manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Thermostat
  8. •
  9. Siemens RDE10.1DHW User manual

Siemens RDE10.1DHW User manual

3038
Room Temperature Controller
with 7-Day Time Switch and
independent DHW Control RDE10.1DHW
•2-position control with ON / OFF output for heating
•Independent ON / OFF control of DHW
•Operating modes: Auto, normal operation, energy saving and
frost protection
•7-day time switch and manual control
•Battery-powered DC 3 V (2 x 1.5 V AA)
Use
The RDE10.1DHW is used for the control of the room temperature in heating systems
with independent control of DHW.
Typical applications:
•Residential apartments
For the control of the following plant components and of DHW:
•Thermal valves or zone valves
•Gas or oil burners
•Fans
•Pumps
•Heat exchanger
•Continuous-flow water heater
•Small water heating systems
CE1N3038en
20.10.2005
Building Technologies
HVAC Products
Functions
.
.
.
Q14
T[°C]
ON
OFF W
SD
3030D01
T Room temperature
SD Switching differential
W Room temperature setpoint
Q14 Output signal for heating
Function diagram
Operating modes
The RDE10.1DHW provides auto, normal operation, energy saving (or OFF) or frost
protection mode. The difference between normal operation and energy saving mode is
merely the room temperature setpoint. The changeover from normal operation to en-
ergy saving or frost protection mode, or vice versa, is made by pressing a button.
In auto mode changeover between operating modes is accomplished automatically
according to the 7-day switching pattern.
Normal operation When normal operation is activated, symbol appears on the display. The setpoint
can be readjusted by pressing buttons , +and -.
Energy saving or OFF When energy saving mode is activated, symbol appears on the display. The setpoint
can be readjusted by pressing buttons , +and -.
In energy saving mode, the unit can also be switched to OFF. This is accomplished by
selecting a setpoint of 5 °C and then keeping button -depressed for 4 seconds. In
that case, symbol does not appear.
When frost protection mode is activated, symbol appears on the display.
Frost protection
7-day time switch The changeover between “normal” and “energy saving” temperature setpoints can take
place either automatically ( ) or manually ( , ), depending on the selection of the
operating mode.
When pressing the operating mode button until appears on the display, changeover
will take place automatically according to the selected switching pattern. A specific
switching pattern can be selected for every weekday.
Factory setting: Day(s) Normal operation Energy saving mode
Mo (1) – Fr (5) 6:00 – 8:00 h and
17:00 – 22:00 h 22:00 – 6:00 h and
08:00 – 17:00 h
Sa (6) – Su (7) 7:00 – 22:00 h 22:00 – 7:00 h
The current setpoint can be temporarily readjusted by pressing buttons +and -. The
setpoint will then be reset to its initial value the next time automatic or manual change-
over takes place.
When the operating mode button is set to or , the controller will maintain normal
operation or energy saving mode respectively.
DHW mode The RDE10.1DHW features independent control of DHW.
2/8
Building Technologies Room temperature controller RDE10.1DHW CE1N3038en
HVAC Products 20.10.2005
The following DHW operating modes can be selected:
Continuously ON: Symbol appears on the display
Continuously OFF: No symbol on the display
Auto: Symbol
appears on the display, DHW is switched
according to the selected switching pattern
Factory setting: Time switch for DHW
Day(s) DHW control ON DHW control OFF
Mo (1) – Fr (5) 6:00 – 8:00 h and
17:00 – 22:00 h 22:00 – 6:00 h and
08:00 – 17:00 h
Sa (6) – Su (7) 7:00 – 22:00 h 22:00 – 7:00 h
Display The digital display shows the actual room temperature, the time of day, the weekday,
the current switching pattern for heating, the switching pattern for DHW, and the symbol
of the operating mode currently active. When the heating output is activated, the trian-
gle symbol appears.
Display of the switching pattern is split up in upper and lower row.
When the segment is displayed and flashing, the DHW output is activated. When no
segment is displayed, the DHW output is deactivated.
Upper row with
switching pattern
for DHW control
3/8
Building Technologies Room temperature controller RDE10.1DHW CE1N3038en
062412 18
C
062412 18
C
062412 18
C
DHW Auto mode DHW ON mode DHW OFF mode
Lower row with
switching pattern
for heating
When the segment is displayed and flashing, the normal temperature setpoint is active.
When no segment is displayed, the energy saving or frost protection temperature set-
point is active.
062412 18
C
C
062412 18 062412 18
C
Automatic changeover Normal operation Energy saving mode
according to switching pattern
OFF mode and frost
protection display
062412 18
C
062412 18
C
OFF mode Frost protection mode
Backup When taking out the batteries, the setpoints and the information required for operating
mode changeover are memorized. However, the real time clock must be reset after the
batteries are replaced.
HVAC Products 20.10.2005
Ordering
When ordering, please give name and type reference: Room temperature controller
RDE10.1DHW.
Valve actuators are to be ordered as separate items.
Equipment combinations
Type of unit Type reference Data sheet
Electromotoric ON / OFF actuator SFA21... 4863
Thermal actuator (for radiator valve) STA21... 4893
Thermal actuator (for small valve 2.5 mm) STP21... 4878
Accessories
Description Type reference
Adapter plate 120 x 120 mm for 4“ x 4“ conduit boxes ARG70
Adapter plate 96 x 120 mm for 2“ x 4“ conduit boxes ARG70.1
Adapter plate for surface wiring 112 x 130 mm ARG70.2
Mechanical design
The controller consists of 2 parts:
•Plastic housing with digital display, which accommodates the electronics, the oper-
ating elements and the built-in room temperature sensor
•Mounting base
The housing engages in the mounting base and snaps on.
The base carries the screw terminals.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
19
17
18
16
20
3038Z05
1 Display of the room temperature in °C, or setpoints
Legend 2 Current time of day using the 00:00... 23:59 format
3 Current weekday from 1 (Monday) to 7 (Sunday)
4 Current heating
and DHW switching pattern
with flashing time pointer
5 Symbol when the actual room temperature is displayed
4/8
Building Technologies Room temperature controller RDE10.1DHW CE1N3038en
HVAC Products 20.10.2005
6 Button for operating mode
7 Button for DHW control
8 Selecting and leaving the setting mode for the DHW switching pattern
9 Symbol in automatic mode or when selecting the switching pattern
10 Heating ON
11
or will show when DHW heating is activaed
12 Symbol indicating that batteries need to be replaced
13 Buttons for adjusting the setpoints, the time of day and the switching times
14 Setting the weekday
15 Setting the time of day
16 Selecting and leaving the setting mode for the heating switching pattern
17 Setpoint adjustment for energy saving mode
18 Setpoint adjustment for normal operation
19 Button for confirming the switching pattern settings
20 Battery compartment
Notes
The room temperature controller should be mounted in a location where the air tem-
perature can be acquired as accurately as possible without getting adversely affected
by direct solar radiation or other heat or refrigeration sources.
Mounting height is about 1.5 m above the floor.
The controller can be fitted to a recessed conduit box.
•Only authorized staff may open the unit.
Caution: AC 230 V!
•The cables used must satisfy the insulation requirements with regard to mains
potential
Mounting, installa-
tions and commis-
sioning
When mounting the controller, fix the base first. Then, make the electrical connections
and fit and secure the cover (also refer to the relevant Mounting Instructions).
The controller must be mounted on a flat wall and in compliance with local regulations.
If there are thermostatic radiator valves in the reference room, they must be set to their
fully open position.
Maintenance The controller is maintenance-free.
Sensor calibration If the temperature on the display does not agree with the room temperature effectively
measured, the temperature sensor can be recalibrated. For that purpose, both buttons
+and must be pressed simultaneously for 3 seconds. Then, the temperature
displayed can be changed by a maximum of +/- 3 K by pressing the +and -buttons.
5 seconds after the last push of a button, the controller will automatically return to the
normal operating state.
5/8
Building Technologies Room temperature controller RDE10.1DHW CE1N3038en
HVAC Products 20.10.2005
Change of batteries If the battery symbol appears, the battery power is almost exhausted and the batteries
should be replaced.
To make a reset, first press and hold the button, then press the 2 buttons +
-simulta-
neously for 3 seconds. All individual settings will be reset to their standard values.
Reset
Technical data
Operating voltage DC 3 V (2 x 1.5 V AA Alkaline batteries)
Battery life (RDE10.1DHW) > 1 year (AA Alkaline batteries)
Power supply
Heating valve or wall-hung boiler – Y1
Control output Q12 (NC contact)
Rating RDE0.1DHW (AC 24...250 V) max. 5(2) A
Control output Q14 (NO contact)
Rating RDE10.1DHW (AC 24...250 V) max. 5(2) A
Control outputs
DHW control – Y2
Control output Q22 (NC contact)
Rating RDE10.1DHW (AC 24...250 V) max. 5(2) A
Control output Q24 (NO contact)
Rating RDE10.1DHW (AC 24...250 V) max. 5(2) A
Switching differential SD 1 K
Setpoint setting range
Normal operation 5…35 °C
Energy saving 0 (OFF) and 5…35 °C
Factory setting normal operation 20 °C
Factory setting energy saving 8 °C
Frost protection 5 °C (fixed)
Resolution of settings and displays
Setpoints 0.5 °C
Switching times 60 min
Actual temperature value displays 0.5 °C
Time of day displays 1 min
Operational data
Operation to IEC 721-3-3
Climatic conditions class 3K5
Temperature 0…+50 °C
Humidity <95 % r.h.
Transport to IEC 721-3-2
Climatic conditions class 2K3
Temperature -25…+60 °C
Humidity <95 % r. h.
Mechanical conditions class 2M2
Environmental conditions
Storage to IEC 721-3-1
Climatic conditions class 1K3
Temperature -25…+60 °C
Humidity <95 % r. h.
conformity to
EMC directive 89/336/EEC
Low-voltage directive 73/23/EEC and 93/68/EEC
N474 C-Tick conformity to
EMC emission standard
AS/NSZ 4251.1:1994
Product standards
Automatic electrical controls for EN 60 730 – 1 and
household and similar use EN 60 730–2-9
Electromagnetic compatibility
Emissions EN 61 000–6-3
Immunity EN 61 000–6-1
Standards
6/8
Building Technologies Room temperature controller RDE10.1DHW CE1N3038en
HVAC Products 20.10.2005
Safety class II to EN 60730
Pollution class normal
Degree of protection of housing IP30 to EN 60529
Connection terminals for solid wires or prepared stranded wires.
2 x 1.5 mm2or 1 x 2.5 mm2(min. 0.5 mm2)
Weight 0.21 kg
Color of housing front white, NCS S 0502-G (RAL 9003)
General
Connection diagram
L
RDE10.1DHW
Q12 Q14
Nx
Lx
(inverse
of Q14)
L
Y1 Y2
Q22 Q24
(inverse
of Q24)
3038A02
3V
Lx -Nx AC 24...250 V / max. 5 (2) A
Legend Y1 Heating valve or wall-hung boiler
Y2 DHW heating equipment
Application examples
T
TF1
F2
N1
M1
Y2
3033S01
T
DHW
T
F1
F2
N1
M1
Y2
3033S02
T T
DHW
Room temperature controller with direct
control of a gas-fired wall-hung boiler and
independent control of DHW
Room temperature controller with direct control
of a gas-fired floor-standing boiler and
independent control of DHW
7/8
Building Technologies Room temperature controller RDE10.1DHW CE1N3038en
HVAC Products 20.10.2005
Legend
T
N1
Y1
3033S03
M1
DHW
F1
F2
M1
N1
Y1
Y2
DHW
Thermal reset limit thermostat
Safety limit thermostat
Circulating pump
RDE10.1DHW room temperatures controller
3-port valve with manual adjustment
Magnetic valve
DHW heating equipment
Room temperature controller with direct
control of a heating circuit pump (precontrol
by manual mixing valve) and independent
control of DHW
Dimensions
Controller and base
8/8
Building Technologies Room temperature controller RDE10.1DHW CE1N3038en
©2005 Siemens Switzerland Ltd Subject to alteration
HVAC Products 20.10.2005

Other manuals for RDE10.1DHW

2

Other Siemens Thermostat manuals

Siemens REV100 User manual

Siemens

Siemens REV100 User manual

Siemens RDF300.02/SRL User manual

Siemens

Siemens RDF300.02/SRL User manual

Siemens REV34 User manual

Siemens

Siemens REV34 User manual

Siemens DIGIFLOOR 2NC9 840 User manual

Siemens

Siemens DIGIFLOOR 2NC9 840 User manual

Siemens RDE100 Series Manual

Siemens

Siemens RDE100 Series Manual

Siemens RDF510 Series User manual

Siemens

Siemens RDF510 Series User manual

Siemens RDD100.1DHW User manual

Siemens

Siemens RDD100.1DHW User manual

Siemens RDJ100RF/SET User manual

Siemens

Siemens RDJ100RF/SET User manual

Siemens RDE100 Series User manual

Siemens

Siemens RDE100 Series User manual

Siemens RDH100RF/SET User manual

Siemens

Siemens RDH100RF/SET User manual

Siemens RDF301 Operator's manual

Siemens

Siemens RDF301 Operator's manual

Siemens RDF800 User manual

Siemens

Siemens RDF800 User manual

Siemens RDG400KN User manual

Siemens

Siemens RDG400KN User manual

Siemens RAM1T Guide

Siemens

Siemens RAM1T Guide

Siemens QAF64 Series Instruction manual

Siemens

Siemens QAF64 Series Instruction manual

Siemens RDE50.1 User manual

Siemens

Siemens RDE50.1 User manual

Siemens RDJ100RF/SET User manual

Siemens

Siemens RDJ100RF/SET User manual

Siemens RDF800KN User manual

Siemens

Siemens RDF800KN User manual

Siemens RAA Series Owner's manual

Siemens

Siemens RAA Series Owner's manual

Siemens RDS120-B Owner's manual

Siemens

Siemens RDS120-B Owner's manual

Siemens Retroline TH 192 User manual

Siemens

Siemens Retroline TH 192 User manual

Siemens RDY2000 User manual

Siemens

Siemens RDY2000 User manual

Siemens RDJ10 User manual

Siemens

Siemens RDJ10 User manual

Siemens RDD100.1RF User manual

Siemens

Siemens RDD100.1RF User manual

Popular Thermostat manuals by other brands

VDH ALFANET 53 user manual

VDH

VDH ALFANET 53 user manual

Danfoss RT 106 installation guide

Danfoss

Danfoss RT 106 installation guide

ardex FLEXBONE HEAT Non-Programmable Thermostat quick start guide

ardex

ardex FLEXBONE HEAT Non-Programmable Thermostat quick start guide

Lauda Alpha A operating instructions

Lauda

Lauda Alpha A operating instructions

Starck Netatmo NTH01 manual

Starck

Starck Netatmo NTH01 manual

DEVI devireg 550 user guide

DEVI

DEVI devireg 550 user guide

PHASELINER TT097 user guide

PHASELINER

PHASELINER TT097 user guide

Trane Nexia TCONT624AS42DA user guide

Trane

Trane Nexia TCONT624AS42DA user guide

Drayton LP10RF Installation & user guide

Drayton

Drayton LP10RF Installation & user guide

Lennox ComfortSense L3021H installation instructions

Lennox

Lennox ComfortSense L3021H installation instructions

POLYPOOL EASY TOUCH PP1467 User instructions

POLYPOOL

POLYPOOL EASY TOUCH PP1467 User instructions

Ruud EcoNet Smart Thermostat quick start guide

Ruud

Ruud EcoNet Smart Thermostat quick start guide

Seltron ST instructions

Seltron

Seltron ST instructions

OJ Electronics AWG4 user manual

OJ Electronics

OJ Electronics AWG4 user manual

Amana PTAC DS02G-H installation instructions

Amana

Amana PTAC DS02G-H installation instructions

Intermatic InTouch Z-Wave CA8900 Installation and user instructions

Intermatic

Intermatic InTouch Z-Wave CA8900 Installation and user instructions

DELTA DORE 6053038 manual

DELTA DORE

DELTA DORE 6053038 manual

CTC Union 43153 owner's manual

CTC Union

CTC Union 43153 owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.