TT/MUX02EX
safety, installation, use and maintenance instructions
1 - CERTIFIED ATEX VERSION IDENTIFICATION
1. Product code
2. Marking
3. Protection degree
4. Serial number
5. Certifyingbodyidenticationcode
2 - SAFETY INSTRUCTIONS
The probes and the power unit are suitable for the installation in potentially explosive atmosphere for the presence of
combustible dust.
Makesurethatthedevicesmarkingisincompliancewiththeareaclassication;donotinstallthedevicesinpresenceof
explosive gases (zone 0, 1 or 2).
Verifythattheinstrumentsinstallationdoesnotaecttheprotectiondegree.
Device improper use may cause damage to people, to the product and the connected equipments.
Always observe the nameplate data for the power supply and the electrical connections.
3 - INSTALLATION AND COMMISSIONING
Theinstallationmustbeperformedonlybyqualiedandproperlytrainedpersonnelinaccordancewiththecurrent
Regulation EN 60079-14.
Theequipmentsmustbeusedonlyaerhavingcorrectlyunderstoodtheinstructionsprovidedonthisdocument
and on the manual.
The devices must be mounted so as to minimize the risk of shock to the housing and to the sensitive part.
Useonlythethreadedconnection(32mmwrench)toinserttheprobesintheprocess;donotusethehousingtomanuallyscrewthe
sensor on the process.
Always connect the cable shield to “SCH” connection that is equipotential with the ground connection of enclosure.
Forangemountingorunder-roofmountinguseonlytheaccessorieslistedonSGMLEKTRAcatalog.
TTprobescanbeconnectedexclusivelytoMUX02EXconcentrators;anyotherconnectioncompromisesthesecurityand
invalidates the method of protection.
SI19001A_ENGRev.of28/10/2021
Multipoint digital probe for temperature measurement in tanks and
storage silos.
European directive: 2014/34/UE
ATEXreference:50014:197;50281-1-1:98incomplianceto
EN60079-0:2018;EN60079-31:2014
Model : TT
ATEXGroupandcategory:II1D
Protection mode: by housing “ta”
Protection degree: IP66
Maximum measurable temperature: +125°C
Ambient temperature: -30°C ÷ +125°C
Warning: This document is an integral part of the manual and must be read and understood in conjunction with it
Power unit for the reading and the re-transmission of the temperature
detected by TT probes.
European directive: 2014/34/UE
ATEXreference:50014:197;50281-1-1:98incomplianceto
EN60079-0:2018;EN60079-31:2014
Model: MUX02EX
ATEXGroupandcategory:II1D
Protection mode: by housing “tb”
Protection degree: IP66
Ambient temperature: -20°C ÷ +70°C
Power supply: 230V 50Hz
Type: TT1E0L05B0
Connect with MUX02EX
SGM LEKTRA 20090 Rodano (MI) , Italy
IP66 T 125 °C
II 1 D
Serial N°TM0101916632-2019
-30°C - +125°C
KEMA 04ATEX2010 0051