manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. socomec
  6. •
  7. Control Unit
  8. •
  9. socomec DIRIS Digiware U-30 User manual

socomec DIRIS Digiware U-30 User manual

This manual suits for next models

2

Other socomec Control Unit manuals

socomec DIRIS O-m User manual

socomec

socomec DIRIS O-m User manual

socomec DIRIS A40 User manual

socomec

socomec DIRIS A40 User manual

socomec DIRIS A41 User manual

socomec

socomec DIRIS A41 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Product startup C31-U30-I35-I35-I35 ADY.docx
Page 1/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
The purpose of this document is to explain the setup steps in "point to point" mode on a Diris Digiware
system:
1 DIGIWARE C-31 control interface
1 DIGIWARE U-30 voltage module (same steps as for U-10 and U-20)
3 DIGIWARE I-35 current modules (same steps as for I-30, I-31 and I-33)
Prerequisite hardware for using this guide:
- You must have the latest version of Easy Config, the setup software for these products
- You must have a PC equipped with USB ports and a micro USB cable
- You must be able to guarantee the implementation, connection and the power of the system to be
configured as shown in the first section.
We recommend that you first configure the U voltage module before the I modules on a
DIGIWARE bus.
Module U-30 must be placed on the DIGIWARE bus first, i.e. just after C-31 and just before
current modules I-xx
Product startup: DIGIWARE C-31 + U-30 + 3x I-35
Date: 26/09/2014
From: ADY
Verified by:
To: All
Copy to :
Product startup C31-U30-I35-I35-I35 ADY.docx
Page 2/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
1) Architecture to configure
Synthesis of the electrical and communication parameters:
Name Type Usage
nominal
current
Phase(s)
1C-31 / / / / / /
2U-30 6 / / / / / /
Cool Water Prod. 3-phases balanced 400V Air Con 60 A V1-V2-V3
/ Lights Basement 1-phase 230V Lighting 20 A V1
Heating Basement 1-phase 230V Heating 35 A V3
4I-35 n°2 8 / Other loads … … … … …
5I-35 n°3 9 / Other loads … … … … …
3P+N Network
(4 wires)
400 Volts
3
I-35 n°1
7
Electrical
Network
Type
Loads
TCP/IP Parameters
N°
Product
Type
Modbus
Address
Product startup C31-U30-I35-I35-I35 ADY.docx
Page 3/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
2) Checking the connection between a module and the PC via Easy Config
Connect the micro USB cable from the module you want to configure and the PC
Open Easy Config
Switch to the "Super User" profile in Easy Config (default password: sOcOmec)
Click "Get from device":
The module is automatically detected by Easy Config (if not, try disconnecting/reconnecting the cable and
click "Refresh USB devices").
Product startup C31-U30-I35-I35-I35 ADY.docx
Page 4/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
Click "Connect to device":
The example above shows how to connect a U-30 module to the PC with Easy Config. If you
connect a different module, its name is shown in Easy Config instead of "Diris Digiware U-30"
Product startup C31-U30-I35-I35-I35 ADY.docx
Page 5/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
3) Configuring module U-30 by architecture
Connect to module U-30 as shown in section 2.
On the "Product" tab, change the JBUS/MODBUS address so that each device on the bus DIGIWARE
has a unique address. Then click "Send to device":
The JBUS/MODBUS address is a single random digit between 1 and 247, attributed to an
included device
On the "Network" tab, configure the network type at the point where the voltage is measured with
voltage module U-30, as well as the nominal voltage of the measured network:
1P + N: Single-phase network
2P: Two-phase network
2P + N: Two-phase network + neutral conductor
3P: Three-phase network
3P + N: Three-phase network + neutral driver
The nominal voltage of the network is typically 400V for a three-phase or two-phase network
and 230V for single-phase network
Product startup C31-U30-I35-I35-I35 ADY.docx
Page 6/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
Example setup with one voltage measurement on a 4-wire network:
To view the network configuration automatically detected by the product, click "Refresh". Please
remember that this automatic detection only works if there is voltage on the network and if the
grounding plug is connected to module U-30.
Product startup C31-U30-I35-I35-I35 ADY.docx
Page 7/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
Apply the setup changes to the product by clicking "Final action" then "Send to device"
Make sure U-30 USB is selected in the list then click "Connect to device":
Product startup C31-U30-I35-I35-I35 ADY.docx
Page 8/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
By default, Easy Config only checks those settings that were changed. This avoids having to resend the
entire configuration to the device:
The U-30 module setup is applied to all I-xx current modules connected at the back of the same
DIGIWARE bus. With a unique voltage reading for all I-xx modules on the same DIGIWARE bus, this is
how it should be:
A warning message appears, showing that the operation completed successfully:
Product startup C31-U30-I35-I35-I35 ADY.docx
Page 9/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
4) Configuring the first I-35 module by architecture
Connect to the first I-35 module as shown in section 2.
On the "Product" tab, change the JBUS/MODBUS address so that each device on the bus DIGIWARE
has a unique address. Then click "Send to device":
The JBUS/MODBUS address is a single random digit between 1 and 247, attributed to an
included device
On the "Network" tab, check that module I-35 received all the network setup information sent by voltage
module U-30:
Product startup C31-U30-I35-I35-I35 ADY.docx
Page 10/14
MARKETING EE / TECHNICAL SUPPORT
PRODUCT STARTUP
On the "Loads" tab, make the following settings:
- The number of loads measured by module I-35
- For each load, the type of measured load
- For each load, the phase(s) on which the sensor(s) are connected
- For each sensor, you may need to adjust the direction of current in case of a wiring fault
The maximum number of loads for an I-3x current module is 3, because there are 3 sensor inputs
on this module.
The measured load type can be:
A single-phase load measured by 1 sensor (1P + N - 1CT)
A three-phase load without unbalanced neutral measured by 2 sensors (3P - 2CT), with the 3rd
current derived from a vector sum
A three-phase load with or without unbalanced neutral measured by 3 sensors (3P - 3CT or 3P +
N - 3CT)
A three-phase balanced load with or without neutral measured by 1 sensor (3P - 1CT or 3P + N -
1CT)
For a balanced load measured by a single sensor you can connect this sensor to any phase
The size of the sensor is always detected automatically and it is not possible to change it. The
only instance in which you will have to manually apply this value is if you are using an adjusting
sensor. In this case, you must send the rated current to the current transformer primary upstream
of the adjusting sensor.