How to order
Nil
N
Wiring specification
High flow rate type
3m lead wire with connector
Without lead wire
03
06
12
Flow rate range
150 to 3000l/min
300 to 6000l/min
600 to 12000l/min
Symbol
10
14
20
Port size
1
1 1/2
2
3000
6000
12000
Port
size Applicable
model
Flow rate (l/min) 28
29
68
69
Output specification
NPN open collector 1 output + Analog output (1 to 5V)
NPN open collector 1 output + Analog output (4 to 20mA)
PNP open collector 1 output + Analog output (1 to 5V)
PNP open collector 1 output + Analog output (4 to 20mA)
Nil
N
F
Port specification
Rc
NPT
G
PFA703H
PFA706H
PFA712H
Integrated
display type
Specifications
Note 1) For the type with unit switching function [The type without the unit switching function will have a fixed SI unit (l/min, or l, m³or m³x 10³).]
Note 2) The high flow rate type is with CE marking. However, the linearity with applied noise is ±5% F.S. or less.
Note 3) Switch output and accumulated pulse output selections are made by button operation.
Note 4) The analog output operates only for real-time flow rate, and does not operate for accumulated flow.
Note 5) Flow rate display can be switched between the basic condition of 0°C, 101.3kPa and the standard condition (ANR) of 20°C, 101.3kPa, 65% RH.
PFA703H
150 to 3000l/min
5l/min
PFA706H PFA712H
Model
Measured fluid
Detection type
Flow rate measurement range Note 5)
Minimum setting unit Note 5)
Operating pressure range
Withstand pressure
Pressure loss
Accumulated flow range
Operating temperature range
Linearity Note 2)
Repeatability
Pressure characteristics
Temperature characteristics
Output
specifications
Response time
Hysteresis
Power supply voltage
Current consumption
Withstand voltage
Insulation resistance
Noise resistance
Vibration resistance
Impact resistance
Weight
Enclosure
Port size (Rc, NPT, G)
Display units
Note 3)
Note 3)
Note 4)
Note 1)
1
Dry air
Heater type
300 to 6000l/min
l/min, CFM
l, m³, m³x 10³, ft³, ft³x 10³, ft³x 10⁶
0.1 to 1.5MPa
2.25MPa
20kPa (at maximum flow rate)
0 to 9,999,999,999l
0 to 50°C (with no condensation)
±1.5% F.S. or less (0.7MPa, at 20°C)
±1.0% F.S. or less (0.7MPa, at 20°C)
±1.5% F.S. or less (0.1 to 1.5MPa, based on 0.7MPa)
±2.0% F.S. or less (0 to 50°C, based on 25°C)
Output voltage: 1 to 5V, Load impedance: 100kΩor more
Output current: 4 to 20mA, Load impedance: 250kΩor more
1s or less
Hysteresis mode: Variable (can be set from 0), Window comparator mode: (can be set from 0 to 3% F.S.)
24VDC (ripple ±10% or less)
150mA or less
1000VAC for 1 min. between external terminal block and case
50MΩ(500VDC) between external terminal block and case
1000Vp-p, Pulse width 1µs, Rise time 1ns
10 to 500Hz at the smaller of amplitude 1.5mm or acceleration 98m/s²in X, Y, Z directions, 2 hours each
490m/s²in X, Y, Z directions, 3 times each
1.3kg (without lead wire)
Equivalent to IP65
1 1/2 2
Real-time flow rate
Accumulated flow
600 to 12000l/min
PFA7 H
Switch output
Analog output
Accumulated
pulse output
10l/min
Nil
MWith unit switching function
Fixed SI unit Note)
Unit specification
2.0kg (without lead wire)1.1kg (without lead wire)
NPN open collector
PNP open collector
Max. load current: 80mA, Max. applied voltage: 30V, Internal voltage drop: 1V or less (with load current of 80mA)
NPN or PNP open collector Flow rate per pulse: 100l/pulse, 10.0ft³/pulse
ON time per pulse: 50msec/pulse
Max. load current: 80mA, Internal voltage drop: 1.5V or less (with load current of 80mA)
Switching of switch output and cumulative pulse output is possible with NPN
or PNP open collector outputs.
Note) Fixed units:
Real-time flow rate: l/min
Accumulated flow: l, m³, m³x 10³