Siemens RDG100KN User manual

s
3191
Room thermostats with
KNX communications
RDG100KN
RDG160KN
–
For fan coil unit applications
–
For universal applications
–
For use with compressor in DX type equipment
•KNX bus communication (S-mode and LTE mode)
•Backlit display
•2P / PI / P control
•Outputs for On/Off, PWM, 3-position or DC 0...10 V control
•Outputs for 3-speed, 1-speed, or DC (DC 0...10 V) fan
•3 multifunctional inputs for keycard contact, external sensor, etc.
•Operating modes: Comfort, Economy and Protection
•Automatic or manual fan speed control
•Automatic or manual heating / cooling changeover
•Minimum and maximum limitation of room temperature setpoint
•Control depending on the room or the return air temperature
•Selectable relay output functions (RDG160KN)
•Adjustable commissioning and control parameters
•Commissioning with Synco ACS, ETS or via local HMI
•Integration into Synco
•Integration into Desigo via group addressing (ETS) or via individual
addressing
•Integration into third-party system via group addressing (ETS)
•Operating voltage:
RDG100KN: AC 230 V
RDG160KN: AC 24 V
Edition 3.2
CE1N3191en
2014-05-23
Building Technologies
Use
The RDG1...KN room thermostats are designed for use with the following types of
system:
Fan coil units via On/Off or modulating / DC control outputs:
•2-pipe system
•2-pipe system with electric heater
•2-pipe system and radiator / floor heating
•4-pipe system
•4-pipe system with electric heater (RDG100KN)
•2-stage heating or cooling system
Chilled / heated ceilings (or radiators) via On/Off or modulating / DC control
outputs:
•Chilled / heated ceiling
•Chilled / heated ceiling with electric heater
•Chilled / heated ceiling and radiator / floor heating
•Chilled / heated ceiling, 2-stage cooling or heating
Compressor application via On/Off control (RDG160KN)
•Compressors in DX-type equipment
•Compressors in DX-type equipment with electric heater
•Compressors in DX-type equipment with Radiator
•2-stage compressors in DX-type equipment for heating or cooling
The RDG100KN controls...
•One single or 3-speed fan
•One or two On/Off / PWM / 3-position valve actuators
•One valve actuator and one electric heater / Radiator
The RDG160KN controls...
•One single, 3-speed or DC 0...10 V fan
•One or two On/Off valve actuators / el. Heater / radiator with DC fan
•One or two DC valve actuators / el. Heater / radiator with DC fan
•One or two DC valve actuators / el. Heater / radiator with 1 / 3-speed fan
•One On/Off valve actuator, one DC valve actuator with DC fan
•1 or 2-stage compressor in DX-type equipment, with electric heater / radiator
Used in systems with:
•Heating or cooling mode
•Automatic heating/cooling changeover
•Manual heating/cooling changeover
•Heating and cooling mode (e.g. 4-pipe system)
The room thermostats are delivered with a fixed set of applications.
The relevant application is selected and activated during commissioning using one
of the following tools:
•Synco ACS
•ETS
•Local DIP switch and HMI
2 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Functions
•Room temperature control via built-in temperature sensor or external room
temperature / return air temperature sensor
•Changeover between heating and cooling mode (automatic via local sensor or
bus, or manual)
•Selection of applications via DIP switches or commissioning tool (ACS, ETS)
•Select operating mode via operating mode button on the thermostat
•Parameters download with commissioning tool (ACS, ETS)
•Temporary Comfort mode extension
•Single speed, 3-speed or DC 0...10 V fan control (automatic or manual)
•Display of current room temperature or setpoint in °C and/or °F
•Minimum and maximum limitation of room temperature setpoint
•Button lock (automatic or manual)
•3 multifunctional inputs, freely selectable for:
−Operating mode switchover contact (keycard, window contact, etc.)
−Sensor for automatic heating / cooling changeover
−External room temperature or return air temperature sensor
−Dewpoint sensor
−Electric heater enable
−Fault input
−Monitor input for temperature sensor or switch status
−Supply air temperature sensor (RDG160KN)
•Advanced fan control function, e.g. fan kick, fan start delay, selectable fan
operation (enable, disable or depending on heating or cooling mode)
•Purge function together with 2-port valve in a 2-pipe changeover system
•Reminder to clean fan filters
•Floor heating temperature limitation
•Minimum and maximum supply air temperature limitation (RDG160KN)
•Reload factory settings for commissioning and control parameters
•KNX bus (terminals CE+ and CE-) for communication with Synco or KNX
compatible devices
•Display of outside temperature or time of day via KNX bus
•Time scheduling and central control of setpoints via KNX bus
•With a Synco RMB7xx controller, the energy demand signal of the thermostat is
used to optimize energy supply
•Selectable relay function for switching external equipment (RDG160KN)
3 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Applications
The thermostats support the following applications, which can be configured using
the DIP switches at the rear of the unit or a commissioning tool.
DIP switches 1...3 need to be set to OFF (remote configuration, factory setting) to
select an application via commissioning tool.
Remote configuration, via commissioning tool (factory set)
•Synco ACS
•ETS
DIP switches
ON
Applications for fan coil systems
Applications, DIP setting, Control outputs
•2-pipe fan coil unit
1 2 3 4 5
ON
OFF
•2-pipe fan coil unit
and electric heater
1 2 3 4 5
ON
OFF
•2-pipe fan coil unit
and radiator / floor
heating
1 2 3 4 5
ON
OFF
(B1)
M1
Y1
TB2
T
T
(B1)
Y1
M1
3076S02_01
T
YE
T
(B1)
T
(B1)
B2
(B1)
M1
Y1
T
B2
T
T
(B1)
YR
Using RDG100KN, RDG160KN Using RDG100KN, RDG160KN Using RDG100KN, RDG160KN
•2-pipe / 2-stage
fan coil unit
1 2 3 4 5
ON
OFF
•4-pipe fan coil unit
1 2 3 4 5
ON
OFF
•4-pipe fan coil unit
and electric heater
1 2 3 4 5
ON
OFF
Y1
M1
T
B2
T
(B1)
T
(B1)
Y2
T
Y2
Y1
M1
(B1)
T
(B1)
T
Y2
Y1 M1
3076S05_01
(B1)
T
(B1)
YE
B2
Using RDG100KN, RDG160KN Using RDG100KN, RDG160KN Using RDG100KN
Product no.
Control outputs
Fan
RDG100KN
On/Off, PWM, 3-position
3-speed, 1-speed
RDG160KN
DC 0...10 V
3-speed, 1-speed, DC 0...10 V
RDG160KN
On/Off
DC 0...10 V
Remote configuration
4 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Applications for Universal systems
Applications, DIP setting, Control outputs
•Chilled / heated
ceiling
1 2 3 4 5
ON
OFF
•Chilled / heated
ceiling
and electric heater
1 2 3 4 5
ON
OFF
•Chilled / heated
ceiling and
radiator
/ floor heating
1 2 3 4 5
ON
OFF
3191S11
N1
T
B1
T
B2
T
D3
Y1
3191S12
N1
T
YE
B1
T
B2
T
D3
Y1
3191S14
N1
T
B1
T
B2
T
D3
Y1
YR
Using RDG100KN, RDG160KN Using RDG100KN, RDG160KN Using RDG100KN, RDG160KN
•2-stage chilled /
heated ceiling
1 2 3 4 5
ON
OFF
•Chilled ceiling
and radiator
1 2 3 4 5
ON
OFF
Y1
Y2
3191S13
N1
T
B1
T
D3
Y1
YR
Using RDG100KN, RDG160KN Using RDG100KN, RDG160KN
Product no.
Control outputs
RDG100KN
On/Off, PWM, 3-position
RDG160KN
On/Off, DC 0...10 V
5 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Applications for heat pump systems (RDG160KN)
Applications, DIP setting, Control outputs
•Heated or cooled with compressors
1 2 3 4 5
ON
OFF
•Heated or cooled with
compressors, with electric heater
1 2 3 4 5
ON
OFF
3181S31
N1
T
B1
T
D3
3181S32
N1
T
YE
B1
T
D3
Using RDG160KN Using RDG160KN
•Heated and cooled with
compressors
1 2 3 4 5
ON
OFF
•2-stage heated or cooled
with compressors
1 2 3 4 5
ON
OFF
3181S35
N1
T
B1
T
D3
3181S36
N1
T
B1
T
D3
2
Using RDG160KN Using RDG160KN
Product no.
Control outputs
Fan
RDG160KN
On/Off , DC 0...10 V
Disabled, DC 0...10 V
Key
Y1 Heating or heating / cooling valve actuator
M1 1-speed or 3-speed fan
Y2 Cooling valve actuator
YE Electric heater
B1 Return air temperature sensor or external room
temperature sensor (optional)
B2 Changeover sensor (optional)
RDG100KN
•Use P46 / P47 to change output from On / Off (factory setting) to PWM
•Use DIP switches 4 and 5 to change output from On/Off to 3-position
RDG160KN
•Use P46 / P47 to change valve actuator output from DC (factory setting) to On/Off
•Use DIP switch 4 to change fan output from DC (factory setting) to 3-speed
Notes
6 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Type summary
Product no.
Stock no.
Features
Operating
voltage
Number of control outputs Fan Backlit
LCD
On/Off
PWM
3-pos.
DC
3-stage
DC
RDG100KN
S55770-T163
AC 230 V
3 1)
2 1)
2 1)


RDG160KN S55770-T297 AC 24 V
2 2)
2 2)


2
3)
1) Selectable: On/Off, PWM or 3-position (triac outputs)
2) Either On/Off or DC control signal
3) 3-speed fan selectable only with DC outputs
Equipment combinations
Description Product no. Data
sheet
Cable temperature or
changeover sensor
QAH11.1 1840
Room temperature sensor
QAA32 1747
Condensation motion
QXA2601 /
QXA2602 /
QXA2603 /
QXA2604
3302
Electromotoric On/Off actuator
SFA21... 4863
Electromotoric On/Off valve and
actuator
(only available in AP, UAE, SA and IN)
MVI… / MXI… 4867
Zone valve actuator
(only available in AP, UAE, SA and IN)
SUA… 4832
Thermal actuator (for radiator valves)
AC 230 V, NO
STA23... *) 4884 *)
Thermal actuator (for radiator valves)
AC 24 V, NO
STA73... *) 4884 *)
Thermal actuator AC 230 V
(for small valves 2.5 mm), NC
STP23... *) 4884 *)
Thermal actuator AC 24 V
(for small valves 2.5 mm), NC
STP73... *) 4884 *)
Electrical actuator, 3-position
(for radiator valves)
SSA31... 4893
Electrical actuator, 3-position
(for 2- and 3-port valves / V…P45)
SSC31 4895
Electrical actuator, 3-position
(for small valves 2.5 mm)
SSP31… 4864
Electrical actuator, 3-position
(for small valves 5.5 mm)
SSB31... 4891
Electrical actuator, 3-position
(for small valve 5,5 mm)
SSD31... 4861
Electromotoric actuator, 3-position
(for valves 5.5 mm)
SQS35… 4573
On / off actuators
On / off and PWM
actuators *)
3-position actuators
7 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Electrical actuator, DC 0...10 V
(for radiator valves)
SSA61... 4893
Electrical actuator, DC 0...10 V
(for 2- and 3-port valves / V…P45)
SSC61… 4895
Electrical actuator, DC 0...10 V
(for small valves 2.5 mm)
SSP61… 4864
Electrical actuator, DC 0...10 V
(for small valves 5.5 mm)
SSB61... 4891
Electrical actuator, DC 0...10 V
(for CombiValves VPI45)
SSD61... 4861
Electromotoric actuator, DC 0...10 V
(for valves 5.5 mm)
SQS65… 4573
Electrothermal actuator,
AC 24 V, NC, DC 0…10 V, 1 m
STA63 4884
Electrothermal actuator,
AC 24 V, NO, DC 0…10 V, 1 m
STP63 4884
*) With PWM control, it is not possible to ensure exact parallel running of
more than one thermal actuator.
If several fan-coil systems are controlled by the same room thermostat, preference
should be given to motorized actuators with On/Off or 3-position control.
Note:
For the parallel operation of the actuators, refer to information in the data sheets of
the selected actuators and to this list, depending on which value is lower:
Maximum number of actuators in parallel on the RDG100KN
•max 6 SS…31.. actuators (3-pos)
•max 4 ST…23.. if used with On/Off control signal
•max 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
•Parallel operation of SQS35 is NOT possible
Maximum number of actuators in parallel on the RDG160KN
•max 10 SS…61.. actuators (DC)
•max 10 ST..23/63/73... actuators (DC or On/Off)
•max 10 SFA.., SUA.., MVI.., MXI … On/Off actuators
•max 10 SQS65 actuators (DC)
Accessories
Description
Product no. /
stock no.
Data
sheet
KNX Power supply 160 mA (Siemens BT LV)
5WG1 125-1AB02
--
KNX Power supply 320 mA (Siemens BT LV)
5WG1 125-1AB12
--
KNX Power supply 640 mA (Siemens BT LV)
5WG1 125-1AB22
--
DC 0…10 V actuators
8 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Mechanical design
The room thermostat consists of 2 parts:
•Plastic housing with electronics, operating elements and room temperature
sensor
•Mounting plate with the screw terminals
The housing engages in the mounting plate and is secured with 2 screws.
1) Operating mode button / Esc
2) Fan mode button / Ok
3) Rotary knob to adjust setpoints and
parameters
Operation and settings
2
1
3
9 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
#
Symbol
Description
#
Symbol
Description
1 Heating mode 14
Automatic fan
2
Heating mode,
electric heater active 15 Manual fan
3
Cooling mode
16
Fan speed
Fan speed 1
4 Comfort
Fan speed 2
5 Economy
Fan speed 3
6
Auto Timer mode according to
schedule (via KNX) 17
Degrees Celsius
Degrees Fahrenheit
8
Protection mode 18
Digits for room temperature and setpoint
display
9
Escape 19 Button lock
10
Additional user information, like out-
door temperature or time of day
from KNX bus. Selectable via
parameters
20 Condensation in room (dewpoint sensor active)
12
Morning: 12-hour format
Afternoon: 12-hour format 21
Weekday 1…7 from KNX bus
1 = Monday / 7 = Sunday
13
Confirmation of parameters 22
Fault
23
Temporary timer function; visible when
operating mode is temporarily extended
(extended presence or absence)
24
Indicates that room temperature is displayed
Display
10 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Engineering notes
See the "Reference documentation", page 17 for information on how to engineer
the KNX bus (topology, bus repeaters, etc.) and how to select and dimension
connecting cables for supply voltage and field devices.
Mounting and installation
Do not mount on a wall in niches or bookshelves, behind curtains, above or near
heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the
floor.
Mounting •Mount the room thermostat on a clean, dry indoor place without direct airflow
from a heating / cooling device, and not exposed to drips or splash water.
Wiring See the mounting instructions M3191 enclosed with the thermostat.
•Comply with local regulations to wire, protection and earth the thermostat.
•The device has no internal fuse for supply lines to fan and actuators. To avoid
risk of fire and injury due to short-circuits, the AC 230 V mains supply line must
have a circuit breaker with a rated current of no more than 10 A.
•Properly size the cables to the thermostat, fan and valve actuators for AC
230 V mains voltage.
•Use only valve actuators rated for AC 230 V.
•The wiring cross section used for power supply (L, N), fan (Q1, Q2, Q3, N) and
230 V outputs (Yx - N) must be adapted to the preceding overload protection
elements (10A) under all circumstances. Comply under all circumstances with
local regulations.
•Isolate the cables of input D1-GND for 230 V if the conduit box carries AC
230 V mains voltage.
•X1-M, X2-M or D1-GND: several switches (e.g. summer/winter switch) may be
connected in parallel. Consider overall maximum contact sensing current for
switch rating.
•Inputs X1-M and X2-M carry mains potential (RDG100KN only).
Sensor cables must be suited for AC 230 V mains voltage
•Selectable relay function (RDG160KN): Follow instructions in P3191 to connect
external equipment to the relay outputs.
•Isolate the cables of KNX communication input CE+ / CE- for 230 V if the
conduit box carries AC 230 V mains voltage.
•No cables provided with a metal sheath.
•Disconnect from supply before removing from the mounting plate.
•When a KNX bus power supply is connected on the line with communicating
thermostats and Synco controller, the internal KNX power supply of the Synco
controllers must be switched off.
11 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Commissioning notes
The room thermostats are delivered with a fixed set of applications.
Select and activate the relevant application during commissioning using one of the
following tools:
−Local DIP switch and HMI
−Synco ACS
−ETS
Set the DIP switches before snapping the thermostat to the mounting plate, if you
want to select an application via DIP switches.
All DIP switches need to be set to “OFF” ("remote configuration"), if you want to
select an application via commissioning tool.
After power is applied, the thermostat resets and all LCD segments flash, indica-
ting that the reset was correct. After the reset, which takes about 3 seconds, the
thermostat is ready for commissioning by qualified HVAC staff.
If all DIP switches are OFF, the display reads "NO APPL" to indicate that
application commissioning via a tool is required.
Each time the application is changed, the thermostat reloads the factory setting for
all control parameters, except for KNX device and zone addresses!
Connect the Synco ACS or ETS tools to the KNX bus cable at any point for
commissioning:
L
N Y1 Y2
X1 M X2
N1
3191A03
Q1 Q2 Q3
CE+ CE-
KNX
KNX
V24
ETS
RS232
Siemens
N148 /
UP146 /
UP152
KNX
USB
ETS / ACS
Siemens
OCI700
D1 GND
Y3 Y4
ACS and ETS require an interface:
−RS232 KNX interface (e.g. Siemens N148 / UP146 / UP152)
−OCI700 USB- KNX interface
An external KNX bus power supply is required if an RDG1...KN is connected
directly to a tool (ACS or ETS) via KNX interface.
The thermostat's control parameters can be set to ensure optimum performance of
the entire system (see basic documentation P3191).
The parameters can be adjusted using
−Local HMI
−Synco ACS
−ETS
Applications
Note
Connect tool
Note
Control parameters
12 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
•The control sequence may need to be set via parameter P01 depending on the
application. The factory setting is as follows:
Application
Factory setting P01
2-pipe and chilled / heated ceiling, and 2-stage
1 = Cooling only
4-pipe, chilled ceiling and radiator
4 = Heating and cooling
•Recalibrate the temperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured (after min. 1 hour of
operation). To do this, change parameter P05.
•We recommend to review the setpoints and setpoint ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy.
The programming mode helps identify the thermostat in the KNX network during
commissioning.
Press the left and right buttons simultaneously for 6 sec to activate programming
mode, which is indicated on the display with "PrOg".
Programming mode remains active until thermostat identification is complete.
Use ETS to assign the KNX group addresses of the RDG communication objects.
Each device has a unique KNX serial number inside the plastic housing.
An additional sticker with the same KNX serial number is enclosed in the packa-
ging box. This sticker is intended for installers for documentation purposes.
Disposal
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
•Dispose of the device via the channels provided for this purpose.
•Comply with all local and currently applicable laws and regulations.
Control sequence
Calibrate sensor
Setpoint and range
limitation
Programming mode
Assign KNX group
addresses
KNX serial number
13 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Technical data
Rated voltage
AC 230 V
Frequency
50/60 Hz
Power consumption
Max. 8 VA / 1 W
No internal fuse
External preliminary protection with max
. C 10 A circuit breaker
required in all cases
Fan control Q1, Q2, Q3 – N
AC 230 V
Rating min, max resistive (inductive)
5 mA...5(4) A
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line
required under all circumstances
Fans must NOT be connected in parallel!
Connect one fan directly, for additional fans, one relay for each speed.
Control outputs
Y1, Y2, Y3, Y4-N
Power limitation
Solid state (Triac)
AC 230 V,
8mA...1 A
3
A fast microfuse, cannot
be exchanged
Multifunctional inputs
X1-M / X2-M
Temperature sensor input
Type
Temperature range
Cable length
Digital input
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
Insulation against mains
D1-GND
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
Insulation against mains
QAH11.1 (NTC)
0...49 °C
Max. 80 m
Selectable (NO/NC)
DC 0…5 V, max. 5 mA
Max. 20 thermostats per
switch.
Do no
t mix with D1!
N/A, mains potential
Selectable (NO/NC)
SELV DC 6…15 V, 3…6 mA
Max. 20 thermostats per
switch.
Do not mix with X1 / X2!
3.75 kV, reinforced
insulation
Function of inputs
External temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dewpoint monitor contact, enable electric
heater contact, fault contact, monitoring input
Selectable
X1: P38
X2: P40
D1: P42
RDG100KN
Power supply
Caution
Outputs
Caution
STOP
Note!
Inputs
14 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Rated voltage
DC 24 V : Make sure to connect G to + and G0 to -
AC 24 V
DC 24 V
Frequency
50/60 Hz
Power consumption
Max. 2 VA / 2 W
No internal fuse
External preliminary protection with max
. C 10 A circuit breaker
required in all cases
Q1 / Q2 / Q3 / L - N (relay)
AC 24...230 V
Use for 3-speed fan control
Rating min, max resistive (inductive)
5 mA...5(4) A
Fans must NOT be connected in parallel!
Connect one fan directly, for additional fans, one relay for each speed.
Use for actuator control (Q1, Q2)
Q1 - rating min, max resistive (inductive)
5 mA...1 A
Q2 - rating min, max resistive (inductive)
5 mA...5(4) A
Use for external equipment (Q3)
Rating min, max resistive / inductive Qx
5 mA…1 A
No internal fuse
External preliminary protection with max. C 10 A circ
uit breaker in the supply line
required under all circumstances
ECM fan control Y50 - G0
SELV DC 0...10 V,
Max. ±5 mA
Actuator control Y10 - G0 / Y20 - G0 (G)
SELV DC 0...10 V,
Max. ±1 mA
Multifunctional inputs
X1-M / X2-M
Temperature sensor input
Type
Temperature range
Cable length
Digital input
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
D1-GND
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
SELV
QAH11.1 (NTC)
0...49 °C
Max. 80 m
Selectable (NO/NC)
DC 0…5 V, max. 5 mA
Max. 20 thermostats per
switch
Selectable (
NO/NC)
DC 6…15 V, 3…6 mA
Max. 20 thermostats per
switch.
Function of inputs
External room temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dewpoint monitor contact, enable electric
heater contact, fault contact, monitoring input,
supply air temperature
Selectable
X1: P38
X2: P40
D1: P42
RDG160KN
Power supply
Caution
Outputs
STOP
Note!
Caution
Inputs
15 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Interface type
KNX, TP1
-64
(electrically isolated)
Bus current
20 mA
Bus topology: See KNX manual (reference documentation, see below)
Switching differential, adjustable
Heating mode (P30)
Cooling mode (P31)
2
K (0.5…6 K)
1 K (0.5…6 K)
Setpoint setting and setpoint range
Comfort mode (P08)
Economy (P11-P12)
Protection (P65-P66)
21 °C (5…40 °C)
15 °C/30 °C (OFF, 5..
40 °C)
8 °C/OFF (OFF, 5..40 °C)
Multifunctional inputs X1 / X2 / D1
Input X1 default value (P38)
Input X2 default value (P40)
Input D1 default value (P42)
Selectable (
0...8)
1 (
Ext. temperature sensor,
room or return air)
0 (n
o function)
3 (
Operating mode
switchover)
Built
-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
0…49 °C
<
± 0.5 K
± 3.0 K
Settings and display res
olution
Setpoints
Current temperature value displayed
0.5 °C
0.5 °C
Operation
Climatic conditions
Temperature
Humidity
IEC 721-3-3
Class 3K5
0
…50 °C
<95% r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
IEC 721-3-2
Class 2K3
−
25…65 °C
<
95% r.h.
Class 2M2
Storage
Climatic conditions
Temperature
Humidity
IEC 721-3-1
Class 1K3
-
25…65 °C
<95% r.h.
EU conformity (CE)
Product standards
Automatic electric controls for household and
similar use
EN60730–1
Special requirements for temperature-dependent
controls
Electronic control type
EN
60730–2-9
2.B (micro
-disconnection on
operation)
Electromagnetic compatibility
Emissions
Immunity
2004/108/EC
EN60730–1, EN50491-5-2
EN60730–1, EN50491-5-2
EN50491-5-3
RDG100KN, RDG160KN
KNX bus
Operational data
Environmental conditions
Standards and directives
16 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Low
-voltage directive
Electrical safety
2006/95/EC
EN60730–1, EN50491-3
RCM Mark conformity (Emission)
AS/NZS 61000-6-3
Reduction of
hazardous substances
2011/65/E
U
EN50581
Safety class
II as per EN60730
Pollution class
Normal
Degree of protection of housing
IP30 as per EN60529
The product environmental declaration CE1E3181*)
contains data on environmen-
tally compatible product design and assessments (RoHS compliance, materials
composition, packaging, environmental benefit, disposal).
Meets the requirements for eu.bac certification
See product list at: http://www.eubaccert.eu/licences-by-criteria.asp
RDG160KN (License 213356)
Energy Effi
-
ciency Label
Control
accuracy [K]
Fancoil unit systems (2 pipes 2 wires)
AA
Heating 0.1
(Motorised actuator DC, variable fan speed)
Cooling 0.1
Fancoil unit systems (4 pipes)
A
Heating 0.4
(Thermal actuator 2-pt, variable fan speed)
Cooling 0.4
Connection terminals
Solid wires or stranded
wires with wire end sleeves
1 x 0.4…2.5 mm
2
or 2 x 0.4…1.5 mm
2
Minimal wiring cross section on
L, N, Q1, Q2, Q3, Y1, Y2, Y3, Y4
min 1.5 mm2
Housing front color
RAL 9003 white
Weight without / with packaging
RDG100KN
RDG160KN
0.270 kg / 0.380 kg
0.240 kg / 0.320 kg
*) The documents can be downloaded from http://siemens.com/bt/download.
Reference documentation
Handbook for Home and Building Control - Basic Principles
(http://www.knx.org/knx-en/training/books-documentation/knx-association-
books/index.php)
Synco
CE1P3127 Communication via the KNX bus for Synco 700, 900 and RXB/RXL
Basic documentation
Desigo CM1Y9775 Desigo RXB integration – S-mode
CM1Y9776 Desigo RXB / RXL integration – individual addressing
CM1Y9777 Third-party integration
CM1Y9778 Synco integration
CM1Y9779 Working with ETS
Environmental
Compatibility
eu.bac
General
Caution
17 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Connection terminals
RDG100KN
LX1 M
NQ1 Q2 Q3 Y1
SELV
X2
3191A01
CE+ CE -
D1 GND
Y2 Y3 Y4
RDG160KN
L
GX1 M
G0 Q1 Q2 Q3 Y50
SELV
X2
3191A11
CE+ CE-
D1 GND
Y10 Y20
L, N Operating voltage AC 230 V (RDG100KN)
G, G0 Operating voltage AC 24 V (RDG160KN)
L Feed for relays AC 24...230 V (RDG160KN)
X1, X2 Multifunctional input for temperature sensor
(e.g. QAH11.1) or potential-free switch
Factory setting:
– X1 = External temperature sensor
– X2 = No function
(function can be selected via parameters P38 / P40).
M Measuring neutral for sensors and switches
D1, GND Multifunctional input for potential-free switch
Factory setting: Operating mode switchover contact
(function can be selected via parameter P42).
Q1 Control output fan speed “low” AC 230 V
Q2 Control output fan speed “medium” AC 230 V
Q3 Control output fan speed “high” AC 230 V
Q1...Q3 Also for special functions AC 24...230 V
(RDG160KN)
Y1…Y4 Control outputs “Valve” AC 230 V
(RDG100KN)
("N/O" triac, for normally closed valves),
output for electric heater via external relay
Y10, Y20 Control outputs “Valve” DC 0...10 V
(RDG160KN)
Y50 Control output “Fan” DC 0...10 V
(RDG160KN)
CE+ KNX data +
CE- KNX data –
18 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Connection diagrams RDG100KN
Application
V1

V2

•2-pipe
YHC
•2-pipe and
radiator
•4-pipe
•2-stage
YHC
YH
1.
YR
YC
2.
•2-pipe
and electric
heater
YHC
E1
•4-pipe
and electric
heater
YH
E1
YC
N1 Room thermostat RDG100KN
F External circuit breaker
S1, S2 Switch (keycard, window contact,
presence detector, etc.)
S3 Switch at SELV input
(keycard, window contact)
B1, B2 Temperature sensor (return air tempe-
rature, external room temperature,
changeover sensor, etc.)
CE+ KNX data +
CE– KNX data –
M1 1- or 3-speed fan
V1, V2 Valve actuators:
On/Off or PWM, 3-position,
heating, cooling, radiator, heating /
cooling,
1st or 2nd stage
E1 Electric heater
K Relay
YH Heating valve actuator
YC Cooling valve actuator
YHC Heating / cooling valve actuator
YR Radiator valve actuator
E1 Electric heater with relay/contactor Y
1
st
/ 2
nd
1
st
/ 2
nd
stage
19 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23
Connection diagrams RDG160KN
DC 0...10 V fan
1- / 3-speed fan
Application
V1

V2

•2-pipe
YHC
•2-pipe and
radiator
•4-pipe
•2-stage
YHC
YH
1st
YR
YC
2nd
•2-pipe and
electric
heater
YHC
E1
•Compressor
1-stage
•Compressor
2-stage
1st
1st
2nd
20 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23

Other manuals for RDG100KN

6

This manual suits for next models

1

Other Siemens Thermostat manuals

Siemens RDE100.1DHW User manual

Siemens

Siemens RDE100.1DHW User manual

Siemens RDH10RF Operating instructions

Siemens

Siemens RDH10RF Operating instructions

Siemens RDF510 Series User manual

Siemens

Siemens RDF510 Series User manual

Siemens RDG400KN User manual

Siemens

Siemens RDG400KN User manual

Siemens RAA20 User manual

Siemens

Siemens RAA20 User manual

Siemens RDS120 User manual

Siemens

Siemens RDS120 User manual

Siemens REV34 User manual

Siemens

Siemens REV34 User manual

Siemens RDD100.1RF User manual

Siemens

Siemens RDD100.1RF User manual

Siemens REA23 User manual

Siemens

Siemens REA23 User manual

Siemens RDS110.R User manual

Siemens

Siemens RDS110.R User manual

Siemens RDD100 Series User manual

Siemens

Siemens RDD100 Series User manual

Siemens TH 192 DN User manual

Siemens

Siemens TH 192 DN User manual

Siemens RDJ100 User manual

Siemens

Siemens RDJ100 User manual

Siemens RAB20 Series Owner's manual

Siemens

Siemens RAB20 Series Owner's manual

Siemens RDS120 User manual

Siemens

Siemens RDS120 User manual

Siemens RDF301 User manual

Siemens

Siemens RDF301 User manual

Siemens Albatros RVS46 Series User manual

Siemens

Siemens Albatros RVS46 Series User manual

Siemens RDH100 User manual

Siemens

Siemens RDH100 User manual

Siemens Powers TH 192 S User manual

Siemens

Siemens Powers TH 192 S User manual

Siemens RDS120 User manual

Siemens

Siemens RDS120 User manual

Siemens BRTRF User manual

Siemens

Siemens BRTRF User manual

Siemens RDS110 User manual

Siemens

Siemens RDS110 User manual

Siemens RDG400 User manual

Siemens

Siemens RDG400 User manual

Siemens RLA162.5U User manual

Siemens

Siemens RLA162.5U User manual

Popular Thermostat manuals by other brands

Warmon TP520 installation instructions

Warmon

Warmon TP520 installation instructions

Comfort Stat CP1919 owner's manual

Comfort Stat

Comfort Stat CP1919 owner's manual

Timeguard TRT047N Installation & operating instructions

Timeguard

Timeguard TRT047N Installation & operating instructions

Seabreeze STS32 manual

Seabreeze

Seabreeze STS32 manual

Climate Technologies 43153 owner's manual

Climate Technologies

Climate Technologies 43153 owner's manual

Pro 1 IAQ T621-2 installation manual

Pro 1 IAQ

Pro 1 IAQ T621-2 installation manual

Mark PinTherm Mistral Technical manual

Mark

Mark PinTherm Mistral Technical manual

Fantini Cosmi CH110 manual

Fantini Cosmi

Fantini Cosmi CH110 manual

Nu-Heat SIGNATURE operating manual

Nu-Heat

Nu-Heat SIGNATURE operating manual

Alarmcom ADC-T3000 quick start guide

Alarmcom

Alarmcom ADC-T3000 quick start guide

Pro 1 IAQ T955 installation manual

Pro 1 IAQ

Pro 1 IAQ T955 installation manual

Fantini Cosmi CH123 user manual

Fantini Cosmi

Fantini Cosmi CH123 user manual

CORAB 7C user guide

CORAB

CORAB 7C user guide

Pro 1 IAQ T705 installation manual

Pro 1 IAQ

Pro 1 IAQ T705 installation manual

ensto ECO16TOUCH user manual

ensto

ensto ECO16TOUCH user manual

ICM Controls SC3211L Installation, operation & application guide

ICM Controls

ICM Controls SC3211L Installation, operation & application guide

Venstar EXPLORER Mini T2100 Owner's Manual & Installation Instructions

Venstar

Venstar EXPLORER Mini T2100 Owner's Manual & Installation Instructions

Server EZ-TOPPER 12B Series manual

Server

Server EZ-TOPPER 12B Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.