Solaira SMaRT 34-DV Instruction Manual

Solaira SMaRT 34-DV Variable Controller
Installation & User Manual
KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE
SAFETY WARNING
ALL INSTALLATIONS/SERVICE MUST
ONLY BE PERFORMED BY A
LICENSED/CERTIFIED ELECTRICIAN TO
LOCAL AND NATIONAL ELECTRICAL
CODE (NEC).
WARNING: SHOCK AND FIRE
HAZARD:
•Serious injury or death could occur
•Disconnect ALL power sources before removing cover. Power should only be re-connected after
electrical installations are complete and cover replaced
•Be certain the power source conforms to the specifications outlined on the heater label
•Maximum heater load SHOULD NOT EXCEED 38 AMPERE
•The unit must be externally fused
•The Controller MUST BE PROPERLY GROUNDED. Ensure that the ground connection from
the electrical supply is connected to the Controller and Heater ground using a green sleeved
conductor.
•Do not connect the Controller or Heater ground connection to a live or “hot” conductor.
•Follow state, provincial, local and national electric codes (NEC) including field certifications
•Do not use in locations containing hazardous or explosive atmospheres.
ELECTRICAL RATING
Maximum load 8.0kW @208-240VAC 50/60HZ
4.0kW @120VAC 50/60HZ
WARNING SERIOUS INJURY OR DEATH COULD OCCUR,
DISCONNECT ALL POWER PRIOR TO SERVICE
SPE-1000 CANADA INSPECTED

INTRODUCTION
The Solaira SMaRT 34-DV Variable Control has been engineered to work with Infrared Heaters, with a
maximum rating of 8.0kW @ 208-240V or 4.0kW @ 120V.
The Solaira SMaRT 34-DV Control has a 1 to 5 step setting allowing you to find the optimum comfort setting
in your specific area.
To increase output to full output, press and release red button.
To increase in increments, press and hold the red button until the desired number is reached.
To reduce output to OFF, press and release red button.
To reduce in increments, press and hold the red button until the desired number is reached
FEATURES
•Weatherproof control for exposed, wet conditions (it is the electricians responsibility to assure correct
water tight connection, this may necessitate replacing included watertight strain relief)
•Variable Control –Ability to adjust output to desired comfort level
•Soft Start –zero current switching point which can extend emitter lamp life
•Temperature Monitoring –Solaira SMaRT 34-DV Variable control is equipped with a local (on
controller) temperature monitor. This will allow user to pre-set the minimum temperature level that will
allow the controller to operate.
Note: the temperature monitor is calibrated in Celsius; please use the following table to aid in set up:
Fahrenheit Celsius Fahrenheit Celsius
32.0 0.0 55.0 12.8
36.0 2.2 60.0 15.6
40.0 4.4 65.0 18.3
45.0 7.2 70.0 21.1
50.0 10.0 75.0 23.9
80.0 26.7
Infrared remote control interface which supports the Solaira SMaRT infrared remote control handset
(sold separately) which must be in line of sight of the controller.
Occupancy Sensor or Push button input (sold separately), which is used to re-trigger an internal "ON"
timer. The "ON" timer is configurable from 1-60 minutes by means of a trimmer potentiometer. If the
internal "ON" timer expires the load output is switched off.
Designed for optional remote, wired controller for use in dry, wall mount electrical box (sold
separately).
WARNING: Solaira SMaRT 34-DV Variable control is a high power
electrical device and MUST ONLY BE INSTALLED BY A CERTIFIED
ELECTRICIAN TO LOCAL AND NATIONAL ELECTRICAL CODE

INSTALLATION
The control can be installed in a convenient VENTED location and does not have to be installed in the
immediate area of the heaters. The unit is shipped with the Occupancy sensor/pushbutton input fitted with a
wire link which continually re-triggers the "ON" timer so that it never expires.
If the user decides to utilize the optional Occupancy Monitor, the occupancy monitor should be mounted 8’ (2.5
+ Meters) above of the floor. Ceiling mounting is preferred but not essential. The Optional Occupancy monitor
must not be mounted directly in line with the heaters output, highly reflective surfaces, radiators or other
thermostatically controlled heaters or open door ways with people walking past.
WARNING: CONTROLLER MOUNTING
It is important that the controller is not mounted directly on any flammable
material i.e. wood AND in ventilated area free of flammable vapours or materials. It is
recommended that the heat sink be spaced off the mounting wall using pillars to aid in
heat dissipation.
INITIAL START UP WITH OPTIONAL OCCUPANCY SENSOR
•Optional Occupancy Sensor (sold separately), it takes 60 seconds to set before detection takes place
•Optional Occupancy Sensor continues to monitor the area and will reset to the set time every time it
detects movement.
•Before testing ensure the wiring is correct.
•Temperature trip point has already been pre-set at the factory.
•Timer is pre-set to 1 minute but can be adjusted using timer trimmer potentiometer to 1-60 minutes.
•The expected detection area can now be “walked tested” using the diagram shown in mind. The area
should be crossed in various directions to ensure coverage is as expected.
DISPLAY FEATURES
Display shows "t" The unit is turned OFF as the ambient temperature is above the trip level set by
TEMPERATURE SETPOINT.
Display shows "0" The output is OFF
Display shows "1", "2", The unit is ON at the indicated power level
"3", "4"
Display shows ‘F The unit is set to FULL output.
Display flashing "." The "ON" timer has expired and is waiting to be re-triggered by the Occupancy
sensor (i.e. no movement detected for "ON" time) or the pushbutton.
Display shows "." The unit is in Standby mode pressing the optional fully on
remote control POWER button will toggle the power ON and OFF.
You can check the remote control is transmitting by observing the "." (dot) flashing rapidly.

TROUBLE SHOOTING
Heater does not come on, t in display….The heater pre-set trip temperature IS ABOVE THE AMBIENT
TEMPERATURE. This can be adjusted using the temperature set point potentiometer.
Heater does not come on, flashing DOT…The controller is waiting for input from optional occupancy sensor
or pushbutton. If your system does not utilize the occupancy sensor or a pushbutton, then wire jumper (factory
installed) must be in place in PIR SENSOR INPUT on pins SIG IN and COM. If the jumper is not in place,
controller will not operate.
SPECIFICATIONS
Max load at 20°C ambient
Voltage
Power Consumption
Occupancy Sensor (option)
Pushbutton Timer (option)
Set Time Period
Temperature Set point
Factory Set Temperature trip point
2 heater Installation
Ambient Operating Temperature
IP Rating
Max Unit Operating Temperature
Occupancy Sensor (optional)
Operating Voltage
Direction
Detection
8.0kW @ 208-240VAC or
4.0kW @ 120VAC
120Vac or 208-240Vac +/- 10%50/60Hz
50mA
See below
Momentary or Toggle
1-60 minutes
5°C to 25°C
25°C
Must be fitted in Parallel
-20°C to 30°C
IP65
65°C
12V dc
90° Adjustable
45’ (18 Meters)
WARNING: Solaira SMaRT 34-DV Variable control is a high power
electrical device and MUST ONLY BE INSTALLED BY A CERTIFIED
ELECTRICIAN TO LOCAL AND NATIONAL ELECTRICAL CODE

SMaRT 34-DV ILLUSTRATIVE WIRING DIAGRAM*
WARNING SERIOUS INJURY OR DEATH COULD OCCUR,
DISCONNECT ALL POWER PRIOR TO SERVICE

Trouble Shooting
Temperature Set Point
Temperature set point allows user to control the
MINIMUM TEMPERATURE for heaters to come
on. If the ambient temperature is above the
pre-set level, the heater control will show "t" and
WIL NOT TURN ON. You can reduce the minimum
temperature to 5⁰C
Temperature Sensor Input
For local temperature sensor input and optional remote
temperature sensor input. The local temperature sensor
is included with all SMaRT 34-DV controllers. If the user
wishes NOT to use the temperature monitoring feature,
simply disconnect the temperature sensor.
FLASHING DOT ON CONTROL PANEL DISPLAY
If the controller is used WITHOUT OPTIONAL OCCUPANCY SENSOR (PIR, Passive Infrared Sensor) or
Pushbutton timer, then "wire jumper" must be installed in pins SIG and COM as shown. If the jumper is
not installed, the controller senses an open circuit and will switch OFF. Your controller comes with the
jumper installed and it should only be removed when a sensor or pushbutton timer is installed.
Wire jumper installed for use
WITHOUT optional Occupancy
Sensor (PIR)

LIMITATION OF LIABILITY
It is understood and agreed that seller’s liability whether in contract, in tort, under any warranty, in negligence or
otherwise shall not exceed the return of the amount of the purchase price paid by purchaser and under no circumstances
shall seller be liable for special, indirect or consequential damages. The price stated for the equipment is a consideration
in limiting seller’s liability. No action, regardless of form, arising out of the transactions may be brought by purchaser
more than one year after the cause of action has accrued.
WARRANTY
1. SOLAIRA CONTROL products are guaranteed to be free from mechanical and electrical defects for a period of one
year from date of shipment under normal use and service provided installation is made in accordance with
manufacturers’ recommendations.
2. Parts deemed defective shall be repaired or replaced at manufacturers option and at manufacturers expense but shall
not include foreign or federal excise taxes, state or municipal sale or use taxes, all such taxes not limited to the
foregoing being responsibility of the purchaser.
3. No charge for travel and/or mileage will be allowed to purchaser.
4. SOLAIRA reserves the right to make changes in design or make any improvements on any products. The right is
always reserved to modify our equipment because of new technology, underwriter’s requirements and/or government
regulations.
5. The following are not covered under warranty:
a. INSTALLATION OF CONTROL BY NON-CERTIFIED ELECTRICIAN.
b. Failure from neglect, abuse, careless handling and mis-application of unit.
c. Failure to observe guidelines for installation or improper voltage hook-up.
d. Failure caused by improper installation and not following local, state/provincial and federal electrical guidelines
e. Unless specifically allowed by SOLAIRA CONTROLS, no other charges may be included under warranty.
Notice: Inforesight Consumer Products Inc. website, product information and products can be accessed from Canada and
other countries around the world. Customer understands that some or all products provided by Inforesight Consumer
Products Inc. may not be available for purchase or installation in certain jurisdictions or geographical areas. Inforesight
Consumer Products Inc. reserves the right, in its sole discretion, to exclude or otherwise limit the provision of any product
to a person or entity residing in any jurisdiction or geographical area outside of Canada. Inforesight Consumer Products
Inc. provides general product information, installation guidelines and procedures and Customer understands that Customer
is solely and exclusively responsible for installation of the product and ascertaining all applicable local municipal,
provincial, state, and federal NEC (National Electrical Code) rules, by-law, ordinances and guidelines applicable to the
installation of any Inforesight Consumer Products Inc. products. Customer must strictly adhere to and be compliant with
the local rules, laws, ordinances and legal requirements for the safe installation and use of any Inforesight Consumer
Products Inc. products. Instruction manuals are included with the product packaging and copies of our instruction manuals
are available upon request. Under no circumstances shall Inforesight Consumer Products Inc. or its affiliated entitles,
employees, agents, shareholders, officers or directors be liable to Customer or any third party for any product installations
and Customer releases Inforesight Consumer Products Inc. from any and all losses, death, personal injury, property
damage, other damages, rights, claims, demands and actions of any kind arising from the Customer’s installation and use of
the product, whether the installation was or was not in accord with the provided instruction manual and/or in compliance
with applicable local laws.
Solairatm is a registered trademark of Inforesight Consumer Products Inc.
125 Traders Blvd. # 4, Mississauga, Ontario, Canada, M4Z 2H3
Tel: 905-568-7655, EXT 23 SERVIC, Fax:905-568-7521
info@solairaheaters.com
Revision: Issue 3, September 2016