INSTALLATION MANUAL
T201DCH50-MU (HW2 version)
T201DCH100-MU (HW2 version)
T201DCH300-MU (HW2 version)
True RMS or DC bipolar AC/DC current transducer
with ModBus RTU protocol and analogue/digital output
SENECA s.r.l.
Via Austria, 26 – 35127 – PADOVA – ITALY
Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287
For manuals in other languages and conguration software, visit:
www.seneca.it/
products
/t201dch50-mu - www.seneca.it/
products
/t201dch100-mu - www.seneca.it/
products
/t201dch300-mu
EN
MI00544-0-EN 1/4
T201DCH50-MU
T201DCH100-MU
T201DCH300-MU
MODULE LAYOUT
Dimensions LxHxD 95 x 68 x 26 mm; Weight: ≈ 120 g; Enclosure: PA6, black
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user's safety at risk.
The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or
the connected equipment.
The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by
the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
WARNING: The full content of this manual must be read before any operation. The module must only be used by
qualied electricians.
Specic documentation is available from:
www.seneca.it/products/t201dch50-mu / www.seneca.it/products/t201dch100-mu / www.seneca.it/products/t201dch300-mu
Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The
symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to
recycle electrical and electronic waste.
The module must be repaired and damaged parts replaced by the Manufacturer.
The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
LED STATUS LED meaning
PWR/COM Green ON The device is powered correctly
PWR/COM Green Flashing Communication via USB port
D-OUT Yellow ON Digital output activated
SIGNALS VIA LED ON FRONT PANEL
2/4
26.0 mm
mm
86
95.0 mm
20.8 mm
ASSEMBLY
The device can be mounted in any position, in compliance with the expected environmental conditions. Use the
accessories supplied for xing on a DIN rail.
Attention: magnetic elds of considerable magnitude can alter the measurement: avoid proximity to permanent
magnetic, electromagnetic elds, or ferrous masses which induce strong alterations of the magnetic eld; possibly,
if the zero error is greater than the declared error, try a different arrangement or change orientation.
TECHNICAL SPECIFICATIONS
STANDARDS
EN61000-6-4 Electromagnetic emissions, industrial environment.
EN61000-6-2 Electromagnetic immunity, industrial environment.
EN61010-1 Safety.
INSULATION Using an insulated conductor, its sheath determines the insulation voltage. An insulation of 3
kV ac is guaranteed on bare conductors
ENVIRONMENTAL
CONDITIONS
Temperature: -20 – + 70°C
Humidity: 10%– 90% non condensing.
Altitude: Up to 2000 m above sea level
Storage temperature: -40 – + 85°C
Degree of protection: IP20.
ASSEMBLY 35mm DIN rail IEC EN60715
CONNECTIONS Removable 5-way screw terminals, 5 mm pitch for cable up to 2.5 mm2
micro USB
POWER SUPPLY Voltage: on Vcc and GND terminals, 11.5 – 28 Vdc;
Absorption: Typical: 21 mA (LOAD EXCLUDED)
COMMUNICATION
PORT
RS485 serial port on terminals A+ and B-; or on USB port
INPUT
(on 20.8 mm
through hole)
Type of measurement: AC/DC TRMS or DC Bipolar
Crest factor: 2
Pass-band: 1 kHz
Overload: 2000 A impulsive, 3 x INcontinuing
CAPACITY AC/DC True RMS (DIP7=OFF) DC Bipolar (DIP7=ON)
T201DCH50-MU 0 – 25A or 0 - 50A -0 – +25A or -50 - +50A
T201DCH100-MU 0 – 50A or 0 - 100A -50 – +50A or -100 - +100A
T201DCH300-MU 0 – 150A or 0 - 300A -150 – +150A or -300 - +300A
ANALOGUE
OUTPUT
on Vout and
GND terminals
Type: 0 – 10 Vdc, minimum load RLOAD =2 kΩ.
Protection: Reverse polarity protection and over voltage protection
Resolution: 13 bit (10000 points)
EMI error: < 0.5%
Temperature coefcient: < 200 ppm/°C
Hysteresis on measurement: 0.2% of full scale
Response speed: With «Fast» lter 800 ms. With «Slow» lter 2000 ms.
The type of output can be selected via software
DIGITAL
OUTPUT
on Vout and
GND terminals
Type: active, 0 – Vcc, maximum load 50 mA
The type of output can be selected via software
ACCURACY below 2% of full scale above 2% of full scale
T201DCH50-MU
1% of full scale at 50/60 Hz, 23°C 0.5% of full scale at 50/60 Hz, 23°C
T201DCH100-MU
T201DCH300-MU
OVERVOLTAGE
CATEGORIES
Bare conductor: CAT. III 300 V
Insulated conductor: CAT. III 600 V
3/4
4/4
USB PORT
CU MICROOTG-A CU MICROB-A-
CU MICROB-A-
Configurazione
tramite APP
Android
Configurazione
tramite
software PC
The module is designed to exchange data according to the modes dened by the MODBUS protocol. It
has a micro USB connector and can be congured using applications and/or software programs. The USB
communication has priority over the RS485 communication.
The USB serial port uses the following communication parameters: 38400,8,N,1
The USB communication port responds exactly like the RS485 port with the exception of the communication
parameters. During the use of the USB port, the 485 bus will be inactive; it will reactivate automatically a few
seconds after the release of the USB port. EASY SETUP is the software to use for the conguration. For further
information go to the website on the cover.
Check that the device in question is included in the list of products supported by the Easy Setup APP in the store.
-
SETTING THE DIP-SWITCHES
The position of the DIP-switches denes the Modbus communication parameters of the module: Address and Baud Rate
The following table shows the values of the Baud Rate and the Address according to the setting of the DIP-switches:
DIP-Switch status
POSITION
ADDRESS
POSITION BAUD
RATE
POSITION TYPE OF
MEASUREMENT
POSITION MEASURING
SCALES
1 2 3 4 5 6 78
#1 9600 AC/DC true RMS Full scale
#2 19200 DC Bipolar Half scale
#3 38400 DIP-switches must be set while the module is not
powered on in order to avoid damaging it. KEY
#... 57600
#14
The instrument is supplied congured for 50 A (DCH50), 100 A (DCH100) and 300A
(DCH300), with 800 ms lter inserted and TRMS mode selected.
ON
#15 OFF
All dip-switches set to OFF: parameters from ash memory. See the USER manual
Note: When DIP switches 3 to 8 are OFF, the communication settings are taken from programming (EEPROM).
+
Vcc
Vout
GND
B-
A+
ELECTRICAL CONNECTIONS
Uscita (V)
Ingresso (A) TRMS
10
0± 50
±100
±300
± 25
± 50
±150
(DIP7 = OFF)
5
Ingresso (A) D C Bipolar
- 50
-100
-300
+ 50
+100
+300
0+
25
+ 50
+150
- 25
- 50
-150
Uscita (V)
(DIP 7 = ON)
10
5
CONTACT INFORMATION
Technical support [email protected] Product information [email protected]
Android
APP
conguration
PC
software
conguration
Output (V)
Output (V)
Input (A) TRMS Input (A) DC Bipolar

Other manuals for T201DCH50-MU

2

This manual suits for next models

2

Other Seneca Transducer manuals

Seneca T201DCH600-MU User manual

Seneca

Seneca T201DCH600-MU User manual

Seneca T201DCH100-OPEN User manual

Seneca

Seneca T201DCH100-OPEN User manual

Seneca T201DC100 User manual

Seneca

Seneca T201DC100 User manual

Seneca T201DC User manual

Seneca

Seneca T201DC User manual

Popular Transducer manuals by other brands

Iskra MT4 Series user manual

Iskra

Iskra MT4 Series user manual

SENSONETICS SEN-430 Series installation instructions

SENSONETICS

SENSONETICS SEN-430 Series installation instructions

APAR AR593 User instructions

APAR

APAR AR593 User instructions

MESSKO Pt-MU operating instructions

MESSKO

MESSKO Pt-MU operating instructions

HBM HBK S2M Mounting instructions

HBM

HBM HBK S2M Mounting instructions

Ashcroft GC55 Installation and maintenance instructions

Ashcroft

Ashcroft GC55 Installation and maintenance instructions

Airmar TRIDUCER P23 Owner's guide & installation instructions

Airmar

Airmar TRIDUCER P23 Owner's guide & installation instructions

ETH-messtechnik DRVL Operator's manual

ETH-messtechnik

ETH-messtechnik DRVL Operator's manual

turck HART IM33-11-Hi/24VDC Series quick start guide

turck

turck HART IM33-11-Hi/24VDC Series quick start guide

NK TECHNOLOGIES ATQ Series instructions

NK TECHNOLOGIES

NK TECHNOLOGIES ATQ Series instructions

Airmar B45 Owner's guide & installation instructions

Airmar

Airmar B45 Owner's guide & installation instructions

Airmar Ultrasonic TRIDUCER UDST800 Owner's guide and installation instructions

Airmar

Airmar Ultrasonic TRIDUCER UDST800 Owner's guide and installation instructions

Humminbird MEGA 360 IMAGING Series installation guide

Humminbird

Humminbird MEGA 360 IMAGING Series installation guide

Humminbird transducer manual&nbsp;

Humminbird

Humminbird transducer manual&nbsp;

Garmin GT15M-TH installation instructions

Garmin

Garmin GT15M-TH installation instructions

Airmar M256 Owner's guide & installation instructions

Airmar

Airmar M256 Owner's guide & installation instructions

MKS 910-11000-0016 quick start guide

MKS

MKS 910-11000-0016 quick start guide

Siemens XRS-5 Quick start manual

Siemens

Siemens XRS-5 Quick start manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.