
WWW.SERFILCO.COM 2900 MacArthur Blvd. Northbrook, IL. USA 60062 (800) 323-5431
Operation and Service Guide
O-3180 - Page 3 of 8
03/05/21
© 2021 Serfilco Ltd, All Right Reserved.
2900 MacArthur Blvd. Northbrook, IL. USA 60062 WWW.SERFILCO.COM (800) 323-5431
Series 'EFB' | Sump Pumps
Pump mounting
The pump may be mounted directly on the pit using
the pump mounting plate or in conjunction with a pit
cover.
Carefully lower the assembled pump into the pit,
taking care not to damage lube lines. Make sure that
any equipment used to lift the pump or any of its
components is capable of supporting the weights
encountered. Make sure that all parts are properly
rigged before attempting to lift.
Pump mounting plate and/or pit cover must be level,
and supported evenly at all points before being bolted
down.
The foundation for the mounting plate or pit cover
must be sufficiently rigid to prevent vibration.
Supporting members must be sufficiently strong to
prevent spring action and /or lateral movement.
Electrical
With power off and solution in sump and water in
bearing cooling lines:
Rotate the motor shaft by hand to make sure it is
free to rotate when energized.
Connect the motor terminals to the leads from the
starter panel.
Start the motor, immediately hit the stop button, and
check for proper rotation which should be clockwise
when looking down on top of the motor. If rotation is
wrong, interchange any two motor connections on
three-phase motors. On single phase motors, follow the
motor manufacturer's instructions. After changing the
connections, again check the rotation.
Motors are suitable for VFD operation.
⚠CAUTION: Failure to follow this instruction can result
in serious damage to pump and driver if rotation is
wrong.
Piping
⚠NOTE: The design of piping systems, foundations and
other areas of system design is the responsibility of the
customer. This data and comments are offered as an
aid, but we cannot assume responsibility for the
installation design and operation.
We recommend that the customer consult a
specialist skilled in the design of piping, sumps and
related systems so as to supplement and interpret the
information and ensure a successful installation.
Discharge piping should be connected to the pump
such that no strain or weight of the piping is carried by
the pump. Check pump shaft for freedom of rotation by
hand to make sure discharge piping strain is not causing
binding.
A check valve is required to prevent back-flow
through the pump on shut-down. Manufacturer will not
be responsible for damages resulting from failure to
install a check valve.
⚠NOTE: If quick-closing valves are installed in the
discharge piping system, protection MUST be provided
to ensure that no surge or water hammer is transmitted
to the pump.
PRE-STARTING CHECKS
Motor preparation
Prepare the driver for operation as instructed by the
driver manufacturer. Re-check all connections to the
motor and control with the wiring diagram. Make sure
voltage and frequency on the motor and control
nameplates correspond with the line voltage.
If the driver has not been checked for rotation, it
must be done now.
Pre-start-up
1. Verify that materials of construction are compatible
with solution being pumped. Refer to ‘Materials in
Solution Contact’ table Page 1.
2. Verify that operating temperature is not in excess of
maximum recommended. Refer to ‘Materials in
Solution Contact’ table Page 1.
3. Carefully place pump into sump or tank and secure
in position using bolts, clamps, etc. Check alignment
and position of level controls as instructed above.
4. Connect electrical supply to motor starter.
A Soft Starter is recommended to prolong the
life of the pump. If starter is furnished, verify that
starter and motor are wired for the correct
operating voltage, and the starter contains the
correct overload heaters. It is recommended that a
motor starter be installed if one was not provided
with the pump assembly.
5. If mounting plate bolts or pump-motor lock nuts are
loosened, pump alignment must be checked.
6. Do not energize motor until pump is immersed
in liquid and then follow startup no.1.
7. Secure the assembly, complete all piping and firmly
support.
8. Check for correct high-low operation of level control
by manually positioning float rod or a current check
of conductivity level controls.
9. Check for correct operation of motor starter and
Dri-Stop when included.
Product flush lubricated pump bearings
Check to see that the product flush lines are
connected to the pump discharge elbow. Check that no
damage has occurred to the lubrication lines during
shipment or installation.
⚠NOTE: If solution being pumped crystalizes when
exposed to air and bearings are not always submerged
in solution, pump bearing lubrication with water is
recommended.
Water-lubricated pump bearings
Clean water from an external source must be used
when pumps are furnished with bearings for which
water lubrication is required. Check to see that
connections are made to bearing lubrication fittings on
pump mounting plate, and that 0.5 GPM of water per
bearing at 10 PSIG is available. Do not install metal pipe
fittings directly onto pipe connections on non-metallic
parts. Check to see that no damage has occurred to the
lubrication lines during shipment or installation.