DF46 – Installation Module
2
DF46 - ANALOG OUTPUTS MODULE
VOLTAGE / CURRENT
DF46 (1 Group of 4 Voltage/Current Analog Outputs)
Description
This module provides 4 pairs of analog outputs. Each pair is composed of one Current output and
one Voltage output. When one output is selected, the corresponding pair is selected simultaneously.
The current outputs can be configured individually on ranges 0-20 mA or 4-20 mA. For voltage
outputs the range is 0-5V, 1-5 V, ± 5 V, 0-10 V, 2-10 V or ± 10 V.
501/46 - 4 Analog Outputs 0-20mA, 4-20mA, 0-5V, 1-5V, 0-10V,±10V
PWR
PWR
GND
GND
I 0
V0
I 1
V1
I 2
V2
I 3
V3
1A
2A
3A
4A
5A
6A
7A
8A
9A
10A
1B
2B
3B
4B
5B
6B
7B
8B
9B
10B
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
1 G 8x Temperature In
smar
PWR
I 0
DF46
V0
I 1
V1
1 G 4x Analog Out
I 2
V2
I 3
V3
DipSwitche’s Configuration
When using Voltage Mode, make sure to configure the Group of Ranges via DipSwitches located
UP and Down inside the Box.
DipSwitch 1 - UP Side: Configure the Group of Ranges of Channel 0 (I0/V0)
DipSwitch 2 - UP Side: Configure the Group of Ranges of Channel 1 (I1/V1)
DipSwitch 1 - DOWN Side: Configure the Group of Ranges of Channel 2 (I2/V2)
DipSwitch 2 - DOWN Side: Configure the Group of Ranges of Channel 3 (I3/V3)
See under Technical Specifications (output range) the Group of Ranges.
Notes
In order to attend EMC standards, use shielded cables in signals inputs (ground the shield in the
panel only in one side of the cable) and cables less then 30 meters for power source inputs.
The scale for Analog Input and Output Modules is done using XD_SCALE parameter in AI and
AO blocks, respectively. When using MAI or MAO, it is assumed a default range, 4-20mA or 1-
5V without possibility to change. For MAI and MAO, input and output parameters are available in
percentage of default range.