852 67 15 2022
-
PHC-3
PARAMETERS - 03 Cooling Pump
No. Name/Value Description
0301 PUMP TYPE Defi nes the cooling pump type
NONE No cooling pump is connected
D-OUT 4 BLUE HARNESS
(default)
Cooling pump is connected to Digital Output 4 on the blue harness. See also DIGITAL OUTPUTS parameter
for more information
HYDRAULIC GREY
HARNESS
Hydraulic cooling pump on the grey harness
ELECTRIC ECI Electric ECI cooling pump
CC MODULE Cooling Control Module
The CC Module is an external enclosed unit that controls one AC pump and one DC pump. The AC pump is
prioritized when AC power-pack is running, in other operating states the 24V DC pump is prioritized. If one
pump fails, the system will try to use the second pump.
0302 PUMP MODE Defi nes how the cooling pump are operated
DEACTIVATED Cooling pump will not be activated (used if cooling is provided by external system)
ALWAYS ON Cooling pump is activated and always running
TEMP CONTROLLED
(default)
Cooling pump is activated at 45°C (113°F) and deactivated at 40°C (104°F) if system use temperature
sensor. If system use temperature switches, cooling is controlled by switch state.
0303 ECI PUMP SPEED Sets ELECTRIC ECI pump speed if selected as PUMP TYPE
800rpm – 1600rpm
(default 1400rpm)
Speed in steps of 100rpm.
0304 POWER SAVE Cooling pump power save function.
DEACTIVATED POWER SAVE is deactivated and cooling pump will act accordingly to PUMP MODE setting (parameter
0302).
ACTIVATED (default) Cooling pump will go into power save mode and stop cooling pump and set selected output to 0V when
there is no system pressure and power-pack is inactive (VFD not running) for more than 10 seconds.
When power save mode is not triggered the cooling pump will act accordingly to PUMP MODE setting
(parameter 0302).
0305 ECI TRIM FUNCTION ECI Cooling pump trim function.
Cooling pump trim function is to run the cooling pump for 30 on regular basis to reduce the risk of corrosion,
growing and sticking seal.
DEACTIVATED ECI Cooling pump trim function is deactivated
ACTIVATED (default) Cooling pump starts:
• 60 seconds after PHC-3 has been powered
• every time system- or stabilizer-pressure is applied
• every 6 days if PHC-3 has continuous power
0380 ECI FIRMWARE Shows the ECI cooling pump fi rmware version. This is read only
VERSION 1.5.0 The Version number is requested from the ECI pump
NA Not Available, ECI pump is not connected
0381 CCM FIRMWARE Shows the CCM cooling module fi rmware version. This is read only
VERSION 1.00 Version number is requested from the CC Module
NA Not Available, CC Module is not connected
Menu - Parameters MC_0201
4.3
PARAMETERS - 05 Digital Outputs
No. Name/Value Description
0501
0502
0503
0504
0505
0506
D-OUTPUT 1
D-OUTPUT 2
D-OUTPUT 3
D-OUTPUT 4
D-OUTPUT 5
D-OUTPUT 6
Sets a function for the selected digital output. Any function can be set to any digital output.
If the number in front of the value/function name is negative (like -1 BOW CROSSOVER) then the output is
inverted.
0-NOT IN USE (default) Output is not in use and set to 0V
-1/1-BOW CROSSOVER Output is activated when input thrust from bow joystick is more than 5%. Remember to set RAMP
DECREASE time to preferred 3000ms at parameter 2005.
This function is automatically set to D-OUTPUT 1 when parameter 2007 is set to DO-1 BOW CROSSOVER.
-2/2-STERN CROSSOVER Output is activated when input thrust from stern joystick is more than 5%. Remember to set RAMP
DECREASE time to preferred 3000ms at parameter 2105.
This function is automatically set to D-OUTPUT 2 when parameter 2107 is set to DO-2 STERN CROSSOVER.
-3/3-COOLING PUMP Output is activated according to parameter 0302 PUMP MODE
This function is automatically set to D-OUTPUT 4 when parameter 0301 is set to D-OUT 4 BLUE HARNESS.
-4/4- BOW THRUST ACTIVE Output is activated when bow thruster is running.
-5/5-STERN THRUST
ACTIVE
Output is activated when stern thruster is running.
-6/6-ANY THRUST ACTIVE Output is activated when bow or stern thruster is running.
-7/7-THRUSTER ENABLED Output is activated when any joystick panel is ON. This requires PHC-3 FW V1.009 and PJC222/221 FW
V2.024 or newer
-8/8-STAB.PTO P.UNLOAD Output is activated when stabilizer is running from PTO pressure.
This function is used on nonstandard option systems (10 4450B-W-X02).
Enabling this function also require setting of parameter 1011-PTO ENGINE INSTANCE.
-9/9-LOW OIL LEVEL
ALARM
Output is active when there is a low oil level fault
-10/10-BOW CROSSOVER
WITH BREAK
10-NO Valve: Output is Low (0V) when PVG feed is ON and input thrust from bow joystick is less than 5%.
Rest of the time the output is High (+24V).
-10-NC Valve: Output is High (+24V) when PVG feed is ON and input thrust from bow joystick is less than
5%. Rest of the time the output is Low (0V).
Remember to set RAMP DECREASE time to preferred 3000ms at parameter 2005.
-11/11-STERN CROSSOVER
WITH BREAK
11-NO Valve: Output is Low (0V) when PVG feed is ON and input thrust from bow joystick is less than 5%.
Rest of the time the output is High (+24V).
-11-NC Valve: Output is High (+24V) when PVG feed is ON and input thrust from bow joystick is less than
5%. Rest of the time the output is Low (0V).
Remember to set RAMP DECREASE time to preferred 3000ms at parameter 2105.
Menu - Parameters MC_0201