Binary input #2 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (Door Dry) Door contact & Motion detector: This configuration is only
functional if binary input #1 is set to Motion NO or Motion NC or a PIR
accessory cover is used. With this sequence enabled, the occupancy is now
dictated through those 2 inputs. Any motion detected will set the zone to
occupied status. The zone will remain permanently in occupied mode until the
door contact switch opens momentarily. The Room Controller will then go in
stand-by mode. If more movements are detected, the occupied mode will
resume. While the door is opened, any movements detected by the remote PIR
sensor or the PIR accessory cover will be ignored. Use a Normally Closed
contact switching device.
Contact opened = Door opened
Contact closed = Door closed
3. (RemOVR): temporary occupancy remote override contact. This function
disables the central button override function on the Room Controller. The
override function is now controlled by a manual remote momentarily closed
contact. When configured in this mode, the input operates in a toggle mode. It is
now possible to toggle between unoccupied & occupied setpoints for the amount
of time set by parameter (TOccTime) temporary occupancy time.
4. (Filter): a backlit flashing Filter alarm will be displayed on the Room Controller
LCD screen when the input is energized. It can be tied to a differential pressure
switch that monitor filters
Contact opened = No alarm
Contact closed = Alarm displayed
5. (Service): a backlit flashing Service alarm will be displayed on the Room
Controller LCD screen when the input is energized. It can be tied in to the AC
unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
Universal input #3 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (COC/NH) Change over dry contact. Normally Heat: Used for hot / cold air /
water change over switching in 2 pipe systems.
Contact closed = Cold air / water present
Contact opened = Hot air / water present
Only used and valid if system is setup as 2.0. Parameter (Out1Conf) set as 2.0.
3. (COC/NC) Change over dry contact. Normally Cool: Used for hot /cold air /
water change over switching in 2 pipe systems.
Contact closed = Hot air / water present
Contact opened = Cold air / water present
Only used and valid if system is setup as 2.0. Parameter (Out1Conf) set as 2.0.