
SEL-487E-3, -4 Data Sheet Schweitzer Engineering Laboratories, Inc.
6
the distance elements when there is transient on the system
with CCVTs that may cause the distance element to over-
reach. All mho elements use positive-sequence memory
polarization that expands the operating characteristic in
proportion to the source impedance. This provides depend-
able and secure operation for close-in faults. The quadri-
lateral phase and ground distance elements provide improved
fault and arc resistance coverage, including application
on short lines.
Out-of-Step Detection
The SEL-487E supports out-of-step detection by using
timers and blinders that are set outside any of the distance
elements. A power swing is declared when an impedance
locus travels through the blinders slower than a preset
time. This logic blocks the distance elements in case of a
stable power swing.
Adaptive Time-Overcurrent
Elements (51S)
The relay supports 20 adaptive time-overcurrent elements
with selectable operate quantity and programmable time-
delay and pickup levels. Choose from the ten time-
overcurrent curves shown in Table 1 (five IEC and
five U.S.). Each torque-controlled time-overcurrent ele-
ment has two reset characteristics. One choice resets the
elements if current drops below pickup for one cycle
while the other choice emulates the reset characteristic of
an electromechanical induction disk relay.
The adaptive time-overcurrent elements in the SEL-487E
allow the selection of a wide variety of current sources as
operate quantities to the element. Select the time-overcurrent
element operate quantity from any one of the following
current sources:
➤Filtered phase currents: IAmFM, IBmFM, ICmFM
➤Maximum filtered phase current: IMAXmF
➤Combined filtered phase currents (any two
terminals): IAmmFM, IBmmFM, ICmmFM
➤Maximum filtered combined phase current:
IMAXmmF
➤Filtered positive-, negative-, and zero-sequence:
I1mFM, 3I2mFM, 3I0mFM, I1mmM, 3I2mmM,
3I0mmM
➤RMS currents: IAmRMS, IBmRMS, ICmRMS,
IMAXmR IAmmRMS, IBmmRMS, ICmmRMS,
IMAXmmR
where:
m= Relay current terminals S, T, U, W, X, Y
mm = Relay current terminals ST, TU, UW, WX
F = Filtered
M = Magnitude
MAX = Maximum magnitude A-, B-, C-phase currents
In addition to the selectable operate quantity, the 51S ele-
ment time-delay and pickup level inputs are SELOGIC-
programmable settings. This flexibility allows these inputs
to be set to fixed numerical values to operate as standard
time overcurrent elements, or the pickup and time-dial
settings can be programmed as SELOGIC math variables.
Programming the time-delay and pickup levels as math
variables allows the numeric value of the pickup and time-
delay settings to change based on system conditions with-
out the added delay of having to change relay setting groups.
For example, change pickup and time-delay settings
dynamically in a parallel transformer application based
upon single or parallel transformer configurations. Another
example would be changing feeder time-overcurrent ele-
ment pickup and coordination delays based upon distributed
generation being connected downstream of a transformer.
REF Protection
Apply the REF protection feature to provide sensitive detec-
tion of internal ground faults on grounded wye-connected
transformer windings and autotransformers. Use single-
phase neutral current inputs for providing neutral CT oper-
ating current for as many as three windings. Polarizing
current is derived from the residual current calculated for
the corresponding protected winding. A directional ele-
ment determines whether the fault is internal or external.
Zero-sequence current thresholds supervise tripping. The
relay can accommodate CT ratio mismatch as great as 35:1.
Figure 4 Mho Characteristics
Table 1 Supported Time-Overcurrent Curves
U.S. Curves IEC Curves
U1 (moderately inverse) C1 (standard inverse)
U2 (inverse) C2 (very inverse)
U3 (very inverse) C3 (extremely inverse)
U4 (extremely inverse) C4 (long-time inverse)
U5 (short-time inverse) C5 (short-time inverse)
Expanded
Characteristic
Steady-State
Characteristic
Relay Reach
Z
R
Z
S
X
R