
VR8405 HIGH CAPACITY DIRECT IGNITION COMBINATION GAS CONTROL
69-0815—02 4
STARTUP AND CHECKOUT
Fire or explosion hazard. Can cause property
damage, severe injury, or death.
1. Do not force the gas control knobs. Use only
your hand to turn the gas control knobs. Never
use any tools.
2. If the gas control knobs will not operate by
hand, call a qualified service technician to
replace the entire gas control.
3. Both knobs must be in the same position for
operation or shutoff.
Gas Control Knobs Settings
The gas control knobs have two settings:
OFF: Prevents main burner gas flow.
ON: Permits gas to flow into the control body. Under
control of the thermostat and direct ignition mod-
ule, gas can flow to the main burner.
NOTE: Gas controls are shipped with the gas control
knobs in the ON position.
Perform Gas Leak Test
Fire or explosion hazard. Can cause property
damage, severe injury, or death.
Check for gas leaks with a rich soap and water
solution any time work is done on a gas control.
Gas Leak Test
1. Paint all pipe connections upstream of the gas
control with a rich soap and water solution. Bub-
bles indicate a gas leak.
2. If a gas leak is detected, tighten the pipe connec-
tion.
3. Stand clear while lighting main burner to prevent
injury caused from hidden gas leaks that could
cause flashback in the appliance vestibule. Turn on
the entire gas control and light the main burner as
described below.
4. With the main burner in operation, paint all pipe
joints and gas control inlet and outlet with a rich
soap and water solution.
5. If another gas leak is detected, tighten pipe con-
nections.
6. Replace the part if gas leak cannot be stopped.
Turn On Gas Control
Rotate the gas control knobs counterclockwise to
ON.
Turn On Main Burner
Follow instructions provided by appliance manufacturer
or turn up thermostat to call for heat.
Check Gas Input to Main Burner
1. Do not exceed the input rating stamped on the
appliance nameplate, or manufacturer
recommended burner orifice pressure for the
size orifice(s) used. Make certain the primary
air supply to the main burner is properly
adjusted for complete combustion (refer to the
appliance manufacturer instructions).
2. WHEN CHECKING GAS INPUT BY CLOCKING
THE GAS METER:
• Make sure that the only gas flow through
the meter is that of the appliance being
checked.
• Make certain that other appliances are
turned off with pilot burners extinguished
(or deduct that gas consumption from the
meter reading).
• Convert the flow rate to Btuh as described
in the Gas Controls Handbook, form 70-
2602, and compare to the Btuh input rating
on the appliance nameplate.
Standard-Opening and Slow-Opening
Pressure Regulator
1. The gas control outlet pressure should match the
manifold pressure listed on the appliance name-
plate.
2. With the main burner operating, check the gas con-
trol flow rate using the meter clocking method.
3. If the desired gas flow rate is not as stamped on
the control, check the gas control inlet pressure
using a manometer at the inlet pressure tap. Regu-
lators are fixed. They are not adjustable. If the inlet
pressure is in the normal range (refer to Table 4),
replace the entire gas control. Otherwise, take the
necessary steps to provide proper gas pressure to
the gas control.
NOTE: Factory set outlet pressure is not field adjust-
able.
Step-Opening Pressure Regulator
1. The gas control outlet pressure should match the
manifold pressure listed on the appliance name-
plate.
2. With the main burner operating, check the gas con-
trol flow rate using the meter clocking method.
3. If desired flow rate is not as stamped on the con-
trol, check the inlet pressure using a manometer at
inlet pressure tap or upstream of the gas control.
Regulators are fixed. They are not adjustable. If the
inlet pressure is in the normal range (refer to
Table 4), replace the entire gas control. Otherwise,
take the necessary steps to provide proper gas
pressure to the gas control.
4. Carefully check main burner lightoff at the step
pressure. Make sure the main burner lights
smoothly and without flashback to the orifice and
that all ports remain lit. Cycle the main burner sev-
eral times, allowing at least 30 seconds between
cycles for the regulator to resume the step func-
tion. Repeat after allowing main burner to cool.