Setra Systems MRMS User manual

Multi-Room Monitoring Station (MRMS)
Installation Instructions
Setra’s Multi-Room Monitoring Station (MRMS)
Setra’s Multi-Room Monitoring Station (MRMS) is a remote environmental
condition monitoring and alarming solution for critical spaces in Healthcare,
Pharmaceutical, Biological Safety Labs and Vivarium. Using BACnet® MS/TP, the
MRMS can remotely monitor up to 8 spaces equipped with other Setra Pressure
and Condition Room Monitors (e.g. Model SRPM or SRCM). The MRMS can be
installed in a centralized location such as a Nurse’s station or in a centralized
control. The MRMS user interface is simple, intuitive and allows the user to access
SRCM are then automatically imported into the MRMS resulting in substantial
installation and setup cost reduction.
1.0 INTENDED USE
The MRMS is designed to be used as a remote monitor of critical environments
by connecting up to 8 other SRPM or SRCM devices that provide local differential
pressure measurement/indication, temperature, humidity, and/or other parameters.
The condition status of the critical space as well as the measurement readings are
propagated to the MRMS through BACnet®. Typical applications include:
Healthcare – Hospital Nurse’s Station
Pharmaceutical, semiconductor, precision manufacturing and other clean rooms
chemicals
1.1 SPECIFICATIONS
Operating Temperature Limits:
Operating Humidity Limits:
Supply Voltage:
Power Consumption:
Electrical Connection:
Housing:
Mounting:
Weight Approx.:
Agency Approval:
Communications:
1.2 MRMS FUNCTION
The MRMS communicates to other Setra Room Pressure Monitors (SRPM) and/or
information displayed on these remote devices. The MRMS visually indicate
humidity and door status.
User Interface:
resistive touch screen.
The home screen of the MRMS shows the name and status/condition of the rooms
being monitored remotely.
Color Status
Normal, Room Pressure is within alarm limits
Yellow
is within the alarm dead band.
Red Alarm. Room Pressure is outside alarm limits and alarm delay
Audible Feedback: The built-in audible buzzer will sound when differential
the remote SRPM or SRCM. Note that the buzzer will not sound at the MRMS
regardless of the volume setting if the audible alarm is disabled in the remote
2.0 PARTS AS SHIPPED
2.1 MRMS PARTS INCLUDED
Parts included in your order:
(Communications connector and power connector)
2.2 REQUIRED PARTS TO BE SUPPLIED BY INSTALLER
To mount and install properly, the following components are required:
recommended), as needed.
2.3 OVERVIEW OF PHYSICAL INSTALLATION
remote SRPM and SRCM devices, power supply, earth ground, etc.
connectors (provided). After the product is properly installed and
screen user interface.
device or negatively affects its performance.
Cleaning and Decontamination:
3.0 INSTALLATION
The MRMS is designed to be mounted in a standard triple gang-double deep
NOTE:
3.1 WIRING ELECTRICAL BOX (ROUGH-IN)
electrical codes.
inaccessible once the MRMS is installed. Strain relief tubing and wires, and seal
Tripe gang electrical box rough wiring and plumbing
3.2 BACNET WIRING
be used for communications ground and the shield wire can be connected to the
other device shield wires.
Connect shields together with wire nut.
right hand section of the PCB as well as through the touch screen interface.
Switch Position Function
Not Connected (Not Used)
3 Pull-Up Resistor
Termination Resistor
If the unit will be at the end of the line, the termination resistor can be enabled by

3.3 NETWORK SETUP
(left) position.
using the change button. Auto baud rate is not supported.
3.
Save and Exit to save settings or Cancel
After the unit returns to the menu screen, cycle the power to the unit by removing
3.4 WIRING (FINISH)
Rear view of the MRMS monitor to show wiring and plumbing connections
the matching function.
Power, labeled POWER, L1, L2, ground symbol
power consumption.
Do not turn on power until all other connections have been made.
COMM BAcnet communication
Analog Output, labeled ANL OUTPUT, RELAY, INPUT1, INPUT2
Not used
4.0 MAINTENANCE
The MRMS is designed to operate in an indoor environment, monitoring clean,
dry air.
to include a brief description of the problem plus any relevant application notes.
Contact customer service to receive a return goods authorization number before
shipping.
WARNING - Cleaning Instructions
5.0 AGENCY ELECTRICAL STANDARD
The MRMS meets the following requirements:
6.0 RETURNING PRODUCTS FOR REPAIR
http://www. setra.com/tra/repairs/cal_rep.htm.
7.0 WARRANTY AND LIMITATION OF LIABILITY
neglect, accident, incorrect wiring not our own, improper installation or servicing,
or use in violation of instructions furnished by SETRA;
its authorized service agencies c) the serial number or date code has not been
removed, defaced, or otherwise changed; and
products shall be warranted for one year from date of sale.
including but not limited to, any implied warranty of merchantability for a particular
purpose. SETRA’s liability for breach of warranty is limited to repair or replacement,
or if the goods cannot be repaired or replaced, to a refund of the purchase price.
In no instance shall SETRA be liable for incidental or consequential damages
arising from a breach of warranty, or from the use or installation of its products.
No representative or person is authorized to give any warranty other than as set
out above or to assume for SETRA any other liability in connection with the sale
of its products.
Other manuals for MRMS
1
Other Setra Systems Measuring Instrument manuals

Setra Systems
Setra Systems SRIMV Operating instructions

Setra Systems
Setra Systems Model 730 User manual

Setra Systems
Setra Systems 760 User manual

Setra Systems
Setra Systems DATUM 2000 User manual

Setra Systems
Setra Systems SRIM1 User manual

Setra Systems
Setra Systems SS-SPM User manual

Setra Systems
Setra Systems Power Patrol Manual

Setra Systems
Setra Systems 370 User manual

Setra Systems
Setra Systems 761 User manual

Setra Systems
Setra Systems SRCM Installation manual