Siemens 667/HB/47750/000 User manual

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 1 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
UPS Solution General Handbook
Part no.
667/HB/47750/000
THIS DOCUMENT IS ELECTRONICALLY APPROVED
AND HELD IN THE STC DOCUMENT CONTROL TOOL
Prepared By Checked and Released
Company/Dept. Siemens Traffic Solutions/Engineering Siemens Traffic Solutions/ Engineering
Name Ore Oluwatudimu David Martin
Function Product Development Engineer Hardware Engineering Manager
Signature
Date
COPYRIGHT STATEMENT
The information contained herein is the property of Siemens plc. and is supplied without liability for errors
or omissions. No part may be reproduced or used except as authorised by contract or other written
permission. The copyright and the foregoing restriction on reproduction and use extend to all media in
which the information may be embodied
Copyright Siemens plc 2017 All Rights Reserved

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 2 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
Preface
SAFETY INFORMATION
Safety of Installation and Maintenance Personnel
In the interests of health and safety, when installing, using or servicing this
equipment the following instructions must be noted and adhered to:
(1) Only skilled or instructed personnel, with relevant technical knowledge
and experience, who are familiar with the safety procedures required
when dealing with modern electrical/electronic equipment, are to be
allowed to use and/or work on this equipment. All work shall be
performed in accordance with the Electricity at Work Regulations 1989.
(2) Such personnel must take heed of all relevant notes, cautions and
warnings in this Handbook and any other Document or Handbooks
associated with this equipment.
(3) The equipment must be correctly connected to the specified incoming
power supply.
(4) Mains voltages may be present within traffic system. Before any
maintenance work within the system is carried out, any mains supply to it
must be isolated or switched off.
(5) Mains voltages may still be present within traffic equipment even when
the site mains supply has been isolated or switched off. The UPS
Solution must be completely off to ensure no mains power is supplied to
connected traffic equipment.
(6) Only trained / competent persons should work on this equipment.
(7) Surfaces within the associated traffic equipment get hot, e.g. lamp, lens
and reflector. Therefore care should be taken when working in such
areas.
(8) Any power tools must be regularly inspected and tested.
(9) Any ladders used must be inspected before use to ensure they are
sound and not damaged.
(10) When using a ladder, before climbing it, ensure that it is erected properly
and is not liable to collapse or movement. If using a ladder near a
carriageway, ensure that the work area is properly signed and coned.
(11) Any personnel working on site must wear the appropriate protective
clothing with high visibility jackets and safety boots as a minimum.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 3 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
Safety of Road Users
It is important that all personnel are aware of the dangers to road users that
could arise during repair and maintenance of traffic control equipment.
Ensure that the junction area is coned and signed as necessary to warn
motorists and pedestrians of any dangers and to help protect the personnel
working on the site.
Precautions for Safe Battery Handling and Storage
Keep battery containers tightly closed when not in use.
If the battery case is broken, avoid contact with any internal components or
materials.
Do not handle near heat, sparks or open flames.
Protect battery containers from physical damage to avoid leaks or spills.
Place cardboard or other insulating material between layers of stacked
batteries to avoid damage and short circuits.
Do not allow conductive material to touch the battery terminals. A dangerous
short-circuit may occur and cause battery failure, fire, arcing, flash burns, etc.
Keep away from combustible materials, organic chemicals, reducing
substances, metals, strong oxidizers and water.
Batteries must be charged in a ventilated area. General ventilation is
acceptable.
Insulated tools must be used at all times and cases involving batteries.
For further information on proper battery handling see the Lead Crystal
Battery User Manual – 667/HB/47764/000.
Fault Protection RCDs
Any traffic controller, Siemens type or otherwise, supported by the UPS must
be fitted with a 300mA RCD at its mains input point. This ensures the quality
of fault protection, no matter what fault scenario the installation may face.
See section 7.2 of this document for more details

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 4 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
MAINTENANCE PROVISION (MP)
Product Reference
UPS Solution – 667/1/47750/ETC.
Installation and Commissioning
Methods of installation, configuration and commissioning are described in this
handbook. In addition, there are a series of documents which have more
specific detail but are supplied by the OEM (Original Equipment
Manufacturer). These documents are listed in section 1.2 below.
Spares and Maintenance
The UPS system elements are designed for ‘return to base’ repair with the
exception of battery replacement.
Modifications
There are no approved modifications for this product.
Warning
Use of components other than those indicated within this document or
modifications or enhancements that have not been authorised by Siemens
will invalidate Type Approval of this product.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 5 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
CONTENTS
1Introduction........................................................................................................................9
1.1 Scope....................................................................................................................9
1.2 Related Documents................................................................................................9
1.3 Definitions..............................................................................................................9
2System Overview..............................................................................................................10
2.1 Description...........................................................................................................10
2.2 Cabinet Variants ..................................................................................................10
2.3 Supported Loads..................................................................................................10
2.4 Generator Connectivity.........................................................................................11
2.5 Electrical Information............................................................................................11
3Modular Overview.............................................................................................................12
3.1 UPS Cabinet Modules..........................................................................................12
3.2 Battery Expansion Cabinet Modules.....................................................................13
3.3 Modular Elements................................................................................................14
3.3.1 Reinforced Cabinet Stool..................................................................................14
3.3.2 Vented Cabinet Outer Case..............................................................................14
3.3.3 Battery Housing Module...................................................................................14
3.3.4 UPS Housing Module.......................................................................................15
3.3.5 DC Housing Module.........................................................................................16
4Hardware Overview ..........................................................................................................17
4.1 Alpha FXM UPS unit ............................................................................................17
4.2 Universal Automatic Transfer Switch....................................................................18
4.3 Lead Crystal Batteries..........................................................................................19
5Sizing the UPS Solution...................................................................................................20
5.1 Key Considerations..............................................................................................20
5.2 Sizing Example....................................................................................................21
5.2.1 Which UPS Unit Should be Installed?...............................................................21
5.2.2 How Many Battery Packs are Required?...........................................................21
6Internal Cabling Scheme..................................................................................................23
6.1 UPS Cabinet Internal Wiring.................................................................................23
6.2 Battery Expansion Cabinet Internal Wiring............................................................24
7External Cabling Scheme.................................................................................................25
7.1 Mains Power Supply ............................................................................................25
7.2 UPS Earthing and Fault Protection RCDs.............................................................25
7.3 UPS Fault / Alarm Relay Contacts........................................................................26
7.4 Ethernet Cable.....................................................................................................26
7.5 Battery Expansion................................................................................................26
8Further UPS Connectivity ................................................................................................27
8.1 Battery Temperature Sensor ................................................................................27
8.2 RS232 Interface...................................................................................................27
8.3 LAN Interface.......................................................................................................27
9Installation........................................................................................................................28
9.1 Required Tools and Consumables........................................................................28
9.2 Preparing and Installing the Reinforced Stool.......................................................29
9.3 Pulling and Gland Ducted Cables.........................................................................30

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 6 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
9.4 Fitting the Vented Cabinet Outer Case and Sealing the Base...............................31
9.5 Fitting and Connecting the Battery Housing Module..............................................32
9.6 Mounting and Connecting the UPS Housing Module.............................................34
9.7 Mounting and connecting the DC Housing Module................................................35
9.8 Terminating External Cables into the UPS Connection Panel ...............................36
9.9 Terminating External Cables into the DC Connection Panel..................................37
9.10 Terminating and Connecting the Ethernet Cable...................................................37
9.11 Fitting and Connecting the Batteries.....................................................................38
9.12 Fitting the Battery Temperature Sensor................................................................39
10 Isolation Switches............................................................................................................40
10.1 Housing Module MCBs.........................................................................................40
10.2 Universal Automatic Transfer Switch (UATS)........................................................40
10.3 FXM UPS Unit......................................................................................................41
11 Commissioning ................................................................................................................42
11.1 Electrical Safety Testing.......................................................................................42
11.2 TT Earth Electrode Test.......................................................................................42
11.3 Putting the UPS Solution in BYPASS...................................................................43
11.4 Powering and Commissioning the Controller........................................................43
11.5 Starting Up the UPS Solution...............................................................................43
11.6 Testing the UPS Battery Support Function ...........................................................44
12 UPS System Operation.....................................................................................................45
12.1 Operating Modes .................................................................................................45
12.2 Active Fault Monitoring.........................................................................................45
12.2.1 Fault / Alarm Relay Contacts........................................................................45
12.2.2 Fault Monitoring using Siemens RMS and UTMC Systems...........................47
12.3 Communicating with the UPS Solution .................................................................48
12.3.1 Three-Button Interface..................................................................................48
12.3.2 RS232 Interface...........................................................................................48
12.3.3 LAN Interface...............................................................................................50
12.4 Battery Charging..................................................................................................52
12.5 Temperature De-Rating........................................................................................53
12.5.1 Power output................................................................................................53
12.5.2 Battery Charging ..........................................................................................54
12.5.3 Battery Support Hold Up Times ....................................................................54
12.6 Generators...........................................................................................................54
12.6.1 The Generator Connect Feeder Pillar...........................................................54
12.6.2 Generator Selection......................................................................................55
12.6.3 Protection and Reference Earthing...............................................................55
12.6.4 Connecting a Generator to the UPS Solution................................................56
12.6.5 Disconnecting a Generator from the UPS Solution:.......................................56
13 Maintenance .....................................................................................................................57
13.1 Periodic inspection...............................................................................................57
13.2 Maintenance Bypass Switching............................................................................58
13.3 Switching Off the UPS Solution............................................................................59
13.4 First Line Maintenance.........................................................................................60
13.4.1 Replacing the Alpha FXM UPS unit ..............................................................60
13.4.2 Replacing a Battery Pack .............................................................................61
13.4.3 Replacing an Alpha UATS unit......................................................................63
13.5 Second Line Maintenance....................................................................................63
14 Disposal............................................................................................................................64
14.1 Under Maintenance Contract................................................................................64
14.2 End of Life and Scrapping....................................................................................64

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 7 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
15 Part Numbers / Spares List..............................................................................................65
15.1 Hardware Spares.................................................................................................65
15.2 Housing Modules.................................................................................................65
15.3 Outer Case and Stool...........................................................................................65
15.4 Connection Panel and MCB Spares.....................................................................65
15.5 Connection Accessories.......................................................................................65
15.6 Generator Connect Feeder Pillar..........................................................................65
APPENDIX A – Estimated Hold Up Times ..............................................................................66
APPENDIX B – FXM UPS Faults and Alarms..........................................................................69
APPENDIX C – Hardware Datasheets.....................................................................................70
Alpha FXM Series UPS Unit.............................................................................................70
Alpha Universal Automatic Transfer Switch (UATS)..........................................................72
Betta Batteries 6CNFT-55 12V 55Ah Front Terminal Lead Crystal Battery........................74
APPENDIX D – UPS Commissioning Certificate....................................................................76
Figure 3-1: UPS Cabinet Modules.......................................................................................12
Figure 3-2: Battery Expansion Cabinet Modules (Cabinet removed).....................................13
Figure 3-3: Reinforced Stool – FRONT VIEW (CET plate attached).....................................14
Figure 3-4: Battery Housing Module.....................................................................................15
Figure 3-5: UPS Housing Module ........................................................................................15
Figure 3-6: DC Housing Module (shown fitted on top of a battery housing module)..............16
Figure 4-1: Alpha FXM Series UPS Unit..............................................................................17
Figure 4-2: Universal Automatic Transfer Switch..................................................................18
Figure 4-3: 6CNFT-55 Lead Crystal Battery with Key Electrical Information..........................19
Figure 5-1: Battery Hold up times at 20°C and 0°C..............................................................20
Figure 5-2: Sizing Example – Battery Pack Selection...........................................................22
Figure 6-1: UPS Cabinet Internal Wiring Diagram................................................................23
Figure 6-2: Battery Expansion Cabinet Internal Wiring Diagram...........................................24
Figure 7-1: Mains Power Supply Chain................................................................................25
Figure 9-1: Reinforced Stool and CET plate.........................................................................29
Figure 9-2: Stool Installation Diagram..................................................................................30
Figure 9-3: Reinforced Stool – LEFT HAND SIDE VIEW......................................................31
Figure 9-4: Battery Housing Modules stacked on the Reinforced Stool (Cabinet removed)...32
Figure 9-5: Battery Housing module mount..........................................................................33
Figure 9-6: Earth Connection between Battery Housing modules.........................................33
Figure 9-7: UPS Housing mounted on Battery Housing within Cabinet.................................34
Figure 9-8: Battery Cable Loom Connectors........................................................................35
Figure 9-9: UPS Connection Panel......................................................................................36
Figure 9-10: Battery Terminals Connected with the Terminal Linking Bar.............................38
Figure 9-11: Battery Temperature Sensor............................................................................39
Figure 10-1: UATS Switches................................................................................................40
Figure 10-2: Alpha FXM UPS Circuit Breakers.....................................................................41
Figure 12-1: Fault Monitoring Connectivity Example ............................................................47
Figure 12-2: Alpha FXM Series UPS RS232 Interface Screenshot.......................................49
Figure 12-3: LAN Interface Screenshot – Relay Contact Configuration.................................51
Figure 12-4: Battery Charging Cycle....................................................................................53
Figure 12-5: Generator Connect Feeder Pillar......................................................................54
Figure 12-6: Three-position Changeover Switch ..................................................................56
Figure 13-1: Battery Terminals Connected with the Terminal Linking Bar.............................62
Figure A-0-1: Estimates of UPS Solution Performance at +20°C..........................................66
Figure A-0-2: Estimates of UPS Solution Performance at 0°C..............................................67
Figure A-0-3: Estimates of UPS Solution Performance at -25°C...........................................68

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 8 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
Table 2-1: UPS Load Suitability...........................................................................................10
Table 2-2: UPS Solution Electrical Information.....................................................................11
Table 3-1: UPS Cabinet Module Quantities..........................................................................12
Table 3-2: Battery Expansion Cabinet Module Quantities.....................................................13
Table 4-1: FXM Series UPS – Key Electrical Information.....................................................17
Table 4-2: UATS – Key Electrical Information......................................................................18
Table 7-1: Alarm Contact Cable Specification......................................................................26
Table 7-2: Ethernet Cable Specification...............................................................................26
Table 7-3: Battery Expansion Cable Specification................................................................26
Table 9-1: Installation Steps for the UPS and Battery Expansion Cabinets...........................28
Table 9-2: RJ45 Interface Cable Connection........................................................................37
Table 12-1: Key UPS Solution Operating Modes..................................................................45
Table 12-2: Default Fault Contact Settings...........................................................................46
Table 12-3: RMS Bit Labelling and Description....................................................................47
Table 12-4: RS232 Interface Connection Information...........................................................48
Table 12-5: LAN Interface Connection Information...............................................................50
Table 12-6: Maximum Output Power against Ambient Temperature.....................................53
Table B-1: FXM UPS Unit Fault and Alarms.........................................................................69
CHANGE HISTORY
Version
Date
Author
Change
1 – 4 Jan
2014 Ore
Oluwatudimu Produce Document
5Nov
2014 Ashley Thorpe Section 15 – added black outer case variant to parts list
6Sept
2016 Ore
Oluwatudimu Change note TS008289 applies.
7Jan
2017 Ore
Oluwatudimu Change note TS008468 applies.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 9 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
1 Introduction
1.1 Scope
This handbook provides a general description of the Siemens UPS Solution and its key
elements, outlining the detailed procedures for installation, commissioning and
maintenance.
1.2 Related Documents
Reference Title Author/Contact
667/HB/47760/000 Alpha FXM Series UPS Installation and Operation
Manual Alpha Technologies
Europe Ltd.
667/HB/47761/000 Alpha Universal Automatic Transfer Switch
Installation Manual Alpha Technologies
Europe Ltd.
667/HB/47764/000 Lead Crystal Battery User Manual Betta Batteries
667/US/47764/000 Lead Crystal Battery Material Safety Data Sheet Betta Batteries
667/HE/45950/000 ST950 ELV Installation, Commissioning and
Maintenance Handbook Dave Martin
667/HE/46950/000 ST950 LV Installation, Commissioning and
Maintenance Handbook Dave Martin
667/HB/45040/000 Isolators and Feeder Pillars General Handbook Peter Lings
1.3 Definitions
Abbreviation
Explanation
DNO Distribution Network Operator
GUI Graphical User Interface
LAN Local Area Network
LC Lead Crystal (refers to battery technology)
LCD Liquid Crystal Display
MCB Miniature Circuit Breaker
MET Main Earth Terminal
OEM Original Equipment Manufacturer
OMU Outstation Monitoring Unit
OTU Outstation Transmission Unit
SNMP Simple Network Management Protocol
SOC State of Charge
UATS Universal Automatic Transfer Switch
UPS Uninterruptable Power Supply
VRLA Valve Regulated Lead Acid (refers to battery technology)

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 10 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
2 System Overview
2.1 Description
The UPS Solution has been designed to provide seamless battery support to a Siemens
type traffic controller in the event of a loss of mains supply. The solution offers a line-
interactive uninterruptable power supply unit to constantly monitor the status of the mains
supply, maintaining a battery bank when power is present and switching to battery back
up when it is not. The switch from mains power to battery back up, and back again, is
almost instantaneous, ensuring that the traffic intersection controller sees no significant
break in power and remains operational.
The UPS Solution can be scaled to suit a range of power and battery hold up time
requirements. Hold up times can be extended further still with the connection of an
external generator as described in section 2.4.
2.2 Cabinet Variants
The UPS solution has been designed to be housed within a standard Siemens traffic
controller cabinet outer case to reduce its visual impact. When installed, the controller
and UPS solution cabinets appear identical. Two cabinet variants are available, as
described below.
UPS Cabinet - Houses the UPS system equipment and up to two
48V 55Ah battery banks.
Battery Expansion Cabinet - Houses up to three 48V 55Ah battery banks only.
The Battery Expansion cabinet can be installed
alongside the UPS cabinet, providing additional
battery support in cases when an extended period of
support time is required.
WARNING: No more than one Battery Expansion Cabinet can be connected to
any one UPS Cabinet.
2.3 Supported Loads
The UPS solution is ideally suited to support ELV LED traffic controllers, but can also
support LV installations. It caters for intersection loads up to 2000W in two optimised
steps via a choice of UPS unit:
UPS Unit
Max Power Output
Suitable for
Alpha FXM1100 1100W / VA Loads up to and including 1000W
Alpha FXM2000 2000W / VA Loads from 1000W to 2000W
Table 2-1: UPS Load Suitability
WARNING: Both UPS units are subject to de-rating at high temperature. This
must be considered when specifying each solution. See sections 4.1 and 12.5.1
for details. See section 5.2 for a solution sizing example.
WARNING: Any traffic controller, Siemens type or third party, which is powered
via the UPS solution must be fitted with a 300mA RCD. See section 7.2 for
more details.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 11 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
2.4 Generator Connectivity
The UPS solution offers the possibility of connecting up an external diesel generator
through a specially designed supporting product, the Generator Connect Feeder Pillar.
This adaptation of the normal large feeder pillar allows a portable generator to be used as
a substitute for the mains supply in cases of extended power outages.
See section 12.6 for more information on the Generator Connect Feeder Pillar.
2.5 Electrical Information
Parameter
Value
Input
:
Voltage 230Vac (150Vac – 328Vac without switching to battery support)
Frequency 50Hz / 60Hz Auto-detect (±5%)
Current (at max battery
charging current) FXM1100: 8A at 230Vac
FXM2000: 15A at 230Vac
Mains Input Circuit Breaker
Rating 20A at 230Vac
Output:
Voltage 230Vac
Frequency 50Hz / 60Hz Auto-detect (±5%)
Maximum Power
1
FXM1100: 1100 W/VA
FXM2000: 2000 W/VA
Waveform Pure Sine Wave
Switching Time <5ms
Voltage Distortion <3% THD
Efficiency Normal mode (LINE): >98%
Battery support mode (INVERTER): >82%
Battery Charging:
Charge Current 10A
Temperature Compensation -5mV/°C/Cell
Battery Type 12V 55Ah Valve Regulated Lead Crystal
Environment:
Operating Temperature -25°C to +74°C
Operating Altitude 12000ft
Operating Humidity Up to 95%
Table 2-2: UPS Solution Electrical Information
1Power output de-rates in high ambient temperatures. See sections 4.1 and 12.5 for details.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 12 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
3 Modular Overview
This section details the five key building blocks of the UPS Solution; the stool, cabinet
outer case and three equipment housing modules.
3.1 UPS Cabinet Modules
Table 3-1 and Figure 3-1 show the modules involved in making up the UPS cabinet.
UPS Solution Modules
Qu
antity
Refer to
Reinforced Stool 1 Section 3.3.1
Vented Cabinet Outer Case 1 Section 3.3.2
Battery Housing 2 (maximum)
2
Section 3.3.3
UPS Housing 1 Section 3.3.4
DC Housing 0 N/A
Table 3-1: UPS Cabinet Module Quantities
Figure 3-1: UPS Cabinet Modules
2The UPS Cabinet can be fitted with just one Battery Housing module in cases where
reduced battery support is required.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 13 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
3.2 Battery Expansion Cabinet Modules
Table 3-2 and Figure 3-2 show the modules involved in making up the Battery Expansion
Cabinet.
UPS Solution Modul
es
Quantity
Refer to
Reinforced Stool 1 Section 3.3.1
Vented Cabinet Outer Case 1 Section 3.3.2
Battery Housing 3 (maximum)
3
Section 3.3.3
UPS Housing 0 N/A
DC Housing 1 Section 3.3.5
Table 3-2: Battery Expansion Cabinet Module Quantities
Figure 3-2: Battery Expansion Cabinet Modules (Cabinet removed)
3The Battery Expansion Cabinet can be fitted with one, two or three Battery Housing modules
allowing each solution to be tailored to the customer performance requirements.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 14 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
3.3 Modular Elements
3.3.1 Reinforced Cabinet Stool
UPS Cabinet and Battery Expansion Cabinet
The Reinforced Cabinet Stool is a load bearing replacement to the normal ST950 cabinet
stool. It provides mounting points for the cabinet outer case and internal housing modules
as well as a CET plate for the earthing of cables entering and exiting the cabinet via
underground ducting.
Figure 3-3: Reinforced Stool – FRONT VIEW (CET plate attached)
3.3.2 Vented Cabinet Outer Case
UPS Cabinet and Battery Expansion Cabinet
Plastic ventilation devices have been added to the ST950 outer case to provide the
additional airflow required by UPS system equipment. The vents are fitted behind the
cabinet’s front door and are invisible when the door is closed.
3.3.3 Battery Housing Module
UPS Cabinet and Battery Expansion Cabinet
The Battery Housing module is the main building block of the internal mounting frame. It
provides mounting and connectivity for one 48V 55Ah battery bank, made up of four
individual batteries. A 63A double-pole MCB on the right hand side provides isolation,
allowing the batteries to be removed and replaced whilst the UPS Solution is still
powering the intersection, and a simple battery connector gives easy plug-and-play
connectivity to the rest of the system.
Battery Housings are stackable and are designed to slide into place on top of each other
for ease of installation. A bar, fitted to the front of each module, can be raised to form a
lip for battery retention.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 15 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
Figure 3-4: Battery Housing Module
NOTE: The Battery Housing Module does not come with batteries fitted.
Batteries are shipped separately and should only be mounted at the end of
installation.
3.3.4 UPS Housing Module
UPS Cabinet ONLY
The UPS Housing contains the key system hardware and is the main control and
connectivity hub for the entire UPS solution. It contains the UPS unit and UATS (as
described in sections 4.1 and 4.2) as well as a UPS Connection Panel that provides
termination for internal and external cabling related to the entire UPS Solution, including
mains input and output, Battery Expansion Cabinet connection and fault-monitoring relay
contacts. A 20A double-pole MCB provides mains input isolation. Wiring of the UPS
Connection Panel is detailed in sections 6.1 and 9.8.
Figure 3-5: UPS Housing Module

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 16 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
3.3.5 DC Housing Module
Battery Expansion Cabinet ONLY
The DC Housing provides a Connection Panel similar to that found within the UPS
Housing. This DC Connection Panel allows for the termination of internal and external
cabling related to the Battery Expansion Cabinet only. A 63A double-pole MCB can be
used to isolate the Battery Expansion Cabinet from the rest of the UPS Solution.
Figure 3-6: DC Housing Module (shown fitted on top of a battery housing
module)

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 17 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
4 Hardware Overview
4.1 Alpha FXM UPS unit
The Alpha FXM series from Alpha Technologies are outdoor, military grade, line-
interactive Uninterruptable Power Supply units that have been selected for use within the
Siemens UPS solution. The unit offers an extended operating temperature range and is
well suited for use with ELV/LV LED type traffic controller equipment.
Figure 4-1: Alpha FXM Series UPS Unit
Each Siemens UPS solution uses one of two FXM series UPS units, depending on the
power requirements of the traffic intersection to be supported.
FXM1100 – Intersections up to 1kW
FXM2000 – Intersections up to 2kW
Key information for each type of unit is listed here. For more detailed information, please see
APPENDIX C – Hardware Datasheets or consult the FXM Series UPS Operating Manual –
667/HB/47760/000.
Parameter FXM1100 FXM2000
Nominal Voltage 230VAC
Nominal Frequency 50Hz / 60Hz
Typical Efficiency >98% (normal mode)
Typical Transfer time <5ms
Operating Temperature -40°C to +74°C
Power output:
At -40° to +50° (Nominal) 1100W/VA 20000W/VA
At 65° (UK Worst case) 962.5W/VA 1700W/VA
At 74° (Operating worst case) 838.75W/VA 1520W/VA
De-rating 1.25% per degree above 55°C 1.0% per degree above 50°C
Table 4-1: FXM Series UPS – Key Electrical Information
NOTE: Care must be taken when selecting a UPS unit if high temperatures are
expected. See section 5 for a solution sizing information and 12.5.1 for further
information on temperature de-rating.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 18 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
4.2 Universal Automatic Transfer Switch
The Universal Automatic Transfer Switch (UATS), also from Alpha Technologies,
provides a manual bypass switch for maintenance purposes. It has been designed to
work alongside the Alpha FXM UPS series and includes an automatic transfer facility that
constantly monitors the output of the UPS unit and will switch the system to bypass if a
fault is detected.
Figure 4-2: Universal Automatic Transfer Switch
Key information on the UATS is listed below. For further information on the unit, please
see APPENDIX C – Hardware Datasheets or consult the UATS Installation Manual –
667/HB/47761/000.
Parameter
Value
Nominal Voltage 230Vac
Nominal Frequency 50Hz / 60Hz
Rated Input Current 16A
Rated Output Current 16A
Max. Output Power 3600W/VA (at +40°C)
Operating Temperature -40°C to +74°C
Table 4-2: UATS – Key Electrical Information

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 19 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
4.3 Lead Crystal Batteries
Battery backup within the Siemens UPS solution is provided by banks of 55Ah 12V front
terminal Lead Crystal batteries. Each bank consists of 4 of these batteries, creating a
48V 55Ah pack. Lead Crystal batteries have a greatly extended operating temperature
range and a longer life expectancy when compared to their Lead Acid equivalents.
For more detailed information, please see APPENDIX C – Hardware Datasheets or
consult the Lead Crystal Battery User Manual – 667/HB/47764/000.
Figure 4-3: 6CNFT-55 Lead Crystal Battery with Key Electrical Information
WARNING: Great care must be taken when handling batteries. Ensure all
relevant safety information has been has been read and understood before
commencing any process involving the Lead Crystal batteries. See the safety
information at the beginning of this document.

Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version 7 Page 20 of 76 Status
ISSUED
Last Editor Ore Oluwatudimu TS008468 Date 31/01/2017
Document
Name UPS Solution General Handbook Doc. No. 667/HB/47750/000
Copyright Siemens plc 2017 All Rights Reserved
5 Sizing the UPS Solution
5.1 Key Considerations
There are two key factors to consider when sizing a UPS Solution for any one traffic
intersection. These are the junction power requirements and the desired battery hold
up time.
A traffic intersection’s power requirements determine which of two Alpha FXM UPS units
is to be installed. The required battery support hold up time determines the number of
battery packs that will need to be installed within the UPS Solution. Extended hold up
periods will require the installation of a Battery Expansion Cabinet alongside the UPS
Cabinet.
Where cost or space is critical, a compromise between the junction power requirements
and required hold up time must be reached. Reducing the required hold up time
potentially decreases the number of battery packs to be installed. Reducing the junction
power requirements, and therefore the UPS system output, will allow each battery pack
to go further in terms of hold up time. Both options should be considered to meet
installation requirements.
Figure 5-1: Battery Hold up times at 20°C and 0°C
Table of contents
Other Siemens UPS manuals