Siko AP10S User manual

269/17
AP10S
Absolute / Electronic Position Indicator with
plug connector for magnetic sensor and RS485
/ SIKONETZ5 interface
User manual

AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 2 of 48
Table of contents
1General Informaton ................................................................................................... 5
1.1 Dokumentation ........................................................................................................5
1.2 Definitions ..............................................................................................................5
2Intended use............................................................................................................. 5
2.1 Switching on the supply voltage.................................................................................6
3Display and control keys ............................................................................................ 6
3.1 General ...................................................................................................................6
3.2 LCD display..............................................................................................................6
3.2.1 Extended display range ..........................................................................................7
3.3 LED display..............................................................................................................7
3.4 Keys .......................................................................................................................7
4Functional Description ............................................................................................... 7
4.1 Operating modes ......................................................................................................7
4.1.1 Position-bound operating modes.............................................................................8
4.1.1.1 Positioning.......................................................................................................8
4.1.1.2 Loop positioning .............................................................................................10
4.1.2 Alpha-numeric display operating mode...................................................................11
4.2 Battery buffering....................................................................................................12
4.3 Parameterization of the position indicator .................................................................12
4.3.1 Manual parameterization......................................................................................12
4.3.1.1 Starting parameterization .................................................................................12
4.3.1.2 Value input.....................................................................................................12
4.3.1.3 Value selection................................................................................................13
4.3.1.4 Adjustable parameters......................................................................................13
4.3.2 Parameterization via interface ..............................................................................13
4.4 Sensor ..................................................................................................................13
4.5 Warnings / Errors....................................................................................................14
4.5.1 Warnings ...........................................................................................................14
4.5.2 Errors ................................................................................................................14
4.6 System commands ..................................................................................................15
4.6.1 Alignment travel.................................................................................................15
4.6.2 Calibration .........................................................................................................15
4.6.3 Restore factory settings .......................................................................................16
4.6.4 Diagnosis...........................................................................................................16
5Overview of parameters............................................................................................ 16
6Communication via SIKONETZ 5 ................................................................................ 18
6.1 Interface...............................................................................................................18
6.2 Data exchange .......................................................................................................18
6.3 Telegram setup.......................................................................................................19
6.3.1 Command...........................................................................................................19

AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 3 of 48
6.3.2 Node address......................................................................................................19
6.3.3 Parameter address...............................................................................................19
6.3.4 Control word ......................................................................................................20
6.3.5 Status word........................................................................................................20
6.3.6 Data..................................................................................................................21
6.3.7 Check sum..........................................................................................................21
6.4 Synchronization .....................................................................................................22
6.5 Error telegram........................................................................................................22
6.5.1 SIKONETZ5 error codes.........................................................................................22
6.6 Communication errors .............................................................................................23
6.7 Communication monitoring ......................................................................................23
6.7.1 Bus-Timeout.......................................................................................................23
6.7.2 Programming interlock.........................................................................................23
6.8 Auto-ID.................................................................................................................24
6.9 Parameter description .............................................................................................26
6.9.1 00h: Node address...............................................................................................26
6.9.2 01h: Baud rate ...................................................................................................26
6.9.3 02h: Bus Timeout................................................................................................26
6.9.4 03h: Response parameter to a set point write access................................................27
6.9.5 04h: Keys enable time: Configuration start delay .....................................................27
6.9.6 05h: Key function enable1: Calibration enable.........................................................27
6.9.7 06h: LED flashing................................................................................................28
6.9.8 07h: LED3 (green right) .......................................................................................28
6.9.9 08h: LED2 (red left) ............................................................................................28
6.9.10 09h: LED1 (green left) .........................................................................................29
6.9.11 0Ah: Decimal places ............................................................................................29
6.9.12 0Bh: Display divisor (ADI) ....................................................................................29
6.9.13 0Ch: Direction indicators (CW, CCW).......................................................................30
6.9.14 0Dh: Display orientation ......................................................................................30
6.9.15 0Eh: Configuration programming mode...................................................................30
6.9.16 1Bh: Counting direction.......................................................................................31
6.9.17 1Ch: Resolution or measurement steps per revolution...............................................31
6.9.18 1Eh: Offset value ................................................................................................32
6.9.19 1Fh: Calibration value..........................................................................................32
6.9.20 20h: Target window1 (near field) ..........................................................................33
6.9.21 21h: Positioning type (loop type)..........................................................................33
6.9.22 22h: Loop length ................................................................................................33
6.9.23 28h: Operating mode...........................................................................................34
6.9.24 30h: Display in the 2nd row ...................................................................................34
6.9.25 31h: Target window2 (extended)...........................................................................35
6.9.26 32h: Target window2 visualization.........................................................................35
6.9.27 33h: Application of the display divisor (ADI application)..........................................35
6.9.28 34h: Formation of the differential value .................................................................36
6.9.29 35h: Key function enable2: Incremental measurement enable....................................36

AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 4 of 48
6.9.30 38h: Sensor type.................................................................................................36
6.9.31 39h: LED4 (red right)...........................................................................................37
6.9.32 3Ah: LCD backlight flashing..................................................................................37
6.9.33 3Bh: LCD backlight white .....................................................................................37
6.9.34 3Ch: LCD backlight red.........................................................................................38
6.9.35 3Dh: Key function enable3: Configuration enable via keyboard ..................................38
6.9.36 3Eh: Acknowledgement settings ............................................................................38
6.9.37 3Fh: Display factor ..............................................................................................39
6.9.38 63h: Battery voltage............................................................................................40
6.9.39 65h: Device identification ....................................................................................40
6.9.40 67h: Software version ..........................................................................................40
6.9.41 80h: Number of errors..........................................................................................41
6.9.42 81h until 8Ah: Errors ...........................................................................................41
6.9.43 96h: Input errors ................................................................................................41
6.9.44 A0h: System commands........................................................................................42
6.9.45 A7h: Calibration..................................................................................................42
6.9.46 A8h: Programming mode ......................................................................................43
6.9.47 AAh: Freeze actual value ......................................................................................43
6.9.48 C3h: Start sensor alignment..................................................................................43
6.9.49 C5h: ADC values of the sensor...............................................................................44
6.9.50 CAh: Bus protocol ...............................................................................................44
6.9.51 CFh: Period counter .............................................................................................44
6.9.52 D0h: Response delay............................................................................................45
6.9.53 D2h: Auto-ID assignment .....................................................................................45
6.9.54 FAh: Status word.................................................................................................45
6.9.55 FBh: Set point1 ..................................................................................................46
6.9.56 FCh: Differential value .........................................................................................46
6.9.57 FDh: Error telegram .............................................................................................46
6.9.58 FEh: Position value..............................................................................................47
6.9.59 FFh: Set point2...................................................................................................47
7Communication via Service Standard Protocol ............................................................ 47
7.1 General .................................................................................................................47
7.2 Error number encoding ............................................................................................48
7.3 Service protocol commands list.................................................................................48

General Informaton
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 5 of 48
1General Informaton
1.1 Dokumentation
The following documents describe this product:
The data sheet describes the technical data, the dimensions, the pin assignments, the
accessories and the order key.
The installation instructions describe the mechanical and electrical installation including
all safety-relevant requirements and the associated technical specification.
The user manual for commissioning and integrating the position indicator into a fieldbus
syste
These documents can also be downloaded at http://www.siko-global.com/p/ap10s.
Additional information and support for this device can also be found there.
1.2 Definitions
If not explicitly indicated otherwise, decimal values are given as figures without addition (e.
g. 1234), binary values are labeled with b (e. g. 1011b), hexadecimal values are identified by
h (e. g. 280h) after the figures.
2Intended use
The device is an absolute position indicator with a plug-in connection for MS500H magnetic
sensor for direct linear distance measurement (combined with MB500 magnetic tape) or a
supported GS04 magnetic sensor for direct shaft mounting. Actual and target values are
indicated via the backlit two-row LC display. A direction indicator (arrow) is blended in if the
actual value deviates from the target value including the adjustable target window. The
direction of the arrow indicates the direction of shaft movement necessary to reach the
target. Additionally, various visualization tasks can be realized by means of two bi-color LEDs.
The device parameters can be adjusted by means of 3 keys. You can change the set point,
output the position value and adjust all device parameters via the integrated bus interface.
Scanning is magnetically-incremental. In the currentless state, scanning and saving of
changes of the position value are battery-supported.
The state of charge of the replaceable battery is monitored and signified.
If no sensor is connected or the MS500H sensor lifted off the tape, an error will be detected
and the position value displayed red with a flashing "Error" message. This condition survives a
power failure. The error must be remedied by way of calibration after checking the sensor
connection or sensor position, respectively.
Display and interface are active with external power supply only.

Display and control keys
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 6 of 48
2.1 Switching on the supply voltage
The AP10S will be initialized after switching on the supply voltage. A display test is executed
during initialization, the LEDs are lighted consecutively and the configutation parameters are
loaded from the non-volative memory into the RAM of the controller.
With the display still unconfigured all parameters are set to their default values. See to it that
the bus will be connected only after correct adjustment of baud rate and ID (see chapter 4.3:
Parameterization of the position indicator and 6.8: Auto-ID). The AP10S functions with the
data last parameterized.
AP10S is in the normal operating state. According to the requirements of the application, the
display can be parameterized via the SIKONETZ5 interface in this state.
3Display and control keys
3.1 General
The position indicator has a two-line display with special characters and three control keys.
The keys serve for position indicator parameterization and control. Two LEDs (1) serve for
monitoring positioning.
Fig. 1: Control elements
3.2 LCD display
The display range is limited to -19999 … 99999. Values outside this range
are displayed with "".
With supply voltage applied to the position indicator with factory settings, the actual value
will be displayed in the 1st row and the set point in the 2nd row. If there is no valid set point,
"---" will be displayed in the 2nd row. The values displayed are determined by the operating
mode.
Direction indicators (arrows) support positioning.
The battery symbol is shown with a critical or insufficient battery status.
With incremental measurement function activated, the incremental measurement symbol
is shown.
LED1

Functional Description
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 7 of 48
If battery voltage drops to a critical value, the battery symbol on the display will flash. If it
falls below the minimum value, the symbol will glow permanently.
Errors are signified by red characters.
3.2.1 Extended display range
Values up to -999999 can be displayed by means of the control word. If the relevant bit has
been set and the value to be displayed is between -199999 and -999999, then the negative
sign and the digit of the highest order will flash alternately. If the value range drops below -
999999, "" will be displayed.
3.3 LED display
In its basic state (factory setting) the LED display has different meanings depending on the
operating mode (see chapter 4.1: Operating modes).
With the basic function of the LEDs inactivated, every LED can be controlled independently via
the control word (see chapters 6.9.8 to 6.9.10 and 6.9.31: LEDs and chapter 6.3.4: Control
word).
3.4 Keys
Pressing the key enables or disables the incremental measurement function. With the
Auto-ID function, the new ID is adopted by actuating this key (see chapter 6.8: Auto-ID).
Pressing the key starts calibration (see chapter 4.6.2: Calibration) and acknowledges a
pending error (see chapter 4.5.2: Errors).
Pressing the key starts the parameterization mode (see chapter 4.3: Parameterization of
the position indicator).
4Functional Description
4.1 Operating modes
The following position-dependent operating modes are differentiated: Absolute Position,
Differential Value, Modulo and the position-independent operating mode Alpha-numeric
Display.
Operating
mode
Absolute position
Differential
value
Modulo
Alpha-numeric
Display
Line 1
Actual position
Actual position
Actual position
Set point1
Line 2
Set point2
Differential value
Set point2
Set point2
Table 1: Display with different operating modes

Functional Description
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 8 of 48
Absolute position:
Linear absolute position values are displayed.
Differential value display:
With factory setting: Differential value = actual position - set point2
Modulo display:
Position values ranging from 0° to 360° are displayed.
Using the parameter 0Ah: Decimal places the resolution and the modulo point of the
displayed values are set.
Decimal places
Display resolution
Value range
0
1°
0°…360°
1
1/10°
0.0°…360.0°
2
1/100°
0.00°…360.00°
3
1/1000°
0.000°…360.000°
4
1/10000°
0.0000°…360.0000°
Table 2: Modulo display
Alpha-numeric display:
Both rows can be written freely. Set point1 is received via the SIKONETZ5 parameter FBh "set
point1", set point2 via parameter FFh "set point2". The data identifier must be correctly set in
the relevant control word. The data identifier differentiates whether the data is interpreted
and displayed as figures or alpha-numeric characters (ASCII) (see chapter 6.3.4: Control
word).
4.1.1 Position-bound operating modes
4.1.1.1 Positioning
(see chapter 4.1.1.2: Loop positioning)
Arrows: (see parameter 0Ch: Direction indicators (CW, CCW))
Arrows are displayed to support the user with positioning as long as the current actual
position value is outside (see parameter 20h: Target window1 (near field)) target window1.
The direction of the arrow indicates the direction of shaft rotation in order to arrive at the set
point.
LED-Anzeige: (siehe z. B. Parameter 09h: LED1 (green left))
With factory setting, the LED glows green as long as the actual position is within the
programmed window1. When leaving target window1, the LED glows red. The sensor must be
adjusted in the direction of the glowing LED in order to arrive at the set point2. The red
glowing LED on the right means: clockwise (cw) rotation required. Red glowing LED on the
left: counter-clockwise (ccw) rotation required.

Functional Description
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 9 of 48
An additional target window (target window2) and an associated visualization can also be
configured (see parameter 31h: Target window2 (extended)).
With factory settings, the LED display has the following meaning:
Operating state
LED
Status
Meaning
There is no valid
set point2.
both
off
Positioning disabled.
There is a valid set
point2.
LED left
off
Target window not reached!
The sensor must be moved in positive counting
direction in order to reach the target.
red
Target window not reached!
The sensor must be moved in negative counting
direction in order to reach the target.
green
Target window reached
LED right
off
Target window not reached!
The sensor must be moved in negative counting
direction in order to reach the target.
red
Target window not reached!
The sensor must be moved in positive counting
direction in order to reach the target.
green
Target window reached
Table 3: LED display
Control word (see chapter 6.3.4: Control word):
The set point is not displayed and positioning not monitored unless the set point2 is marked
as valid in the control word.
Status word (see chapter 6.3.5: Status word):
Upon reaching target window1, the static and dynamic target-window-reached bits are set in
the status word. The dynamic bit is deleted when leaving target window1. The user must
acknowledge the static bit.
Example Position monitoring:
Parameterization: Factory setting
Additionally: Set point2 = 100
Fig. 2: Positioning monitoring
100
+
-
Target
window1
95
105
LED left
Positioning monitoring
LED right

Functional Description
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 10 of 48
Example of position monitoring with additionally activated target window2 parameter:
Parameterization: Factory setting
Additionally: Target window 2 = 15
Visualization target window 2 = 1
Set point = 100
Fig. 3: Positioning monitoring with target window2
4.1.1.2 Loop positioning
Target window1 is also applied to the loop length.
If the position indicator is operated on a spindle or an additional gear, the spindle or external
gear backlash can be compensated by means of loop positioning. Therefore, movement
towards the set point is always in the same direction. This direction of approach can be
defined.
Example:
The direction from which every target position shall be driven to is positive.
Case 1 the new position is greater than actual position:
Direct travel to the target position.
Case 2 the new position is smaller than actual position:
The position indicator's arrows show that the set point is to be overrun by the loop length.
Afterwards, the set point is approached in positive direction.
+
-
Target
window1
Target window2
LED left
Positioning monitoring
85
115
LED right
100
95
105

Functional Description
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 11 of 48
Fig. 4: Positioning Loop+
4.1.2 Alpha-numeric display operating mode
Two 6-digit set points can be displayed in this operating mode. With factory settings, the set
points are acknowledged by pressing the asterisk key (see chapter 3.4: Keys).
LCD display:
In the absence of a valid set point, the 1st row is displayed empty (blank). "---" appears in
the 2nd row.
A valid set point is displayed flashing until its receipt is acknowledged.
LED display:
With factory settings, the LED display works according to the following table.
Operating state
LED
Status
Meaning
There is no valid set
point.
both
off
There is a valid set
point.
LED left
red
Set point1 not acknowledged
green
Set point1 acknowledged
LED right
red
Set point2 not acknowledged
green
Set point2 acknowledged
Table 4: LED display in the alpha-numeric display operating mode
Control word:
In the control word, the relevant type (number or character string) and the validity of the set
point is transmitted to the display. As an additional option, the set point can be
acknowledged via the control word.
Status word:
Type, validity and acknowledgement status of the set points are fed back in the status word.
Set point
+
-
Positioning in positive
direction
Positioning in negative
direction
Positioning: loop +
Loop length
Target window1

Functional Description
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 12 of 48
4.2 Battery buffering
The battery makes possible the detection of currentless displacement. Battery life is approx. 5
years depending on the duration of battery operation (including storage) and frequency of
currentless adjustments. Battery voltage is checked at intervals of approx. 5 min. If battery
voltage drops below a specified value, the battery symbol will blink on the display. If
the battery voltage continues to drop, will be displayed permanently. The battery
should be replaced within approx. three months after the first appearance of the battery
symbol. The battery can be replaced by the SIKO distribution partners or at the SIKO main
factory. For battery replacement it is mandatory to follow the instructions of the installation
instructions.
Status word:
The charge status of the battery is signified in the status word. Bit 11 is set when the
charging voltage is critical and an error is signified with the additional bit 7 set when the
battery is empty.
4.3 Parameterization of the position indicator
The position indicator can be fully parameterized via the bus interface. You can configure
manually via keyboard the most significant bus parameters (node address, baud rate, protocol,
bus timeout and reponse delay time).
4.3.1 Manual parameterization
4.3.1.1 Starting parameterization
After applying supply voltage and completion of initialization, the position indicator is on the
uppermost level of the menu structure (default/Factory settings).
By actuating the key, the set node address and baud rate is displayed. Parameterization
starts if it is actuated for the duration of the enable time (see parameter 04h: Keys enable
time: Configuration start delay and 3Dh: Key function enable3: Configuration enable via
keyboard).
4.3.1.2 Value input
Enter values via the key and the key. Confirm values entered by pressing the key.
- decimal place selection key
- value input key

Functional Description
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 13 of 48
4.3.1.3 Value selection
For some parameters you can select values from a list.
Direct value input is not possible there.
Pressing the key, the value can be selected from the list. By pressing the key, the
selection is confirmed.
4.3.1.4 Adjustable parameters
The following parameters can be adjusted.
Display
Parameter
Options
ID
Node-ID
1 … 127
KBAUD
Baud rate
19.2 kbaud
57.6 kbaud
115.2 kbaud
Protcl
Protocol
SIKONETZ5
Service-standard
BUS TO
Bus-Timeout
0 … 20
Inhibt
Response delay time
0 … 10
CODE
System commands
Reset factory settings (see chapter 4.6.3)
Start diagnosis (see chapter 4.6.4)
Table 5: Manually adjustable parameters
4.3.2 Parameterization via interface
The position indicator can be completely parameterized in the RS485-SIKONETZ5 interface
(see chapter 6: Communication via SIKONETZ 5).
4.4 Sensor
Alignment travel is required if a new sensor is connected (see chapter 4.6.1:
Alignment travel).
Mounting of the sensors as well as installation of the sensor cable is explained in the
documentation pertaining to the sensor MS500H or GS04. With supply voltage switched on,
the display monitors the connected sensor. If no sensor is connected or if the sensor is lifted
from the tape (MS500H), an error will be detected and the position value displayed red with
flashing "Error". This status persists even with power supply failure. The error must be
corrected after checking the sensor connection or sensor position with calibration (see
chapter 3.4: Keys and chapter 4.6.2: Calibration). If both battery supply and power supply fail
simultaneously (e. g. during a battery change), the absolute position value can get lost. For
making the measuring system work again, calibration is required (see chapter 4.5.2: Errors and
4.6.2: Calibration).

Functional Description
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 14 of 48
4.5 Warnings / Errors
4.5.1 Warnings
Warnings do not influence the acquisition of the absolute position value.
Warnings are deleted after removing the cause.
Possible warnings:
Battery voltage for absolute position detection is below limit immediately exchange
battery!
This warning is displayed with a blinking battery symbol . Warnings are issued through
the interface via the status word (see chapter 6.3.5:Status word,and chapter 4.6.4:
Diagnosis).
Display
Bit assignment in the status word
Error
blinking
11
Low battery voltage
4.5.2 Errors
Errors are signified via the display (written in red) and via the interface.
The cause of error must be removed to enable resumption of normal operation (see Table 7:
Corrective actions). Afterwards you can acknowledge or delete the error message by pressing
the key or via the interface (see chapter 6.3.4: Control word).
(For signaling see chapter 6.3.5:Status word and chapter 4.6.4: Diagnosis)
Display
Error code
SIKONETZ5
Bit assignment in
the status word
Error
permanent
0006h
11+7
Low battery voltage (empty)
SENBND
000Fh
12+7
Tape-sensor gap exceeded
noSENS
001Ah
12+7
No sensor connected
SPEED
0019h
12+7
Travel speed exceeded
CS bUS
0080h
7
Checksum SIKONETZ5
to bUS
0081h
7
Timeout SIKONETZ5
Table 6: Error messages
Display
Error
Possible effect
Corrective actions
permanent
Battery empty
Position value not
reliable
Battery change +
calibration
SENBND
Tape-sensor gap
exceeded
Position value not
reliable
Check sensor position +
calibration
Alignment travel
executed?

Functional Description
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 15 of 48
Display
Error
Possible effect
Corrective actions
noSENS
No sensor connected
Position value not
reliable
Check sensor +
calibration
Alignment travel
executed?
SPEED
Admissible travel speed
exceeded (see
installation instruction)
Error may also occur
during alignment travel.
Position value not
reliable
Decelerate travel speed
+ calibration
Alignment travel
executed?
Table 7: Corrective actions
4.6 System commands
4.6.1 Alignment travel
The AP10S is fully functional as delivered. To adjust the display to the connected sensor and
to achieve optimum measuring accuracy, alignment travel must be carried out whenever a
new/different sensor is connected to the AP10S. For calibration, the sensor must have been
mounted correctly (see documentation MS500H or GS04).
1. By entering the CODE 000100 or the SIKONETZ5 command "Encoder software alignment"
AP10S is set to the alignment mode (see chapter 4.3.1: Manual parameterization and
6.9.48: C3h: Start sensor alignment).
Display: 1st line. "ADJUST"
2nd line. "100" this value may vary by ±1.
2. When connecting sensor MS500H, it must be moved by a few millimeters in the direction
of the cable outlet (speed <1 cm/s).
When connecting sensor GS04, the shaft must be rotated clockwise by a few millimeters
(speed <<1 U/min).
In the lower line, the value will change in positive direction up to "103".
3. The alignment process will be completed when this value is finally exceeded. AP10S has
returned to normal operation and shows the corresponding display. If values above 103
are displayed during alignment, then travel speed must be slowed down during alignment.
4. It is not unusual that the position value cannot be displayed immediately after alignment
travel and "FULL" is displayed instead of the value. The display should be calibrated in
this case (see chapter 4.6.2: Calibration).
4.6.2 Calibration
Two steps are required for executing calibration:
1. Write calibration value (see object 1Fh: Calibration value)
2. Execute calibration (reset) (see chapter 3.4: Keys or object A7h: Calibration)
Since the measuring system is an absolute system, calibration is necessary only once with
commissioning. With calibration, the calibration value is adopted for calculation of the
position value. The following equation is applied in case of calibration:

Overview of parameters
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 16 of 48
Position value = 0 + calibration value + offset value
Calibration value (see object 1Fh: Calibration value)
Offset value (see object 1Eh: Offset value)
4.6.3 Restore factory settings
There are various options for restoring the factory settings of the device:
Access
Coding
Factory settings are restored
Manuell
11100
all parameters
11102
all except bus parameters
11105
only bus parameters
SIKONETZ5
(see parameter A0h:
System commands)
A0h
1
all parameters
2
all except bus parameters
5
only bus parameters
Table 8: Access to factory settings
4.6.4 Diagnosis
To receive a list of device errors that occurred switch the device to the diagnosis mode. Enter
CODE "200000" in parameterization (see chapter 4.3.1: Manual parameterization) and confirm
by pressing the key. Any errors occurring are output indicating the error number and total
of occurrences in the upper row. The type of error is shown in the lower row. Error number 1
contains the latest error. The oldest error is output with the highest error number.
5Overview of parameters
Name
Description
see
page
00h: Node address
Node address
26
01h: Baud rate
Baud rate of the RS485 interface
26
02h: Bus Timeout
Indication of bus timeout in x100 ms
26
03h: Response parameter to a set
point write access
Defines the response to the command
"Write set point"
27
04h: Keys enable time:
Configuration start delay
Period of key actuation in order to start
configuration.
27
05h: Key function enable1:
Calibration enable
Enable calibration
27
06h: LED flashing
All LEDs flashing
28
07h: LED3 (green right)
LED green right (LED3)
28
08h: LED2 (red left)
LED red left (LED2)
28
09h: LED1 (green left)
LED green left (LED1)
29
0Ah: Decimal places
Number of decimal places
29

Overview of parameters
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 17 of 48
Name
Description
see
page
0Bh: Display divisor (ADI)
ADI display divisor
29
0Ch: Direction indicators (CW, CCW)
Visualization of direction indicators
30
0Dh: Display orientation
Display orientation
30
0Eh: Configuration programming
mode
Basic setting of programming interlock
30
1Bh: Counting direction
Counting direction
31
1Ch: Resolution or measurement
steps per revolution
Resolution of the measuring system
31
1Eh: Offset value
Offset value
32
1Fh: Calibration value
Calibration value
32
20h: Target window1 (near field)
The set point has been reached when the
actual value is within the target window1
33
21h: Positioning type (loop type)
Travel towards set point in this direction
33
22h: Loop length
Loop length
33
28h: Operating mode
Operating mode
34
30h: Display in the 2nd row
Controls the display of the 2nd row of the
display
34
31h: Target window2 (extended)
Extended target window for easier positioning
35
32h: Target window2 visualization
Visualization of target window2
35
33h: Application of the display
divisor (ADI application)
ADI application
35
34h: Formation of the differential
value
Formation of the differential value
36
35h: Key function enable2:
Incremental measurement enable
Incremental measurement enable
36
38h: Sensor type
Selection of the sensor type
36
39h: LED4 (red right)
LED red right (LED4)
37
3Ah: LCD backlight flashing
Flashing LCD backlight
37
3Bh: LCD backlight white
LCD backlight white
37
3Ch: LCD backlight red
LCD backlight red
38
3Dh: Key function enable3:
Configuration enable via keyboard
Configuration enable
38
3Eh: Acknowledgement settings
Acknowledgment settings (alpha-numeric
display)
38
3Fh: Display factor
Display factor (inch indication)
39
63h: Battery voltage
Battery state of charge
39
65h: Device identification
SIKONETZ5 device identification (AP10S = 9)
40
67h: Software version
Software version
40
80h: Number of errors
Number of error incidents
41
81h until 8Ah: Errors
Error list
41
96h: Input errors
Input error list
41
A0h: System commands
Various system commands
42
A7h: Calibration
Starting calibration
42

Communication via SIKONETZ 5
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 18 of 48
Name
Description
see
page
A8h: Programming mode
Programming disable
43
AAh: Freeze actual value
Freeze position value
43
C3h: Start sensor alignment
Execute alignment
43
C5h: ADC values of the sensor
Hardware analysis
44
CAh: Bus protocol
Setting of the communication protocol
44
CFh: Period counter
Hardware analysis
44
D0h: Response delay
Delay until a SIKONETZ5 bus telegram is
answered.
45
D2h: Auto-ID assignment
Automated node address assignment
45
FAh: Status word
Device status
45
FBh: Set point1
Set point1 (alpha-numeric display)
46
FCh: Differential value
Deviation between actual and target positions
46
FDh: Error telegram
Error telegram
46
FEh: Position value
Actual position
47
FFh: Set point2
Target position
47
Table 9: Parameter description
6Communication via SIKONETZ 5
6.1 Interface
RS485 interface
Available baud rates: 19.2 kBit / 57.6 kBit (factory setting) / 115.2 kBit
No parity, 8 data bits, 1 stop bit, no handshake
6.2 Data exchange
The protocol functions according to the master –slave principle.
The position indicator acts as a slave. Every instance of communication must be initiated by
the master. When the master has sent a command telegram, the slave sends a reply telegram.
Broadcast commands are an exception, they remain always unanswered by the slave.
The protocol is optimized for cyclical data exchange. The relevant data such as set point and
actual value as well as control and status words can be transferred between master and slave
by a single telegram exchange.
The parameter to be returned by the slave as a reply to the master's Write set point command
can be defined via the "Write set point reply parameter".

Communication via SIKONETZ 5
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 19 of 48
6.3 Telegram setup
Control word (CW), status word (SW) and data are transferred in the Big-Endian format.
1stbyte
2ndbyte
3rdbyte
4thbyte
5thbyte
6thbyte
7thbyte
8thbyte
9thbyte
10thbyte
Command
Node
address
Parameter
address
high
Byte
low
Byte
MSB
LSB
Check
sum
CW
Data
Table 10: Command telegram (from master)
1stbyte
2ndbyte
3rdbyte
4thbyte
5thbyte
6thbyte
7thbyte
8thbyte
9thbyte
10thbyte
Command
Node
address
Parameter
address
high
Byte
low
Byte
MSB
LSB
Check
sum
SW
Data
Table 11: Reply telegram (from slave)
6.3.1 Command
The following access types are provided by SIKONETZ5.
Access code
Meaning
Description
00h
read
The master requests the addressed slave to output the
relevant value in a response telegram.
01h
write
The master requests the addressed slave to accept the value
transferred in the same telegram.
02h
broadcast
The master requests all connected slaves to execute the
command transferred in the same telegram.
6.3.2 Node address
The device address can be freely set in the range of 0 to 127. The delivered devices are preset
to node address 31 ex works and must be reset to the desired address to enable their
operation with multiple slaves on the SIKONETZ5 fieldbus (see parameter 00h: Node address
and chapter 6.8: Auto-ID).
Each address can be assigned in the fieldbus only once!
6.3.3 Parameter address
A distinct address is assigned to every parameter (e. g. calibration value) or functional value
(e. g. set point) (see chapter 6.9: Parameter description).

Communication via SIKONETZ 5
AP10S Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 20 of 48
6.3.4 Control word
The control word consists of 16 bits.
Control word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB High Byte
Low Byte LSB
The following table lists the designations of the individual bits of the control word and their
meanings.
Bit
Meaning
Value = 0
Value = 1
0
reserved
ever 0
-
1
reserved
ever 0
-
2
Validity of set point1
invalid
valid
3
Display range
standard
extended
4
Acknowledgment target window1 static
not acknowledged
acknowledged
5
Error
not acknowledged
acknowledged
6
With "Display" operating mode:
Acknowledgement of set point2
not acknowledged
acknowledged
7
With "Display" operating mode:
Data identifier
number
ASCII
8
reserved
ever 0
-
9
Validity of set point2
invalid
valid
10
With "Display" operating mode:
Acknowledgement of set point1
not acknowledged
acknowledged
11
LED1 green left
Off
On
12
LED3 green right
Off
On
13
LED4 red right
Off
On
14
LED2 red left
Off
On
15
LED blinking
Off
On
Table 12: Control word
6.3.5 Status word
The status word indicates the current status of AP10S. It consists of 16 bits.
Status word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB High Byte
Low Byte LSB
The following table lists the designations of the individual bits of the status word and their
meanings.
Bit
Meaning
Value = 0
Value = 1
0
Direction indication CW
Off
On
1
Direction indication CCW
Off
On
2
Validity set point1
invalid
valid
Other manuals for AP10S
2
Table of contents
Other Siko Touch Panel manuals