
EM_aSENSE mIII_standard_NC_installation_Nov'06 3 of 4
Electrical connections
The power supply has to be connected to G+ and G0. G0 is considered as system ground. The
same ground reference has to be used for the
aSENSE™ m
III unit and for any connected
device! Unless different transformers are used, special precautions need to be taken.
PLEASE NOTE! The signal ground is not galvanically separated from
the
aSENSE™ m
III power supply!
PLEASE NOTE! The same ground reference has to be used for the
aSENSE™
m
III unit and for the control system!
Connection
Terminal
Function
Electrical Data
Remarks
G+
G0
Power (+)
Power ground (-)
24 VAC/DC+ (+-20%), 3W
24 VAC/DC-
2W without output load
See note 1!
OUT 1
OUT 2
M
Analogue Output 1 (+)
Analogue Output 2 (+)
Signal Ground (-)
0-10 VDC or 0-20 mA,
2-10 VDC or 4-20 mA,
Same as Output 1
Connected to G0 via PTC fuse
According to positions of
OUT1 jumper and start
point selection.
See note 2!
According to positions of
OUT2 jumper and start
point selection.
See note 2!
See note 1!
Relay
Relay
Normally closed
Open at alarm situ-
ations and power loss
Contact free relay
minimum load 1mA/5V
rated load 0,5A/125VAC;
1A/24VDC
Triggered by register
OUT3
OUT4
Analogue Output 4 (+)
or Open Collector
0-10 VDC
Max 0,5A, 55VDC / 40VAC
(half-wave rectifier protection)
According to positions of
OUT4.
See note 2 & 3!
DI1
Digital Input 1 Closed contact current 1mA
Open contact voltage max 5V Do not apply any voltage
on this input!
Table I. Electrical terminal connections for
aSENSE™ m
III
Note 1:The ground terminal is used as negative power supply DC input or AC phase ground G0
(halfwave rectifier). The signal ground M, protected by a PTC resistor, is the same as power ground
G0 (permitting a ”3-wire” configuration). A single transformer may be used for the entire system.
Note 2:
aSENSE™ m
III can deliver both a voltage or a current loop for OUT1/OUT2. For OUT4 a
voltage output or an open collector output is selected with jumper OUT4. To change between voltage
and current output mode the hardware jumpers are used. There is one jumper for OUT1 and one for
OUT2, so that one output can be a voltage output and the other a current output. Both, voltage output
and current output, can have start points 0 % (0-10 VDC or 0-20mA) or 20% (2-10 VDC or 4-20mA)
selected from PC software. See the function manual.
Note 3:Current of Open Collector is internally returned to G0 terminal.