  7. Thermostat
  8. •
  9. Siemens RDF301 User manual

Siemens RDF301 User manual

Other manuals for RDF301

4

This manual suits for next models

3

Other Siemens Thermostat manuals

Siemens RDH10RF Quick start guide

Siemens

Siemens RDH10RF Quick start guide

Siemens QAW20 User manual

Siemens

Siemens QAW20 User manual

Siemens ZIEHL TR 1200 User manual

Siemens

Siemens ZIEHL TR 1200 User manual

Siemens KNX RDF301.50H User manual

Siemens

Siemens KNX RDF301.50H User manual

Siemens Powers TH 192 S Owner's manual

Siemens

Siemens Powers TH 192 S Owner's manual

Siemens Albatros2 RVS46 Series User manual

Siemens

Siemens Albatros2 RVS46 Series User manual

Siemens RDG200KN User manual

Siemens

Siemens RDG200KN User manual

Siemens EcoView 97-004 User manual

Siemens

Siemens EcoView 97-004 User manual

Siemens RDJ100RF/SET User manual

Siemens

Siemens RDJ100RF/SET User manual

Siemens RDF510 Series User manual

Siemens

Siemens RDF510 Series User manual

Siemens RDB160BN Operator's manual

Siemens

Siemens RDB160BN Operator's manual

Siemens RDS110 User manual

Siemens

Siemens RDS110 User manual

Siemens RDF880KN Series Operator's manual

Siemens

Siemens RDF880KN Series Operator's manual

Siemens RDG400KN Operator's manual

Siemens

Siemens RDG400KN Operator's manual

Siemens RDF301 User manual

Siemens

Siemens RDF301 User manual

Siemens RDG110 User manual

Siemens

Siemens RDG110 User manual

Siemens REV34 User manual

Siemens

Siemens REV34 User manual

Siemens RDG110 User manual

Siemens

Siemens RDG110 User manual

Siemens RDG160TU User manual

Siemens

Siemens RDG160TU User manual

Siemens REV100 User manual

Siemens

Siemens REV100 User manual

Siemens TH 192 S User manual

Siemens

Siemens TH 192 S User manual

Siemens RDH100 User manual

Siemens

Siemens RDH100 User manual

Siemens REV17 Series User manual

Siemens

Siemens REV17 Series User manual

Siemens QAW740 User manual

Siemens

Siemens QAW740 User manual

Popular Thermostat manuals by other brands

Full Gauge TIC-17C product manual

Full Gauge

Full Gauge TIC-17C product manual

Imit Chronomix S manual

Imit

Imit Chronomix S manual

ChiliTec ST-35 ana instruction manual

ChiliTec

ChiliTec ST-35 ana instruction manual

Salus VS05 Installer's/user's manual

Salus

Salus VS05 Installer's/user's manual

Azel D-500 user guide

Azel

Azel D-500 user guide

Honeywell Chronotherm III owner's manual

Honeywell

Honeywell Chronotherm III owner's manual

Charmeg MP-R user manual

Charmeg

Charmeg MP-R user manual

dixell WING XW40LS Installing and operating instructions

dixell

dixell WING XW40LS Installing and operating instructions

Network Thermostat NetX X7C-WIFI Installation and programming manual

Network Thermostat

Network Thermostat NetX X7C-WIFI Installation and programming manual

Radio Thermostat CT80 Operation guide

Radio Thermostat

Radio Thermostat CT80 Operation guide

HAI Omnistat RC-120 installation manual

HAI

HAI Omnistat RC-120 installation manual

Lennox iComfort E30 Installation and setup guide

Lennox

Lennox iComfort E30 Installation and setup guide

Lux Products PSD011Ba Installation and operating instructions

Lux Products

Lux Products PSD011Ba Installation and operating instructions

Computherm Q20 operating instructions

Computherm

Computherm Q20 operating instructions

Heatmiser neoStat user manual

Heatmiser

Heatmiser neoStat user manual

Mars HEAT CONTROLLER IR Wireless Thermostat user manual

Mars

Mars HEAT CONTROLLER IR Wireless Thermostat user manual

LUX LP0511D user manual

LUX

LUX LP0511D user manual

Saswell SAS920XWHB-7-S-RF User manual and warranty card

Saswell

Saswell SAS920XWHB-7-S-RF User manual and warranty card

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

s
3171
RDF301, RDF600KN RDF301.50 RDF301.50H
Semi flush-mount
communicating room
thermostats
RDF301
RDF301.50
..
RDF600KN
For 2
-pipe, 2-pipe with electrical heater, and 4-pipe fan coil units
For use with compressors in DX type equipment
•KNX bus communications (S-mode and LTE mode)
•Backlit display
•2P / PI / P control
•Outputs for on/off or 3-position control
•Outputs for 3-speed or 1-speed fan
•2 multifunctional inputs for keycard contact, external sensor, etc.
•Operating modes: Comfort, Economy and Protection
•Automatic or manual fan speed control
•Automatic or manual heating/cooling changeover
•Minimum and maximum limitation of room temperature setpoint
•Control depending on the room or the return air temperature
•Adjustable commissioning and control parameters
•Commissioning with Synco ACS, ETS or via local HMI
•Integration into Synco
•Integration into Desigo and Apogee via group addressing (ETS) or via
individual addressing
•Integration into third-party system via group addressing (ETS)
•AC 230 V operating voltage
CE1N3171en
2014-05-23
Building Technologies
Additional RDF600KN features:
•Independent function for window contact and presence detector
Additional RDF301.50 features:
•Four buttons to control KNX actuators via KNX S-mode
(functions: switching, dimming, blinds control, 8-bit scene)
Additional RDF301.50H features:
•Four buttons for hotel functions MUR (Make Up Room), DND (Do Not
Disturb) via KNX S-mode
Type of mounting / suitable conduit boxes:
•RDF600KN for round box, with min 60 mm diameter, min 40 mm depth
and recessed rectangular box with 60.3 mm fixing centers
•RDF301... for recessed rectangular box with 60.3 mm fixing centers
Use
Room temperature control (heating or cooling) in individual rooms and zones by
means of:
•2-pipe fan coil units
•2-pipe fan coil units with electrical heater
•4-pipe fan coil units
•Compressors in DX-type equipment
•Compressors in DX-type equipment with electrical heater
The RDF301... / RDF600KN controls:
•One single or 3-speed fan
•One or two on/off valve actuators
•One on/off valve actuator and one 1-stage electrical heater
•One 3-position valve actuator
•One 1-stage compressor in DX-type equipment, or one 1-stage compressor with
electrical heater
Used in systems with:
•Heating or cooling mode
•Automatic heating/cooling changeover
•Manual heating/cooling changeover
•Heating and cooling mode (e.g. 4-pipe system)
The room thermostats are delivered with a fixed set of applications.
The relevant application is selected and activated during commissioning using one
of the following tools:
•Synco ACS
•ETS
•Local DIP switch and HMI
Functions
•Room temperature control via built-in temperature sensor or external room
temperature / return air temperature sensor.
•Changeover between heating and cooling mode (automatically via local sensor
or bus, or manually).
•Selection of applications via DIP switches or commissioning tool.
•Selection of operating mode via operating mode button on the thermostat.
2 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23
•Temporary Comfort mode extension.
•1- or 3-speed fan control (automatically or manually).
•Display of current room temperature or setpoint in °C and/or °F.
•Minimum and maximum limitation of room temperature setpoint.
•Button lock (automatically and manually).
•2 multifunctional inputs, freely selectable for:
−Sensor for automatic heating / cooling changeover
−External room temperature or return air temperature sensor
−Dew point sensor
−Electric heater enable
−Fault input
−Monitor input for temperature sensor or switch state
RDF301…:
−Operating mode switchover contact … (keycard, window contact, etc )
RDF600KN:
−Window contact
−Presence detector
•Advanced fan control function, e.g. fan kick, fan start, selectable fan operation
(enable, disable or depending on heating or cooling mode).
•Purge function together with 2-port valve in a 2-pipe changeover system.
•Reminder to clean fan filters (adjust with P62).
•Floor heating temperature limitation.
•Reload factory settings for commissioning and control parameters.
•KNX bus (terminals CE+ and CE-) for communication with Synco or KNX
compatible devices.
•Display of outdoor temperature or time of day via KNX bus.
•Time scheduling and central control of setpoints via KNX bus.
•With a Synco RMx7xx controller, the energy demand signal of the thermostat is
used to optimize energy supply.
RDF301.50 only:
•Four buttons to control KNX actuators via KNX S-mode.
("switching groups" with functions such as switching, dimming, blinds control,
8-bit scene).
RDF301.50H only:
•Four buttons for Hotel applications to control via KNX S-mode.
Same functions as RDF301.50, but with dedicated button labels for hotel
applications: Make Up Room (MUR), Do Not Disturb (DND).
Applications
The thermostats support the following applications, which can be configured using
the DIP-switches on the inner side of the thermostat's front panel or a commissio-
ning tool.
All DIP switches need to be set to OFF (remote configuration, factory setting) to
select an application via commissioning tool.
Remote configuration
, via commissioning tool (factory set)
•Synco ACS
•ETS
DIP switches
1
ON
2 3
Remote configuration
3 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23
Applications for fan coil systems
Application and output signal, DIP switches, diagram
•2-pipe fan coil unit ON/OFF
(heating or cooling)
1
ON
2 3
•2-pipe fan coil unit with el. heater
(heating or cooling) ON/OFF
1
ON
2 3
3076D20
(B1)
M1
Y1
T
B2
T
T
(B1)
Y1
M1
3171D21
T
B2 YE
T
(B1)
T
(B1)
•2-pipe fan coil unit 3-position
(heating or cooling)
1
ON
2 3
•4-pipe fan coil unit ON/OFF
(heating and cooling)
1
ON
2 3
3076D20
(B1)
M1
Y1
T
B2
T
T
(B1)
T
Y2
Y1
M1
3076D22
(B1)
T
(B1)
4 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23
Applications for Universal systems
Application and output signal, DIP switches, diagram
•Chilled / heated ceiling ON/OFF
(heating or cooling)
1
ON
2 3
•Chilled / heated ceiling with electric
heater (heating or cooling) ON/OFF
1
ON
2 3
3191S11
N1
T
B1
T
B2
T
D3
Y1
3191S12
N1
T
YE
B1
T
B2
T
D3
Y1
•Chilled / heated ceiling 3-position
(heating or cooling)
1
ON
2 3
•Chilled ceiling and radiator ON/OFF
(heating and cooling)
1
ON
2 3
3191S11
N1
T
B1
T
B2
T
D3
Y1
3191S13
N1
T
B1
T
D3
Y1
YR
5 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23
Applications for heat pump systems
Application and output signal, DIP switches, diagram
•1-stage compressor ON/OFF
(heating or cooling)
1
ON
2 3
•1-stage compressor with electric
heater (heating or cooling)
ON/OFF
1
ON
2 3
3181S31
N1
T
B1
T
D3
3181S32
N1
T
YE
B1
T
D3
•1-stage compressor ON/OFF
(heating and cooling)
1
ON
2 3
3181S35
N1
T
B1
T
D3
Y1 Heating or heating / cooling
valve actuator
B1 Return air temperature sensor or external
room temperature sensor (optional)
Y2 Cooling valve actuator
B2 Changeover sensor (optional)
YE Electric heater
M1 3- or 1-speed fan
Key
6 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23
Type summary
Product no. Stock no. Operating
voltage
Control outputs
Suitable
conduit
box 2)
3-
pos
ON/
OFF
DC
0..10 V
KNX switching
groups
RDF301
S55770-T104
AC 230 V
1 1)
2 1)
--
rectangular
RDF301.50
S55770-T105
AC 230 V
1
1)
2
1)
--

rectangular
RDF301.50H
S55770-T334
AC 230 V
1 1)
2 1)
--
Hotel: MUR, DND 3)
rectangular
RDF600KN S55770-T293 AC 230 V 1
1)
2
1)
-- round &
rectangular
1) Selectable: ON/OFF or 3-position.
2) Rectangular conduit box e.g. ARG71.
Round CEE conduit box min 60 mm diameter and min 40 mm depth.
3) MUR: Make Up Room, DND: Do Not Disturb.
Ordering
•When ordering, indicate both product number / SSN number and name:
E.g. RDF301 / S55770-T104 room thermostat
•Order valve actuators separately.
Equipment combinations
Type of unit Product no. Data
sheet
Cable temperature sensor or changeover
sensor
QAH11.1 1840
Room temperature sensor
QAA32 1747
Condensation monitor
QXA2601 /
QXA2602 /
QXA2603 /
AQX2604
3302
Electromotoric ON/OFF actuator
SFA21... 4863
Electromotoric ON/OFF valve and
actuator
(only available in AP, UAE, SA and IN)
MVI…/MXI… 4867
Zone valve actuators
(only available in AP, UAE, SA and IN)
SUA… 4832
Thermal actuator (for radiator valves),
NO
STA23... 4884
Thermal actuator
(for small valves 2.5 mm), NC
STP23... 4884
On/off actuators
7 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23
Electrical actuator, 3-position
(for radiator valve)
SSA31... 4893
Electrical actuator, 3-position
(for 2- and 3-port valves / V…P45)
SSC31 4895
Electrical actuator, 3-position
(for small valve 2,5 mm)
SSP31… 4864
Electrical actuator, 3-position
(for small valve 5,5 mm)
SSB31... 4891
Electrical actuator, 3-position
(for small valve 5,5 mm)
SSD31... 4861
Electromotoric actuator, 3-position
(for valves 5.5 mm)
SQS35… 4573
For the maximal number of actuators in parallel, refer to information in the data sheets
of the selected actuators and to this list, depending on which value is lower:
•Parallel operation of max 6 SS… actuators (3-pos) is possible.
•Parallel operation of max 10 on/off actuators is possible.
•Parallel operation of SQS35 is not possible.
Accessories
Designation Product no / SSN
Data
sheet
Changeover mounting kit
(50 pcs/package)
ARG86.3 N3009
Plastic mounting bracket for semi-
flush-mount thermostats RDF301... for
increasing the headroom in the conduit
box by 10mm
ARG70.3 N3009
Conduit box for semi-flush mounted
thermostat RDF301...
ARG71 /
S55770-T137 N3009
KNX Power supply 160 mA (Siemens BT LV)
5WG1 125-1AB02
--
KNX Power supply 320 mA (Siemens BT LV)
5WG1 125-1AB12
--
KNX Power supply 640 mA (Siemens BT LV)
5WG1 125-1AB22
--
3-position actuators
Note:
8 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23
Mechanical design
The thermostats consist of 2 parts:
•Front panel with electronics, operating elements and built-in room temperature
sensor.
•Mounting base with power electronics.
The rear of the mounting base contains the screw terminals.
Slide the front panel in the mounting base and snap on.
Operation
and
settings
RDF301, RDF600KN
RDF301.50
RDF301.50H
1 Operating mode selector
2 Change fan operation
3 Adjust setpoint and control parameters
4 Four buttons to control KNX actuators via KNX S-mode
(functions: switching, dimming, blinds control, 8-bit scene)
5 Four dedicated buttons for hotel functions (Make Up Room, Do Not Disturb)
via KNX S-mode (functions: switching)
Display
1 Operating mode
Protection
Comfort
Economy
Auto Timer according to
schedule (via KNX)
2 Displays room temperature, set-
points and control parameters.
Symbol indicates current room
temperature
3 Fan mode
Auto fan active
Fan speed
low, medium, high
4 Heating/cooling mode
Cooling
Heating
Electrical heater active
5
Condensation in room
(dewpoint sensor active)
6 Indicates fault or reminder
7 Temporary comfort mode
extension active
8 Additional user information, like
outdoor temperature or
time of day from KNX bus.
Selectable via parameters
9 Button lock active
10
Weekday 1…7 from KNX bus
(1 = Monday / 7 = Sunday)
RDF301.50
RDF301.50H
1
2 5
3 8
6
9
7
4
10
3
2
1
3
4 4 5
1
2
5
1 2
3
9 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23
Engineering notes
See the "Reference documentation", page 15 for information on how to engineer
the KNX bus (topology, bus repeaters, etc.) and how to select and dimension
connecting cables for supply voltage and field devices.
Mounting and installation
Mount the room thermostat on a conduit box. Do not mount on a wall in niches or
bookshelves, behind curtains, above or near heat sources, or exposed to direct
solar radiation. Mount about 1.5 m above the floor.
Mounting / Dismounting
•Mount the room thermostat on a clean, dry indoor place without direct airflow
from a heating / cooling device, and not exposed to drips or splash water.
•RDF301… : In case of limited space in the conduit box use the mounting
bracket ARG70.3 to increase the headroom by 10mm
•Before removing the front cover, disconnect the power supply.
Wiring See the mounting instructions M3171... and M3076.1 enclosed with the
thermostat.
•Comply with local regulations to wire, protection and earth the thermostat.
•The device has no internal fuse for supply lines to fan and actuators. To avoid
risk of fire and injury due to short-circuits, the AC 230 V mains supply line must
have a circuit breaker with a rated current of no more than 10 A.
•Properly size the cables to the thermostat, fan and valve actuators for
AC 230 V mains voltage.
•Use only valve actuators rated for AC 230 V.
•The wiring cross section used for power supply (L, N), fan (Q1, Q2, Q3,N) and
230 V outputs (Yx -N) must be adapted to the preceding overload protection
elements (10A) under all circumstances. Comply under all circumstances with
local regulations
•Cables of SELV inputs X1-M/X2-M: Use cables with 230 V insulation, as the
conduit box carries AC 230 V mains voltage.
•Inputs X1-M or X2-M of different units (e.g. summer/winter switch) may be
connected in parallel with an external switch. Consider overall maximum
contact sensing current for switch rating.
•KNX communication cables (input CE+ / CE-): Use cables with 230 V
insulation, as the conduit box carries AC 230 V mains voltage.
•No metal conduits.
•No cables provided with a metal sheath.
•Disconnect from supply before opening the cover.
•When a KNX bus power supply is connected on the line with communicating
thermostats and Synco controller, the internal KNX power supply of the Synco
controllers must be switched off.
10 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23