US PATENTED
120V AC Line in
(by others)
Smoke Detector
(by others)
Housing
Kevlar®
Cables
Flexible
Magnetic
Edge
DuraNet™
Screen
Assembly
Auxiliary Rail
Auxiliary Rail
Backer
Screen
Rewind Switch
(both sides of curtain)
Fail Safe Secure.
M200/M400
systems operate on a fail safe
basis, on loss of AC power the screen will deploy. There is a
deployment delay on power failure built into the system to
avoid nuisance deploys on brief power outage.
Battery Backup.
M400 units may be specified with an internal
battery backup. This feature is not available in M200 units.
Listed Releasing Device. The
M200/M400
features a
releasing device tested in accordance with the UL 864
standard by Intertek Laboratories.
Rewind Switch. The Smoke Guard system screen rewind
switch may be activated from both sides of the screen.
This feature allows elevator occupants to exit from the
elevator car using the interior (shaft side) of the switch. The
screen will then redeploy after egress, as long as the smoke
detector continues to be activated, providing continued
smoke protection for the elevator hoistway. In the event of
power outage, the vertical edge of the curtain can be pushed
away from the rail to allow passage with a force less than
15 lbs. as referenced by the ICC.
800.574.7474
I
smokeguard.com
SGSO-1 • Rev. 2 • COPYRIGHT 2020 SMOKE GUARD, INC.
System Operation.
Smoke Guard elevator systems
are designed to protect elevator openings and
shaft from vertical smoke migration. The system
will deploy when the smoke detector in the
elevator lobby goes into alarm (or on loss of power
to the unit). The system is not designed to deploy
on general alarm. As the lobby smoke detector
goes into alarm, the elevator will automatically
return to the recall floor. If an elevator occupant
were to encounter a deployed M200/M400, a
screen rewind switch located on both sides of the
screen will allow for egress. If smoke is still actively
being detected, the screen will then redeploy to
seal the opening. As power is restored, the screen
will automatically rewind into the housing.
Installation. All Smoke Guard units are installed
by factory trained and certified personnel. There
is minimal preparation work. Installation requires
a clear, plumb, unobstructed wall surface above
the hoistway door, 120v AC power and a smoke
detector.
Elevator Smoke Curtain
Models 200/400
Check for clearance/obstructions issues
on, above, and surrounding the elevator
opening (sprinklers, call buttons, HVAC, etc.)
Field verify elevator opening measurements
prior to ordering systems
Available 120 VAC circuit with 2 amp
capacity per unit
Fire alarm system has local auxiliary
contacts available
No auxiliary rails: elevator door frame
is ferromagnetic
Smoke Guard and Your Project