socomec DIRIS A40 User manual

DIRIS A40/A41
ETHERNET®
Operating instructions
F GB D I NL E P

2DIRIS A40/A41 - Ref.: 536 181 B GB

3
DIRIS A40/A41 - Ref.: 536 181 B GB
PRELIMINARY OPERATIONS _________________________________________________________ 4
GENERAL INFORMATION_________________________________________________________ 4
INSTALLATION __________________________________________________________________________ 5
CONNECTION _____________________________________________________________________ 5
VISUAL DIAGNOSTIC _____________________________________________________________ 6
PROGRAMMING ________________________________________________________________________ 7
ETHERNET CONFIGURATION ON DIRIS A40/A41_______________________________ 7
IP ADDRESS _______________________________________________________________________ 8
MASK _____________________________________________________________________________11
GATEWAY _________________________________________________________________________11
DHCP _____________________________________________________________________________12
WEBSERVER _____________________________________________________________________13
ENVIRONMENTAL CONDITIONS AND TYPE OF TEST _________________________14
INTERFACE SPECIFICATIONS: SUPPLY ________________________________________14
RS485 _____________________________________________________________________________14
ETHERNET________________________________________________________________________14
COMMUNICATION_____________________________________________________________________15
A : NEW COMMUNICATION TABLE FROM 01/2009__________________________ 15
1 > TABLE C550 Hex : Main measurements allocated from current transformer
and voltage transformer values__________________________________________ 15
2 > TABLE C650 Hex : Energy monitoring _____________________________________ 16
3 > TABLE C750 Hex : Additional measurements allocated from current transformer
and voltage transformer values__________________________________________ 16
4 > TABLE C850 Hex : Main measurements not allocated from current transformer
and voltage transformer values__________________________________________ 17
5 > TABLE C900Hex : Temperature measurements ______________________________ 18
6 > TABLE C950Hex : Harmonics___________________________________________ 18
7>TABLEE000Hex:Primaryconguration___________________________________ 24
8>TABLEE110Hex:Ethernetconguration __________________________________ 24
9>TABLEE200Hex:Ethernetconguration __________________________________ 26
Contents
GB

DIRIS A40/A41 - RS485 - ETHERNET®
4DIRIS A40/A41 - Ref.: 536 181 B GB
PRELIMINARY OPERATIONS
•ETHERNET MODULE WITH MODBUS RTU
GATEWAY – Ref. 48250204:
> MODBUS master gateway with RS485 3-point link
with TCP.
> MODBUS TCP and MODBUS RTU protocols.
>WEB-serverforproductconguration,displaying
the values and the diagnostics.
The gateway in this version enables the module to be
used as a master gateway for a Jbus/Modbus network
onRS485withamaximumof246slaves.Todothis,
a Jbus/Modbus address other than 255 needs to be
congured.
For personnel and product safety please read the
contents of these operating instructions carefully
before connecting.
Check the following points as soon as you receive the
DIRIS A40/A41 package:
•thepackingisingoodcondition,
•theproducthasnotbeendamagedduringtransit,
•the product reference number conforms to your
order,
•thepackagecontainstheproductandtheoperating
instructions.
Functions
The optional Ethernet module is linked to the DIRIS A40/A41(ref.48250201,48250202,48250207,48251201,
48251202,4825U201,48250211,48250213,48250214)andenablesconnectionstobemadetoa10BaseT
or 100BaseT type network. It also enables the DIRIS measurement units to be used and monitored from a PC
or an API.
GENERAL INFORMATION
The module is available in 2 versions:
•ETHERNET MODULE – Ref. 48250203:
> Link to an RJ45 connection.
> MODBUS TCP or MODBUS RTU Protocol with TCP.
>WEB-serverforproductconguration,displayingthe
values and diagnostics.
TCP/IP
Ethernet
Module
DIRIS A40/41
@1
(maximum of 4 clients)
Client 1
PC
Client 2
API
(maximum of 4 clients)
TCP/IP
(RJ45)
MODBUS
(RS485)
Ethernet
Module
DIRIS A40/41
@1
Client 1
PC
Client 2
API
Module
RS485
DIRIS A40/41
@2
Module
RS485
DIRIS A40/41
@3
Maximum of 246 slaves

DIRIS A40/A41 - RS485 - ETHERNET®
5
DIRIS A40/A41 - Ref.: 536 181 B GB
GB
INSTALLATION
CONNECTION
4
Follow indications when connecting the termi-
nal. Switch on voltage supply.
The DIRIS A40/A41 must be switched off
DIRIS 342 A
1
DIRIS 343 A
2
Fix the module in one of the four positions.
DIRIS 347 A
3
ThemoduleisttedontothebackoftheDIRIS A40/A41 in one of the 4 positions provided.
DIRIS 347 A

DIRIS A40/A41 - RS485 - ETHERNET®
6DIRIS A40/A41 - Ref.: 536 181 B GB
VISUAL DIAGNOSTIC
INSTALLATION
LED Colour Status Description
SYS - NOT LIT No internal electrical supply
Firmware is re-initialising
Hardware is faulty
Yellow LIT Loadingphaseofthesoftware,
waiting to start
FLASHING AT 1Hz Error during the start-up phase
Green LIT Operating system functioning
COM Red NOT LIT No errors
FLASHING Not used
LIT Internal JBUS error
Green NOT LIT See red LED
FLASHING JBUS external error
LIT Noerror,fullyfunctional
Link Green NOT LIT No connection to the Ethernet network
LIT Ethernet Network connected
Activity Yellow FLASHING Sending/receiving Ethernet frames
>
LED indicators

DIRIS A40/A41 - RS485 -
ETHERNET®
7
DIRIS A40/A41 - Ref.: 536 181 B GB
GB
PROGRAMMING
ETHERNET CONFIGURATION ON DIRIS A40/A41
This involves setting up the IP parameters for the
DIRIS connected to the gateway
IP address (Rth Adr IP) :
[CLASS A].[CLASS B].[CLASS C].[CLASS D]
Subnet mask (Eth MASH) :
[CLASS A].[CLASS B].[CLASS C].[CLASS D]
Gateway (Eth GATE) :
[CLASS A].[CLASS B].[CLASS C].[CLASS D]
DHCP activation (Eth DHCP) : Yes/ No
The factory setting is:
• IP address: 192.168.1.1
• Subnet mask: 255.255.255.0
• Gateway: 0.0.0.0
• DHCP activation: NO
x 4
x 4
x 4
x 1

DIRIS A40/A41 - RS485 - ETHERNET®
8DIRIS A40/A41 - Ref.: 536 181 B GB
PROGRAMMING
ADRESSE IP :
>
For example: Programming the address 191.158.1.7
CLASS A = 191
x 1
x 3
x 1

DIRIS A40/A41 - RS485 -
ETHERNET®
9
DIRIS A40/A41 - Ref.: 536 181 B GB
GB
ADRESSE IP :
>
For example: Programming the address 191.158.1.7
CLASS D = 158
PROGRAMMING
x 2
x 1
x 1

DIRIS A40/A41 - RS485 - ETHERNET®
10 DIRIS A40/A41 - Ref.: 536 181 B GB
PROGRAMMING
ADRESSE IP :
>
For example: Programming the address 191.158.1.7
CLASS C = 1
x 6
>
For example: Programming the address 191.158.1.7
CLASS C = 7
x 3
x 3
x 1

DIRIS A40/A41 - RS485 -
ETHERNET®
11
DIRIS A40/A41 - Ref.: 536 181 B GB
GB
PROGRAMMING
MASQUE:
>
For example: 255.255.255.0
The principle is the same as for the IP address
x 4
x 4
GATEWAY:
>
For example: 0.0.0.0
The principle is the same as for the IP address

DIRIS A40/A41 - RS485 - ETHERNET®
12 DIRIS A40/A41 - Ref.: 536 181 B GB
PROGRAMMING
DHCP :
>
WARNING: The DHCP function is not recommended.
Contact your IT networks administrator.
x 1
x 1
x 1

DIRIS A40/A41 - RS485 -
ETHERNET®
13
DIRIS A40/A41 - Ref.: 536 181 B GB
GB
PROGRAMMING
WEBSERVER
>
The Webserver can be accessed by entering the
product’s IP address into your internet browser.
For example:
IP address of the DIRIS : 192.168.1.0
URL address: http://192.168.1.0/index.htm
The Web server makes the following available:
- The main DIRIS database parameters.
- The main instant and average meter readings.

DIRIS A40/A41 - RS485 - ETHERNET®
14 DIRIS A40/A41 - Ref.: 536 181 B GB
ENVIRONMENTAL CONDITIONS AND TYPE OF TEST
Description Standard Level
Electrostatic discharge IEC 61000-4-2 4 kV contact
8 kV air
Modulated A
electromagnetic radiation
IEC 61000-4-3 10V/m(80MHz–1GHz)
3V/m(1,4GHz–2GHz)
1V/m(2,0GHz–2,7GHz)
Magneticelds
frequency factor
IEC 61000-4-8 50 Hz / 60 Hz
30 A/m
Rapid transients in bursts IEC 61000-4-4 1 kV
Impulsewaves(lightning) IEC 61000-4-5 1 kV
Injection of HF current IEC 61000-4-6 150 KHz – 80 MHz
80%AM,1KHzsinusoidalwave
1,5x10E-3decade/s
3 V
>
Electromagnetic compatibility:
Operational temperature -25 to +70°C
Storage temperature -40 to +70°C
>
Environmental:
Supply voltage (from the DIRIS)+ 9 VDC
Consumption Between 1.3 and 1.7 W
INTERFACE SPECIFICATIONS: SUPPLY
Electricalspecication RJ45 Norme IEE
3-wire
Transmission speed 10MBits/s or 100MBits/s
Protocol Modbus/TCP or Jbus/Modbus
RTU with TCP
ETHERNET
Electricalspecication RS485 EIA
3-wire half duplex
Transmission speed 38,4kBit/s
Stop bit 2
Parity without
Maximum number of slaves 246
RS485
PROGRAMMING
UL-CSA APPROVAL
Standard UL 61010-1
CSA-C22.2 No. 61010-1
Certicate ULleNo:E257746

DIRIS A40/A41 - RS485 -
ETHERNET®
15
DIRIS A40/A41 - Ref.: 536 181 B GB
GB
COMMUNICATION
A : NEW COMMUNICATION TABLE FROM 01/2009
These new tables are available for all new Socomec products on sale from January 2009. The aim is to have common
tables for common values, irrespective of the Socomec product. We recommend that you use these new tables whe-
never possible for developing your applications.
1 > TABLE C550 Hex : Main measurements allocated from CT (current transformer) and VT (voltage
transformer) values
Decimal Hex. No. of Description Unit JBUS function
address address words available
50512 C550 2 hour meter 1/100 h 3
50514 C552 2 phase to phase voltage U12 V/100 3
50516 C554 2 phase to phase voltage U23 V/100 3
50518 C556 2 phase to phase voltage U31 V/100 3
50520 C558 2 phase to neutral voltage phase 1 V/100 3
50522 C55A 2 phase to neutral voltage phase 2 V/100 3
50524 C55C 2 phase to neutral voltage phase 3 V/100 3
50526 C55E 2 frequency Hz/100 3
50528 C560 2 phase current 1 mA 3
50530 C562 2 phase current 2 mA 3
50532 C564 2 phase current 3 mA 3
50534 C566 2 neutral current mA 3
50536 C568 2
Σ
active power +/- kW/100 3
50538 C56A 2
Σ
reactive power +/- kvar/100 3
50540 C56C 2
Σ
apparent power kVA/100 3
50542 C56E 2
Σ
powerfactor-:leadingand+:lagging 0,001 3
50544 C570 2 active power phase 1 +/- kW/100 3
50546 C572 2 active power phase 2 +/- kW/100 3
50548 C574 2 active power phase 3 +/- kW/100 3
50550 C576 2 reactive power phase 1 +/- kvar/100 3
50552 C578 2 reactive power phase 2 +/- kvar/100 3
50554 C57A 2 reactive power phase 3 +/- kvar/100 3
50556 C57C 2 apparent power phase 1 kVA/100 3
50558 C57E 2 apparent power phase 2 kVA/100 3
50560 C580 2 apparent power phase 3 kVA/100 3
50562 C582 2 powerfactorphase1-:leadingand+:lagging 0,001 3
50564 C584 2 powerfactorphase2-:leadingand+:lagging 0,001 3
50566 C586 2 powerfactorphase3-:leadingand+:lagging 0,001 3
50568 C588 2 Reserved for manufacturer - 3
50570 C58A 2 Reserved for manufacturer - 3
50572 C58C 2 Reserved for manufacturer - 3

DIRIS A40/A41 - RS485 - ETHERNET®
16 DIRIS A40/A41 - Ref.: 536 181 B GB
COMMUNICATION
A : NEW COMMUNICATION TABLE FROM 01/2009
2 > TABLE C650 Hex : Energy monitoring
Decimal Hex. No. of Description Unit JBUS function
address address words available
50768 C650 2 hour meter 1/100 h 3
50770 C652 2 Reserved for manufacturer - 3
50772 C654 2 Reserved for manufacturer - 3
50774 C656 2 Reserved for manufacturer - 3
50776 C658 2 Reserved for manufacturer - 3
50778 C65A 2 Reserved for manufacturer - 3
50770 C652 2 active energy + kWh 3
50772 C654 2 reactive energy + kvarh 3
50774 C656 2 apparent apparente kVAh 3
50776 C658 2 active energy - kWh 3
50778 C65A 2 active energy + kWh 3
50780 C65C 2 No. Compteurs d’Impulsions - 3
50782 C65E 2 pulse meter 1 - 3
50784 C660 2 pulse meter 2 - 3
50786 C662 2 pulse meter 3 - 3
50788 C664 2 pulse meter 4 - 3
50790 C666 2 pulse meter 5 - 3
50792 C668 2 pulse meter 6 - 3
50794 C66A 2 Reserved for manufacturer - 3
50796 C66C 2 Reserved for manufacturer - 3
50798 C66E 2 Reserved for manufacturer - 3
50800 C670 2 Reserved for manufacturer - 3
50802 C672 2 S Predicted active power kW/100 3
50804 C674 2 S Predicted reactive power kvar/100 3
50806 C676 2 S Predicted apparent power kVA/100 3
50808 C678 2 Ea+ between2tops 0,1Ws 3
50810 C67A 2 Ea- between2tops 0,1Ws 3
50812 C67C 2 Er+ between2tops 0,1vars 3
50814 C67E 2 Er- between2tops 0,1vars 3
50816 C680 2 Reserved for manufacturer - 3
50816 C680 1 Reserved for manufacturer - 3
50817 C681 1 Reserved for manufacturer - 3
3 > TABLE C750 Hex : Additional measurements allocated from CT values (current transformer) and VT
(voltage transformer) values
Decimal Hex. No. of Description Unit JBUS function
address address words available
51024 C750 2 avg U12 V/100 3
51026 C752 2 avg U23 V/100 3
51028 C754 2 avg U31 V/100 3
51030 C756 2 avg V1 V/100 3
51032 C758 2 avg V2 V/100 3
51034 C75A 2 avg V3 V/100 3
51036 C75C 2 avg F Hz/100 3
51038 C75E 2 avg I1 mA 3
51040 C760 2 avg I2 mA 3
51042 C762 2 avg I3 mA 3
51044 C764 2 avg In mA 3
51046 C766 2 avg
Σ
active power + kW/100 3
51048 C768 2 avg
Σ
active power - kW/100 3
51050 C76A 2 avg
Σ
reactive power + kvar/100 3
51052 C76C 2 avg
Σ
reactive power - kvar/100 3
51054 C76E 2 avg
Σ
apparent power kVA/100 3
51056 C770 2 max/avg U12 V/100 3

DIRIS A40/A41 - RS485 -
ETHERNET®
17
DIRIS A40/A41 - Ref.: 536 181 B GB
GB
COMMUNICATION
Decimal Hex. No. of Description Unit JBUS function
address address words available
51058 C772 2 max/avg U23 V/100 3
51060 C774 2 max/avg U31 V/100 3
51062 C776 2 max/avg V1 V/100 3
51064 C778 2 max/avg V2 V/100 3
51066 C77A 2 max/avg V3 V/100 3
51068 C77C 2 max/avg F Hz/100 3
51070 C77E 2 max/avg I1 mA 3
51072 C780 2 max/avg I2 mA 3
51074 C782 2 max/avg I3 mA 3
51076 C784 2 max/avg In mA 3
51078 C786 2 max/avg
Σ
active power + kW/100 3
51080 C788 2 max/avg
Σ
active power - kW/100 3
51082 C78A 2 max/avg
Σ
reactive power + kvar/100 3
51084 C78C 2 max/avg
Σ
reactive power - kvar/100 3
51086 C78E 2 max/avg
Σ
apparent power kVA/100 3
51088 C790 1 Reserved for manufacturer - 3
51089 C791 1 Reserved for manufacturer - 3
51090 C792 1 Reserved for manufacturer - 3
51091 C793 1 Reserved for manufacturer - 3
51092 C794 1 Reserved for manufacturer - 3
51093 C795 1 Reserved for manufacturer - 3
A : NEW COMMUNICATION TABLE FROM 01/2009
3 > TABLE C750 Hex (continued)
Decimal Hex. No. of Description Unit JBUS function
address address words available
51280 C850 1 hour meter h 3
51281 C851 1 phase to phase voltage U12 V/100 3
51282 C852 1 phase to phase voltage U23 V/100 3
51283 C853 1 phase to phase voltage U31 V/100 3
51284 C854 1 phase to neutral voltage 1 V/100 3
51285 C855 1 phase to neutral voltage 2 V/100 3
51286 C856 1 phase to neutral voltage 3 V/100 3
51287 C857 1 frequency Hz/100 3
51288 C858 1 phase current 1 mA 3
51289 C859 1 phase current 3 mA 3
51291 C85B 1 neutral current mA 3
51292 C85C 1
Σ
active power +/- kW/100 3
51293 C85D 1
Σ
reactive power +/- kvar/100 3
51294 C85E 1
Σ
apparent power +/- kVA/100 3
51295 C85F 1
Σ
power factor L/C -:
leadingand+:lagging 0,001 3
51296 C860 1 phase active power 1 +/- kW/100 3
51297 C861 1 phase active power 2 +/- kW/100 3
51298 C862 1 phase active power 3 +/- kW/100 3
51299 C863 1 phase reactive power 1 +/- kvar/100 3
51300 C864 1 phase reactive power 2 +/- kvar/100 3
51301 C865 1 phase reactive power 3 +/- kvar/100 3
51302 C866 1 phase apparent power 1 kVA/100 3
51303 C867 1 phase apparent power 2 kVA/100 3
51304 C868 1 phase apparent power 3 kVA/100 3
4 > TABLE C850 Hex : Main measurements not allocated from CT values (current transformer) and VT
(voltage transformer) values
CAUTION : using this table involves multiplying values by transformation ratios.

DIRIS A40/A41 - RS485 - ETHERNET®
18 DIRIS A40/A41 - Ref.: 536 181 B GB
COMMUNICATION
A : NEW COMMUNICATION TABLE FROM 01/2009
4 > TABLE C850 Hex (continued)
Decimal Hex. No. of Description Unit JBUS function
address address words available
51305 C869 1 phase power factor 1 -:
leadingand+:lagging 0,001 3
51306 C86A 1 phase power factor 2 -:
leadingand+:lagging 0,001 3
51307 C86B 1 phase power factor 3 -:
leadingand+:lagging 0,001 3
51308 C86C 1 Reserved for manufacturer - 3
51309 C86D 1 Reserved for manufacturer - 3
51310 C86E 1 Reserved for manufacturer - 3
51311 C86F 1 Ea+ MWh 3
51312 C870 1 Reserved for manufacturer - 3
51313 C871 1 ER+ MWh 3
5 > TABLE C900Hex : Temperature measurements
Decimal Hex. No. of Description Unit JBUS function
address address words available
51456 C900 1 Internal temperature sensor present
0 : no - 1 : yes - 3
51457 C901 1 Temperature module °C 3
51458 C902 1
Externaltemperaturesensors(1to5max)
- 3
51459 C903 1 extern temperature 1 °C 3
51460 C904 1 extern temperature 2 °C 3
51461 C905 1 extern temperature 3 °C 3
51462 C906 1 Reserved for manufacturer - 3
51463 C907 1 Reserved for manufacturer - 3
6 > TABLE C950Hex : Harmonics
Decimal Hex. No. of Description Unit JBUS function
address address words available
THD
51536 C950 1 thdU12 0,001 3
51537 C951 1 thdU23 0,001 3
51538 C952 1 thdU31 0,001 3
51539 C953 1 thdV1 0,001 3
51540 C954 1 thdV2 0,001 3
51541 C955 1 thdV3 0,001 3
51542 C956 1 thdI1 0,001 3
51543 C957 1 thdI2 0,001 3
51544 C958 1 thdI3 0,001 3
51545 C959 1 thdIn 0,001 3
Current
51546 C95A 1 Max rank 3
51547 C95B 1
Harmonic
I1row3 0,001 3
51548 C95C 1 HarmonicI2row3 0,001 3
51549 C95D 1 HarmonicI3row3 0,001 3
51550 C95E 1 HarmonicINrow3 0,001 3
51551 C95F 1 HarmonicI1row5 0,001 3
51552 C960 1 HarmonicI2row5 0,001 3
51553 C961 1 HarmonicI3row5 0,001 3
51554 C962 1 HarmonicINrow5 0,001 3
51555 C963 1 HarmonicI1row7 0,001 3

DIRIS A40/A41 - RS485 -
ETHERNET®
19
DIRIS A40/A41 - Ref.: 536 181 B GB
GB
COMMUNICATION
Decimal Hex. No. of Description Unit JBUS function
address address words available
51556 C964 1 HarmonicI2row7 0,001 3
51557 C965 1 HarmonicI3row7 0,001 3
51558 C966 1 HarmonicINrow7 0,001 3
51559 C967 1 HarmonicI1row9 0,001 3
51560 C968 1 HarmonicI2row9 0,001 3
51561 C969 1 HarmonicI3row9 0,001 3
51562 C96A 1 HarmonicINrow9 0,001 3
51563 C96B 1 HarmonicI1row11 0,001 3
51564 C96C 1 HarmonicI2row11 0,001 3
51565 C96D 1 HarmonicI3row11 0,001 3
51566 C96E 1 HarmonicINrow11 0,001 3
51567 C96F 1 HarmonicI1row13 0,001 3
51568 C970 1 HarmonicI2row13 0,001 3
51569 C971 1 HarmonicI3row13 0,001 3
51570 C972 1 HarmonicINrow13 0,001 3
51571 C973 1 HarmonicI1row15 0,001 3
51572 C974 1 HarmonicI2row15 0,001 3
51573 C975 1 HarmonicI3row15 0,001 3
51574 C976 1 HarmonicINrow15 0,001 3
51575 C977 1 HarmonicI1row17 0,001 3
51576 C978 1 HarmonicI2row17 0,001 3
51577 C979 1 HarmonicI3row17 0,001 3
51578 C97A 1 HarmonicINrow17 0,001 3
51579 C97B 1 HarmonicI1row19 0,001 3
51580 C97C 1 HarmonicI2row19 0,001 3
51581 C97D 1 HarmonicI3row19 0,001 3
51582 C97E 1 HarmonicINrow19 0,001 3
51583 C97F 1 HarmonicI1row21 0,001 3
51584 C980 1 HarmonicI2row21 0,001 3
51585 C981 1 HarmonicI3row21 0,001 3
51586 C982 1 HarmonicINrow21 0,001 3
51587 C983 1 HarmonicI1row23 0,001 3
51588 C984 1 HarmonicI2row23 0,001 3
51589 C985 1 HarmonicI3row23 0,001 3
51590 C986 1 HarmonicINrow23 0,001 3
51591 C987 1 HarmonicI1row25 0,001 3
51592 C988 1 HarmonicI2row25 0,001 3
51593 C989 1 HarmonicI3row25 0,001 3
51594 C98A 1 HarmonicINrow25 0,001 3
51595 C98B 1 HarmonicI1row27 0,001 3
51596 C98C 1 HarmonicI2row27 0,001 3
51597 C98D 1 HarmonicI3row27 0,001 3
51598 C98E 1 HarmonicINrow27 0,001 3
51599 C98F 1 HarmonicI1row29 0,001 3
51600 C990 1 HarmonicI2row29 0,001 3
51601 C991 1 HarmonicI3row29 0,001 3
51602 C992 1 HarmonicINrow29 0,001 3
51603 C993 1 HarmonicI1row31 0,001 3
51604 C994 1 HarmonicI2row31 0,001 3
51605 C995 1 HarmonicI3row31 0,001 3
51606 C996 1 HarmonicINrow31 0,001 3
51607 C997 1 HarmonicI1row33 0,001 3
51608 C998 1 HarmonicI2row33 0,001 3
51609 C999 1 HarmonicI3row33 0,001 3
A : NEW COMMUNICATION TABLE FROM 01/2009
6 > TABLE C950Hex (continued)

DIRIS A40/A41 - RS485 - ETHERNET®
20 DIRIS A40/A41 - Ref.: 536 181 B GB
COMMUNICATION
A : NEW COMMUNICATION TABLE FROM 01/2009
6 > TABLE C950Hex (continued)
Decimal Hex. No. of Description Unit JBUS function
address address words available
51610 C99A 1 HarmonicINrow33 0,001 3
51611 C99B 1 HarmonicI1row35 0,001 3
51612 C99C 1 HarmonicI2row35 0,001 3
51613 C99D 1 HarmonicI3row35 0,001 3
51614 C99E 1 HarmonicINrow35 0,001 3
51615 C99F 1 HarmonicI1row37 0,001 3
51616 C9A0 1 HarmonicI2row37 0,001 3
51617 C9A1 1 HarmonicI3row37 0,001 3
51618 C9A2 1 HarmonicINrow37 0,001 3
51619 C9A3 1 HarmonicI1row39 0,001 3
51620 C9A4 1 HarmonicI2row39 0,001 3
51621 C9A5 1 HarmonicI3row39 0,001 3
51622 C9A6 1 HarmonicINrow39 0,001 3
51623 C9A7 1 HarmonicI1row41 0,001 3
51624 C9A8 1 HarmonicI2row41 0,001 3
51625 C9A9 1 HarmonicI3row41 0,001 3
51626 C9AA 1 HarmonicINrow41 0,001 3
51627 C9AB 1 HarmonicI1row43 0,001 3
51628 C9AC 1 HarmonicI2row43 0,001 3
51629 C9AD 1 HarmonicI3row43 0,001 3
51630 C9AE 1 HarmonicINrow43 0,001 3
51631 C9AF 1 HarmonicI1row45 0,001 3
51632 C9B0 1 HarmonicI2row45 0,001 3
51633 C9B1 1 HarmonicI3row45 0,001 3
51634 C9B2 1 HarmonicINrow45 0,001 3
51635 C9B3 1 HarmonicI1row47 0,001 3
51636 C9B4 1 HarmonicI2row47 0,001 3
51637 C9B5 1 HarmonicI3row47 0,001 3
51638 C9B6 1 HarmonicINrow47 0,001 3
51639 C9B7 1 HarmonicI1row49 0,001 3
51640 C9B8 1 HarmonicI2row49 0,001 3
51641 C9B9 1 HarmonicI3row49 0,001 3
51642 C9BA 1 HarmonicINrow49 0,001 3
51643 C9BB 1 HarmonicI1row51 0,001 3
51644 C9BC 1 HarmonicI2row51 0,001 3
51645 C9BD 1 HarmonicI3row51 0,001 3
51646 C9BE 1 HarmonicINrow51 0,001 3
51647 C9BF 1 HarmonicI1row53 0,001 3
51648 C9C0 1 HarmonicI2row53 0,001 3
51649 C9C1 1 HarmonicI3row53 0,001 3
51650 C9C2 1 HarmonicINrow53 0,001 3
51651 C9C3 1 HarmonicI1row55 0,001 3
51652 C9C4 1 HarmonicI2row55 0,001 3
51653 C9C5 1 HarmonicI3row55 0,001 3
51654 C9C6 1 HarmonicINrow55 0,001 3
51655 C9C7 1 HarmonicI1row57 0,001 3
51656 C9C8 1 HarmonicI2row57 0,001 3
51657 C9C9 1 HarmonicI3row57 0,001 3
51658 C9CA 1 HarmonicINrow57 0,001 3
51659 C9CB 1 HarmonicI1row59 0,001 3
51660 C9CC 1 HarmonicI2row59 0,001 3
51661 C9CD 1 HarmonicI3row59 0,001 3
51662 C9CE 1 HarmonicINrow59 0,001 3
51663 C9CF 1 HarmonicI1row61 0,001 3
Other manuals for DIRIS A40
14
This manual suits for next models
1
Table of contents
Other socomec Control Unit manuals
Popular Control Unit manuals by other brands

Red Valve
Red Valve Tideflex 35 Series Installation, operation and maintenance manual

M&S Systems
M&S Systems MC960 installation guide

PROPOINT
PROPOINT 8689507 Assembly & installation

Siemens
Siemens multiranger 200 Application guide

Cutler-Hammer
Cutler-Hammer Digitrip RMS 810 instructions

resideo
resideo Braukmann D15S installation instructions