Operating Instructions
Automatic Power Factor Controller Relay
7UG0572-1GT21
7UG0
IEC 60947-5-1
Please read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
Hazardous voltage can cause death or serious injury.
Disconnect power before working on equipment.
CAUTION
Reliable functioning of the equipment is only ensured
with certied components.
Overvoltage category III
(Refer IEC 60947-1)
NOTICE
This product has been designed for environment A. Use of this product
in environment B may cause unwanted electromagnetic disturbances in
which case the user may require to take adequate mitigation measures.
Technical Data
Designation 7UG0572-1GT21
Type Automatic Power Factor Controller
Operating range 50 to 440 VAC (L-L)
30 to 250 VAC (L-N)
AC Network 3Φ4W / 3Φ3W / 2Φ2W/ 1Φ2W
Display parameters Power Factor
Control Supply 90 to 250 VAC, 50/60Hz
Power consumption 15VA
Frequency range 50/60Hz
Operating temperature 0°C to 60°C
Humidity upto 95% ,without moisture
condensation
Alarm mode (relay output) Over voltage, Under voltage, Over
Compensate, Under Compensate, CT
Polarity error
Trip indication Alarm relay turns ON and ALARM
LED blinks
No. of relay outputs 12
(Additional 1 for Alarm)
Rated current of relay outputs
(@250VAC)
5A* (AC12), 1A (AC15)
CT Burden 20 mohms
Switching program Automatic / Linear / Rotational
Mounting Panel mounting
SCPD for relay output (For
Short circuit current of 1kA as
per IEC 60947-5-1)
6A, gL, HRC fuse
* 5A AC12 rating is for individual relay contact. If multiple relays are ON,
relay AC12 rating will be limited to 1.2A @ 250V.
LED Indications
LED Description
Capacitor Banksthat areON.
Indicates controller is in AUTO mode.
Indicates controller is in MANUAL mode.
No fault condition present.
Fault condition occurred
[Press OK key to display trip parameter]
This will take place when user will press OK key in
fault condition. Trip parameters will be displayedfor
3sec each.
AUTO
AUTO
ALARM
ALARM
ALARM
Note : On occurrence of any new fault condition ALARM LED starts
blinking again & on pressing OK key all trip parameters will be displayed
for 3sec each