDT (1 Form C)
Contact Current
10A NC / 20A NO
Contact Voltage VAC (Maximum allowable)
277VAC
N/C –Normally Closed Contact
N/O –Normally Open Contact
COM –Common Terminal
4.2. Relay De-Energized State
When the MSRS is operational and in the standby mode, all the relays should be in the de-energized state.
The N/C and the COM terminals are connected.
The N/O terminal is open.

Page 6of 11 123-652 Rev -
4.3 Relay Energized State
When the MSRS is operational and is in the shutdown state, all the relays should be in the energized state.
The N/C terminal is open.
The N/O and the COM terminals are connected.
4.4 Relay 20 Second Reset
Automatic reset timer functions are optional in the MSRS. Please contact Sea-Fire Marine for additional
information regarding the setting of the relay 20 second timer.
5INSTALLATION CHECK
1. Check that all the Machinery wires installed in the MSRS terminal blocks are correct and secure as described
above and from the machinery’s installation manuals.
2. Apply power to the MSRS. The Green Power LED on the MSRS Unit and Display Panel should illuminate.
3. Start vessel engine(s) and all other machinery connected to / controlled by the MSRS.
4. Press the “ ” Dimmer Button on the Display Panel and the Green Power LED intensity on the panel and the
MSRS Unit shall change. Press again to return to full brightness.
5. Open the “PS1”circuit loop. The relays should energize, all connected machinery should shut down, the alarm
should sound and the red “PS1”LED on the MSRS Unit should illuminate as well as the red Discharge LED on the
Display Panel.
6. Press the “SILENCE” button on the Display Panel or on the MSRS Unit to silence the alarm.
7. With the PS1 circuit still open, put the MSRS into override by simultaneously pressing the “SILENCE” and the “”
buttons on display panel.
a. The connected machinery should be able to be restarted.
b. The red Discharged LED on the Display Panel and the red PS1 LED on the MSRS unit will remain illuminated.
8. Reset the unit by closing the PS1 circuit loop and simultaneously press the “SILENCE” and the “ ” buttons.
9. The Green power LED on display panel and MSRS Unit should be the only LEDs lit.
The PS2 circuit:
1. If applicable, open “PS2” circuit. The alarm should sound and both the “PS2” LED on the MSRS Unit and the Second
Zone (Low Pressure, High Temp or Aux Discharge) LED on the Display Panel should illuminate. The Relays should
remain in the de-energized state.
2. Reset the unit by closing the PS2 circuit and simultaneously press the “SILENCE” and the “ ” buttons.
3. The green POWER LED on the Display panel and the MSRS unit should be the only LEDs lit.
4. Use one of the Display Panels in a multiple Display Panel chain to reset the MSRS unit.

Page 7of 11 123-652 Rev -
6COMMON PROBLEM TROUBLESHOOTING GUIDE
Troubleshooting Guide
Caution: Turn off all power sources before installation, prior to removing or servicing.
Problem
Possible Cause(s)
Action
1. The Power LED on the Unit does
not come on.
There is no input power source.
The MSRS power converter is
damaged.
Recycle power to the MSRS unit.
Check input voltage source
connected to the MSRS.
2. The Alarm and the PS1 LED are
on.
There is no continuity across terminal
1 and 2.
Cylinder has discharged or has a loss of
pressure.
Check the Cylinder pressure
gauge.
Check for continuity across
terminals 1 and 2 with pressure
switch wires connected.
3. The Alarm and the PS2 LED are
on but there is a wire jumper
across terminals 3 and 4.
The jumper across terminal 3 and 4 is
not making good contact with the
terminals.
Recycle power to the MSRS unit.
Remove and re-install jumper.
The MSRS has an internal fault.
Recycle power to the MSRS unit.
Replace the MSRS unit.
4. The PS1 and the PS2 LED are on,
the Alarm does not silence AND
the unit does not reset.
The MSRS has an internal fault.
Replace the MSRS unit.
5. The SILENCE button on the MSRS
unit does not silence the alarm.
The MSRS SILENCE tactile switch on
the MSRS unit has failed.
Ensure that the tactile switch on
the MSRS unit clicks when
pushed in.
The MSRS SILENCE tactile switch on
the MSRS is fully depressed under the
faceplate
Use a small pointed object to re-
center pin until it re-seats above
the faceplate.
6. The Unit override does not work.
The MSRS did not receive the signal
from the Display Panel.
Check the CAT-5 cable and clean
the CAT-5 jack.
Replace Display Panel.
Note: If discharge occurs, contact SEA-FIRE Customer Support for assistance in locating an approved filling location.

Page 8of 11 123-652 Rev -
PN: 124-LPS
CYLINDER
SUPERVISORY
SWITCH (SPST)
DISPLAY - HIGH TEMP
PN:131-467
CAT-5
FIGURE 3: EXAMPLE ESRS 131-745 PRE-ENGINEERED WIRING SCHEMATIC
NOTE:
THIS WIRING SCHEMATIC IS A REFERENCE
EXAMPLE ONLY. CUSTOMER SPECIFIC WIRING
SCHEMATIC MAY APPLY PER CUSTOM
CONFIGURATION DIAGRAMS.
NOTE- THE 5A CIRCUIT BREAKER WITH ON/OFF SWITCH ARE TO BE SUPPLIED BY CUSTOMER.
MANUAL AUTOMATIC
FIRE SUPPRESSION SYSTEM
UPON SYSTEM DISCHARGE, SHUT DOWN:
ENGINE
FORCED VENTILATION
ELECTRI CAL SYSTEMS
FOR MANUAL OPERATION
REMOVE PIN
PULL HANDLE
F
I
R
E
PN: 136-XXX
SMAC PULL CABLE
5A
CIRCUIT
BREAKER
WITH
ON/OFF
SWITCH
5A
CIRCUIT
BREAKER
WITH
ON/OFF
SWITCH
5A
CIRCUIT
BREAKER
WITH
ON/OFF
SWITCH
PRE-ENGINEERED SYSTEM

Page 9of 11 123-652 Rev -
DISPLAY - HIGH TEMP
PN:131-467
CAT-5
FIGURE 4: EXAMPLE MSRS 131-745 ENGINEERED WIRING SCHEMATIC
NOTE- THE 5A CIRCUIT BREAKER WITH ON/OFF SWITCH ARE TO BE SUPPLIED BY CUSTOMER.
5A CIRCUIT
BREAKER
WITH ON/OFF
SWITCH
5A CIRCUIT
BREAKER
WITH ON/OFF
SWITCH
5A CIRCUIT
BREAKER
WITH ON/OFF
SWITCH
PN: 124-LPS
CYLINDER
SUPERVISORY
SWITCH (SPST)
BLACK RED
PN:124-969
OR
PN:124-914
HORN/STROBE
P/N: 131-311
DISCHARGE PRESSURE
SWITCH (DPDT)
NOTE:
THIS WIRING SCHEMATIC IS A REFERENCE
EXAMPLE ONLY. CUSTOMER SPECIFIC WIRING
SCHEMATIC MAY APPLY PER CUSTOM
CONFIGURATION DIAGRAMS.

Page 10 of 11 123-
652 Rev -
OWNERS RECORD
Installation Date ______________________
Installer ________________________
For More Information Call
Sea-Fire Marine
Phone: 1(410) 687 5500
Fax: 1 (410) 687 5503
www.Sea-Fire.com
Manufacturer of Quality Fire, Suppression and Detection Systems
This manual will be revise frequently to keep up-to-date with new changes and development.
“Sea-Fire Marine, an ISO 9001 registered company, is fully committed to exceeding our Customer’s expectations.”
ONE YEAR LIMITED WARRANTY
We guarantee to the original retail purchaser of the Sea-Fire Machinery Shutdown Restart
System for a period of one (1) year after retail purchase against defective material and
faulty workmanship. Any Engine Interrupt System found to be defective during the
warranty period will be replaced or repaired free of charge upon the prepaid return of the
defective system.
This warranty provides specific legal rights and you may have other rights, which vary from
country to country.

Page 11 of 11 123-
652 Rev -
This manual suits for next models
2
Table of contents