manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Controllers
  8. •
  9. Honeywell R7426A User manual

Honeywell R7426A User manual

Other manuals for R7426A

1

This manual suits for next models

3

Other Honeywell Controllers manuals

Honeywell S9240F2051 User manual

Honeywell

Honeywell S9240F2051 User manual

Honeywell 1000 Series User manual

Honeywell

Honeywell 1000 Series User manual

Honeywell Excel 800 Installation and operation manual

Honeywell

Honeywell Excel 800 Installation and operation manual

Honeywell Ultrakey Lite User manual

Honeywell

Honeywell Ultrakey Lite User manual

Honeywell WEB/CP-202-XPR User manual

Honeywell

Honeywell WEB/CP-202-XPR User manual

Honeywell UMC800 User manual

Honeywell

Honeywell UMC800 User manual

Honeywell DC1010 Quick start guide

Honeywell

Honeywell DC1010 Quick start guide

Honeywell LYNX Touch L5200 Series User manual

Honeywell

Honeywell LYNX Touch L5200 Series User manual

Honeywell ML9185 User manual

Honeywell

Honeywell ML9185 User manual

Honeywell AQUASTAT L4188A User manual

Honeywell

Honeywell AQUASTAT L4188A User manual

Honeywell UDC3500 User manual

Honeywell

Honeywell UDC3500 User manual

Honeywell C User manual

Honeywell

Honeywell C User manual

Honeywell PCR-300 User manual

Honeywell

Honeywell PCR-300 User manual

Honeywell Ex-Or MSM2000D Installation and operation manual

Honeywell

Honeywell Ex-Or MSM2000D Installation and operation manual

Honeywell 190797-YAD User manual

Honeywell

Honeywell 190797-YAD User manual

Honeywell LP1501 Operator's manual

Honeywell

Honeywell LP1501 Operator's manual

Honeywell Tradeline H1008A Operation manual

Honeywell

Honeywell Tradeline H1008A Operation manual

Honeywell PRO-2200 User manual

Honeywell

Honeywell PRO-2200 User manual

Honeywell Aquasat L7224 A Aquasat L7224 C User manual

Honeywell

Honeywell Aquasat L7224 A Aquasat L7224 C User manual

Honeywell ML4125 Operation manual

Honeywell

Honeywell ML4125 Operation manual

Honeywell MT4-024 User manual

Honeywell

Honeywell MT4-024 User manual

Honeywell AQUASTATIC L7224 Series User manual

Honeywell

Honeywell AQUASTATIC L7224 Series User manual

Honeywell UDC3500 User manual

Honeywell

Honeywell UDC3500 User manual

Honeywell ML8824 Series Operator's manual

Honeywell

Honeywell ML8824 Series Operator's manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

PRODUCT DATA
63- 2565
® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved
R7426A,B,C,D
Temperature and
Universal Input Controllers
TIME-INDEPENDENT CONTROLLERS
APPLICATION
R7426A,B,C Temperature Controllers use directdigital control
technology to provide more accurate and efficient operation of
heating, ventilation and air conditioning (HVAC) systems.
Parametersare preset for plug and play operation and provide
different control strategies for optimum system performance.
The controller performs proportional or proportional plus
integral (P+I) control and covers all space, supply air or water
flow applications within the specified ranges of 32°F to 122°F
(0°C to 50°C) or 32°F to 266°F (0°C to 130°C). Standard
Pt 1000 or NTC 20K ohm temperature sensors can be used.
The modern design with its easy to operate user interface and
LCD allows complete flexibility of control system design,
accurate parameter setting, and display of actual temperature
values, setpoints and outputs.
The R7426D Universal Input Controller covers all space or
discharge air humidity control applications and special
applications, such as pressure control, within 0 to 10 Vdcinput
ranges. The controller provides input span adjustment to
match the transmitter output specification.
FEATURES
• Selectable proportional, proportional plus integral
(P+I), or (R7426D only) proportional plus integral plus
derivative (P+I+D) control.
• Pre-programmed control parameters.
• Digital parameter setting.
• Selectable direct/reverse acting output.
• 24 Vac power supply.
R7426A,B,C
• 3 inputs for temperature sensors.
• Automatic sensor type identification of Pt 1000 or
NTC 20K ohm.
• 3 digital inputs for plant/system On/Off, occupancy
(alternatively summer/winter changeover) and freeze
protection.
• Dehumidification control via humidity deviation input.
• Selectable floating output functions:
— Floating.
— 2, 3, 4, 6 or 15 stage On/Off (TRIAC).
— Pulse width modulation (PWM).
• Analog outputs 0/2 to 10Vdc selectable.
• Start-up routine.
• Space/supply limit or cascade control.
• Sequence control of heating, mixed air damper or
energy recovery system and cooling.
R7426D
• 2 analog inputs 0 to 10Vdc for transmitters.
• Control output monitoring and manual output signal
override.
• Master/submaster cascade control.
• Main variable control and optional high/low limit control.
• Input span adjustment.
• Temperature compensation input.
• Optional remote setpoint adjustment. Contents
Application ....................................................................... 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Operation ......................................................................... 4
Operating Overview ......................................................... 8
Appendix .......................................................................... 10
Control And Configuration Parameters ....................... 10
Parameter Details ....................................................... 12
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
63-2565 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
Models:
R7426A: Temperature Controller with floating, PWM, and 2 or
3-stage On/Off outputs.
R7426B: Temperature Controller for sequence control of
heating, energy recovery, and cooling. Floating, PWM, and
2,3,4,6, or 15-stage On/Off outputs.
R7426C: Temperature Controller for sequence control of
heating, energyrecovery or mixed-air damper, and cooling,
or to drive step controllers. Analog 0/2 to 10 Vdc output.
R7426D: Universal Input Controller with two transmitter inputs
for master/submaster cascade control, or main and
optional high or low limit control. One temperature
compensation input to provide main setpoint reset. One
analog output and one deviation signal output.
Dimensions: See Fig. 1.
Weight: 0.55 lb (250g).
Mounting: Back panel, wall, DIN rail, or (with panel mounting
accessory frame) front panel.
Electronic:
Microcontroller: 8-bit, 10-bit A/D converter, EEPROM and LCD.
Power supply: 24 Vac +10, -15%, 50/60Hz.
Power consumption: 3 VA.
Wiring:
Maximum Wiring Run from Controller to All Devices:
18 AWG: 328 ft (100m).
16 AWG: 492 ft (150m).
Offset Due to Wire Resistance: See Table 2.
Ambient Ratings:
Temperature:
Operating: 32°F to 122°F (0°C to 50°C).
Storage: -31°F to +158°F (-35°C to +70°C).
Humidity: 5 to 95% relative humidity, non-condensing.
Digital Inputs:
Occupancy (Summer/Winter Changeover) (R7426A,B,C only):
Operation Mode: Unoccupied (Winter), Occupied (Summer).
Potential Free Contact: open > 40kW, closed < 100W.
Freeze Protection (R7426A,B,C only):
Operation Mode: Freeze protection (normal).
Potential Free Contact: open > 40kW, closed < 100W.
Plant System On/Off:
Potential-Free Contact: open (off) greater than 40 kW,
closed (on) less than 100W.
Accuracy: ±0.9°F (±0.5K) (not including sensor inaccuracy).
Analog Inputs:
All Models: I03: Temperature compensation sensor.
R7426A,B,C Temperature Inputs:
I01: Main sensor.
I02: Limit or cascade sensor.
R7426D Universal Inputs (0 to100%, adjustable 0to 10 Vdc span):
I01: Main sensor.
I02: Limit or cascade sensor.
Outputs:
R7426A,B,C:
TRIAC (selectable) (Maximum Load: 450 mA at 24 Vac.):
Floating: Single-pole, double-throw (spdt) switching.
2,3,4,6 or 15-stage: On (24 Vac) / Off (0 Vac).
Pulse width modulation: 0 to 100% based on run time.
Humidity Deviation (optional): -5 to 5 Vdc, 200 mV/%rh.
Maximum Load: 450 mA at 24 Vac.
Analog (R7426C,D only):
Control Range: 0/2 to 10 Vdc (0 to 100%).
Full Range: 0 to 12 Vdc.
Maximum Load: 1.2 mA at 12 Vdc.
R7426D:
On/Off: Delay adjustable single-pole, single-throw (spst) switching.
Maximum Load: 450 mA at 24 Vac.
Deviation Signal:
Deviation Range: -5 to 5 Vdc (-25 to +25%), 200 mV/%.
Maximum Load: 0.5 mA at 5 Vdc.
Analog Output (O1):
Control Range: 0/2 to 10 Vdc (0 to 100%).
Full Range: 0 to 12 Vdc.
Maximum Load: 1.2 mA at 12 Vdc.
Sensor Ratings:
Temperature Range:
Pt 1000: -22°F to 266°F (-30°C to +130°C).
NTC 20K ohms (selectable):
-22°F to 185°F (-30°C to +85°C).
-22°F to 266°F (-30°C to +130°C).
Characteristics:
Pt 1000: 1000 ohms at 32°F (0°C).
NTC 20K ohms: 20K ohms at 77°F (25°C).
Control ranges:
R7426A,B,C: 32°F to 122°F (0°C to 50°C) or 32°F to 266°F
(0°C to 130°C).
R7426D: 0 to 100%.
Control Point Adjustments (CPA)/Setpoint Adjustments
(SPA): See Accessories and Table 1.
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
3 63-2565
Approvals:
Protection class II.
NEMA 1, IP30 or (with front panel mounting only) IP40.
FCC Part 15, Class B.
Accessories:
43193862-001 Front panel mounting frame.
NTC 20K ohm sensors for CPATYP 3 (10 to 20K ohms):
C7031B1033: For duct discharge air, hot water.
C7031D1062: For hot or chilled water.
C7031F1018: For outdoor air temperature.
C7031J1050: For duct discharge air (averaging).
C7031K1017: For hot or chilled water (strap-on).
T7770A1006: Wall module with locking cover.
T7770B1004: Wall module with locking cover and setpoint
adjustment knob (55°F to 85°F).
Pt 1000 sensors for CPATYP 1:
C7031D1070: For hot or chilled water.
C7031F1026: For outdoor air temperature.
C7031J1068: For duct discharge air (averaging).
C7031K1025: For hot or chilled water (strap-on).
Table 1. CPA/SPA Selectable Inputs.
aDefault value.
Table 2. Sensor Offset Per 33 ft (10m) of Wire.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product operation
as provided in these instructions.
Mounting
The controller can be mounted in an electric cabinet or other
suitable enclosure. They are suitable for back panel, wall, and
DIN rail mounting.
Fig. 1. R7426 Dimensions.
Back Panel or Wall Mounting
1. Drill two holes in the mounting surface (see Fig. 1).
2. Remove the controller from the baseplate:
a. Insert a flat head screwdriver into the slot at the right
side of the control face.
b. Pull control right side slightly away from baseplate.
c. Insert a flat head screwdriver into the slot at the left
side of the control face.
d. Pull the controller away from the baseplate.
3. Mount the baseplate to the surface.
4. Replace the controller on the baseplate.
DIN Rail Mounting
1. Remove the controller from the baseplate:
a. Insert a flat head screwdriver into the slot at the right
side of the control face.
b. Pull control right side slightly away from baseplate.
c. Insert a flat head screwdriver into the slot at the left
side of the control face.
d. Pull the controller away from the baseplate.
2. Mount the baseplate to the TS35 DIN rail.
3. Replace the controller on the baseplate.
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
Connect the wires to the device:
1. Strip 3/8 in. to 1/2 in. of insulation from the controller
end of each wire.
2. Insert each wire into the appropriate terminal on the top
or bottom of the device (see Fig. 2 and 3):
a. Solid wire: Push stripped end into terminal.
b. Stranded wire: Apply pressure to numbered indent
corresponding to the terminal while inserting wire.
3. Apply power to the device.
CPATYP
Value Sensor
(in ohms) CPA/SPA range
0ainternal CPA: ±9°F
1 9574 to 1426
2 100K to 0
4 0 to 10K
3 9574 to1426 SPA: 59°F to 86°F (15°C to 30°C)
5 0 to 100K
6 0 to 100K SPA: 32°F to 122°F (0°C to 50°C)
or 32°F to 266°F (0°C to 130°C).
Wire Type
in AWG (mm2)Temperature offset in °F (°C)
Pt 1000 NTC
20 (0.5) 0.32 (0.18) negligible
17 (1.0) 0.16 (0.09)
15 (1.5) 0.11 (0.06)
+
–
SEL
SET
4-1/8
(105)
3-7/16
(87)
1-7/16
(37)
6 (152)
4-5/8 (118) 1/8 (3) DIAMETER
WALL MOUNTING M17411
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
63-2565 4
Fig. 2. R7426A,B typical wiring.
Fig. 3. R7426C,D typical wiring.
OPERATION
Main Temperature Control
The controller compares the actual temperature value
measured by the main sensor (I01) with the calculated setpoint
(CTRP1) and generates a proportional (Xw) or proportional
plus integral (Xwi) deviation signal. CTPR1 is the sum of the
compensation effect, the CPA and the unoccupied offset.
NOTE: All diagrams show proportional control action only. If
P+I controlis in operation heating and cooling slopes
are not defined.
2515 16 17 18 19 20 21 22 23 24 26 27 28
R7426A
2
1112345678910 12
OFF
ON
13 14
L1
(HOT)
L2
+–
CLOSE
OUT OPEN
OUT
IO1
CPA/SPA
UNOCCUPIED FREEZE
PROTECTION
OFF
ON
PLANT/
SYSTEM
OCCUPIED
MAIN
TEMPERATURE
SENSOR
LIMIT OR
CASCADE
SENSOR
COMPENSATION
SENSOR
+–
IO2
O1
+–
IO3
HONEYWELL
SERIES 61
ACTUATOR
2515 16 17 18 19 20 21 22 23 24 26 27 28
R7426B
2
1112345678910 12
OFF
ON
13 14
+–
CLOSE
OUT OPEN
OUT CLOSE
OUT OPEN
OUT CLOSE
OUT OPEN
OUT
IO1
CPA/SPA
UNOCCUPIED FREEZE
PROTECTION
OFF
ON
PLANT/
SYSTEM
OCCUPIED
MAIN
TEMPERATURE
SENSOR
LIMIT OR
CASCADE
SENSOR
COMPENSATION
SENSOR
+–
IO2
O1
+–
IO3
M17483
1
2
3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TERMINALS 13 AND 14 ARE A SERIAL INTERFACE FOR A PANEL BUS.
RELATIVE HUMIDITY INPUT IS EQUAL TO 200 mV DIVIDED BY PERCENT RH.
O2 O3
3
L1
(HOT)
L2
1
1
HUMIDITY
SENSOR
+–
XWRH HONEYWELL
SERIES 61
ACTUATOR
HONEYWELL
SERIES 61
ACTUATOR
HONEYWELL
SERIES 61
ACTUATOR
2515 16 17 18 19 20 21 22 23 24 26 27 28
R7426D
M17446
2
1112345678910 12
OFF
ON
ON/OFF
OUTPUT
13 14
1
2
3
4
4
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
TERMINALS 13 AND 14 ARE A SERIAL INTERFACE FOR A PANEL BUS.
L1
(HOT)
L2
1
+–
IO1
CPA/
SPA
0/2 TO 10 Vdc
OUTPUT
FREEZE
PROTECTION
OFF
ON
PLANT/
SYSTEM
COMPENSATION
SENSOR
+–
+–
IO2
O1
+–
IO3
HONEYWELL
SERIES 70
ACTUATOR
RELAY
2515 16 17 18 19 20 21 22 23 24 26 27 28
R7426C
2
111234 5 678910 12
OFF
ON
13 14
1
3
L1
(HOT)
L2
+–
IO1
CPA/SPA
0/2 TO
10 Vdc
OUTPUT
0/2 TO
10 Vdc
OUTPUT
0/2 TO
10 Vdc
OUTPUT
UNOCCUPIED
FREEZE
PROTECTION
OFF
ON
PLANT/
SYSTEM
OCCUPIED
MAIN
TEMPERATURE
SENSOR
LIMIT OR
CASCADE
SENSOR
COMPENSATION
SENSOR
+–
+–+–+–
IO2
O1 O2 O3
+–
IO3
HUMIDITY
SENSOR
+–
XWRH HONEYWELL
SERIES 70
ACTUATOR
HONEYWELL
SERIES 70
ACTUATOR
HONEYWELL
SERIES 70
ACTUATOR
RELATIVE HUMIDITY OUTPUT (Xw). EQUAL TO 200 mV DIVIDED BY PERCENT RH.
RELATIVE HUMIDITY INPUT IS EQUAL TO 200 mV DIVIDED BY PERCENT RH.
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
5 63-2565
R7426 Temperature Control
Depending on the deviation signal, the control output (O1)
value is calculated and converted to a floating signal. Select
director reverse action using theDIR/REV parameter (cooling
is Dir, heating is Rev). The throttling range setting (Xp1)
controls the output span.
The startpoint Ostart determines the midrange shift of the
output (O1) from the calculated setpoint (CTRP1).
Limit Control (Wlim, Xp2 and tr2)
The R7426 controller offers limit control (Wlim) by comparing
the deviation signals of the main and limit control loops. The
lowest (low limit control) or highest (high limit control)
deviation signal is selected and fed to the output stage.
High limit control is performed when parameter LimTyp is 1.
Low limit control is performed when parameter LimTyp is 0.
During limit control, throttling range (Xp2) and reset time (tr2)
are active.
NOTES: Limit control is active only if either:
—I02 temperature sensor (parameter I02ext is 0) is
connected, or
—I01 sensor (control parameter I02ext is 1)
supplies the control loop.
Cascade Control (Wcas, Rcas and tr2)
The R7426 provides cascade control using two control loops
(master and submaster) to maintain setpoint (CTRP1).
At zero room temperature deviation (XWMaster), discharge
temperature (I02) is controlled by the programmed setpoint
(Wcas = CTRP2). If room temperature deviates, submaster
setpoint (CTRP2) is altered. See Fig. 4.
—Reset span adjustment (Rcas) determines degree of reset
effect.
—Integral reset time and throttling range of submaster P+I
control can be adjusted with tr2 and Xp2.
—CTRP2 high limit is performed if LimTyp is 1.
—CTRP2 low limit is performed if LimTyp is 0.
Fig. 4. Cascade control.
NOTES: Offs varies depending on the control mode:
—Occupied: Offs is 0. (See Fig. 6.)
—Unoccupied: Offs is SOFFS.
—Night: Offs is NOFFS.
R7426B,C Control with Heating, Mixed Air
Dampers and Cooling
Sequence Control
This application will be active with the R7426B,C controllers
when I02 is not connected. It can be used for sequence
control of a heating valve, an energy recovery system or a
mixed air damper and a cooling valve.
The characteristic of each output can be selected via the
parameters DIR/REVx (where x is O1, O2 or O3). Fig. 5 shows:
•Dir characteristic for all outputs.
•Control of damper signal within the range Xp1.
NOTE: If no cooling actuator is available, the parameter Xpc
can be set to Off and damper output is maintained at
100 percent above control point (CTRP1).
If damper output should be descreased to MINPOS level
above CTRP1 (see Fig. 5), or if no cooling actuator is
available, parameter Xpc must be adjusted to a value
between 2°F and 72°F.
Fig. 5. R7426B,C direct/reverse action.
Temperature Cascade Control
This application will be active with the R7426B,C controllers if
parameter Wcas is set to any value other than Off. It can be
used for sequence control of: a heating valve, an energy
recovery system, or mixed air damper and cooling valve.
Three cascade control modes are available:
•With occupied (contact closed) mode. (See Fig. 6.)
•With unoccupied (contact open) mode. See Cascade
Control section (Fig. 4).
•With night mode. See Cascade Control section (Fig. 4).
Each output characteristic can be selected via parameters
DIR/REVx (where x is O1, O2 or O3). Fig. 5 shows:
•Dir characteristic for all outputs.
•Control of damper signal within the range Xp2.
NOTE: If no cooling actuator is available, the parameter Xpc
can be set to Off.
If parameter Xpc is Off, the cooling signal is set to 0 percent
and damper output is maintained at 100 percent above control
point (CTRP1).
M17450
IO1
0
CTRP1
CTRP2 Xw MASTER
MASTER
SUBMASTER
Xp/2
Xp/2
0Xw MASTER
1
1 2WHEN LimTyp IS 1.
2
WHEN LimTyp IS 0.
Offs
Offs
W
2x
RWCAS
CAS
LIM
WLIM
M17447
O1
IO1
Y
100%
00
REV DIR
CTRP1
Xw
Xp1 START
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
63-2565 6
Fig. 6. Occupied Cascade Control.
—CTRP2 high limit is performed if parameter LimTyp is 1.
—CTRP2 low limit is performed if parameter LimTyp is 0.
Economizer Modes
Economizer modes are suitable for installations where the
main temperature sensor (I01) is installed in either exhaust air
or the room with a constant offset between room and exhaust
air conditions. The offset value is programmable within 0°F to
9°F with parameter RetOffs which will be added to the actual
room temperature value to simulate exhaust air conditions.
NOTE: Economizer mode is disabled if parameter RetOffs is
programmed Off, or no OAT sensor is connected.
By comparing the conditions of outside air with exhaust air,
the O1 output on the three-output controller operates using
Mixed Air Dampers or an Energy Recovery System:
Economizer Mixed Air Damper Mode
Economizer mixed air damper mode is active when:
•RetOffs is not Off.
•DIR/REVO1 is Dir.
NOTE: See Table 3 for control logic.
Table 3. Economizer Mixed Air Damper Mode.
NOTE: A fixed hysteresis of 2°F is used to switch between
MINPOS and O1.
Economizer Energy Recovery System
Economizer mixed air damper mode is active when:
•RetOffs is not Off.
•DIR/REVO1 is Rev.
NOTE: See Table 4 for control logic.
Table 4. Economizer Energy Recovery System Mode.
NOTE: A fixed hysteresis of 2°F is used to switch between
100 percent and O1.
Controller Functions
Outside Air Temperature Compensation
Outside air temperature compensation is performed when I03
is connected. The parameter Wcomp defines the summer and
winter compensation changeover point. Parameters Wi and
Su define the degree of summer and winter compensation.
Fig. 7. OAT Compensation.
When Dir/RevO1 = Rev (heating control):
When Dir/RevO1 = Dir (cooling control):
•Winter compensation is performed if .
•Summer compensation is performed if .
SMOOTHING FILTER FOR OUTSIDE AIR TEMPERATURE INPUT
A smoothing filter for OAT input I03 is incorporated to
eliminate sudden temperature variations. This provides more
stable control system operation.
Summer/Winter Changeover Function
Occupancy input can alternatively be used for summer/winter
changeover. Activate the summer/winter changeover function
by setting the control parameter DIR/REVO1 to Cho.
NOTE: This is provided only on the R7426A controller.
A potential free contact can be used between terminals 1 and
4 to switch the controller mode to heating (contact open) or
cooling (contact closed).
Freeze Protection
See Table 5 for actions executed when the contact connected
to the freeze protection input is opened. A closed contact
performs frost recovery (see Table 6).
NOTE: Freeze protection operation takes priority over all
other control operations.
Outside Air Temperature O1
Greater than exhaust air
temperature MINPOS
Less than exhaust air
temperature Included in direct acting
heating sequence control
M17448
IO1
0
CTRP1
CTRP2 Xw MASTER
MASTER
SUBMASTER
Xp
0
W
Xw MASTER
2x
RWCAS
CAS
1
1 2WHEN LimTyp IS 1.
2
WHEN LimTyp IS 0.
LIM
WLIM
Outside Air Temperature O1
Greater than exhaust air
temperature 100 percent
Less than exhaust air
temperature Energy Recovery System
included in heating sequence
control. MINPOS is not active.
M17451
CTRP1 Su
Wcomp
W1+XOFFS+CPA
IO3
Wi
XOFFS OFFS–=
XOFFS OFFS=
I03 WCOMP
<
I03 WCOMP
>
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
7 63-2565
Dehumidification Control (Humidity Deviation Input)
Dehumidification control is available only on the R7426B,C
controllers (three outputs). Use it to connect a humidity
controller. The R7426 compares the deviation input signal
from the humidity controller (Xwrh) with the temperature
control cooling deviation signal (Xwc). The signal with the
highest cooling demand is used to control cooling output (O2).
Table 5. Freeze Protection Actions.
Table 6. Frost Recovery.
Output Functions
The controller provides a choice of output signals suitable for
operating a range of final control devices. Suitability is based
on the parameter setting of OMode and OxMode (where x is
1, 2 or 3) parameters.
R7426A and R7426B
FLOATING VALVE OR DAMPER ACTUATORS (FLOATING MODE)
Parameter setting for Heating/Cooling Control Outputs:
OMode is 0; OxMode (where x is 1, 2 or 3) is 0.
The controller converts the deviation signal to a proportional
output pulse which drives the actuators depending on the
Runtimex (where x is O1, O2 or O3) parameter value.
An automatic synchronization function ensures correct
actuator positioning. This is performed by periodically running
all actuators to the closed position. Synchronization run time
is derived by control parameter Runtimex (where x is O1, O2
or O3) multiplied by 1.25.
Synchronization by the controller is initiated:
•After power up reset (initial start).
•After 250 control steps with control output below 5 percent.
•If plant/system On/Off input is switched to Off.
ELECTRIC HEAT CURRENT VALVE (PWM OUTPUT)
PWM output is suitable for driving electric heat current valves.
It is controlled from the heating signal. The interval or total
cycle time is set by parameter Runtimex (where x is O1 or O3).
EXAMPLE:With 60 percent Output Signal and Motor
Runtimex (where x is O1 or O3) set to 50 sec,
OMode is 0, OxMode (where x is 1 or 3) is 3.
2-STAGE ON/OFF SEQUENCE CONTROL
The R7426A,B controllers convert the output signal into a
2-stage On/Off sequence output signal suitable for operating
relays. Two relays can be connected to provide sequence
control of two stages (such as electric heat stages).
Parameter setting for Output Switching Position:
•OMode is 0.
•OxMode (where x is 1, 2 or 3) is 1.
3-STAGE BINARY ON/OFF SEQUENCE CONTROL
The R7426A,B controllers convert the heating signal into a
3-stage binary On/Off sequence.
Parameter setting for Output Switching Position:
•OMode is 0.
•OxMode (where x is 1 or 3) is 2.
Outputs for R7426B only
4-STAGE ON/OFF ELECTRIC HEATING OR COOLING
When OMode is 2, the O3/O1 output sequence is controlled from
the heating signal and O2 is controlled from the cooling signal.
When OMode is 3 the O3/O1 output sequence is controlled from
the cooling signal and O2 is controlled from the heating signal.
For temperature control sequence, see Temperature
Sequence Control with Heating, Mixed Air Dampers and
Cooling section.
NOTES:
—Mixed air damper operation is not available.
—Output O2 operates in accordance with O2Mode.
6-STAGE ON/OFF SEQUENCE CONTROL HEATING OR COOLING
The output sequence of O3/O2/O1 is controlled from one
output signal. (See Main Temperature Control or R7426A
Cascade Control.)
15-STAGE BINARY ON/OFF ELECTRIC HEATING AND COOLING
The output sequence of O3/O1 is controlled from the heating
signal. The output sequence of O2 is controlled from the
cooling signal (see Temperature Sequence Control with
Heating, Mixed Air Dampers and Cooling section). O2 output
is operated in accordance with O2Mode.
NOTE: The mixed air damper operation is not available.
Fig. 8. 15-stage binary on/off electric heating and cooling.
Model
Output Function Freeze Protection Action
DIR/
REVO1 Su/Wi
Changeover Outputs (in percent)
O1 O2 O3.
R7426A Dir —0——
Rev —100 ——
Cho Cooling 0 ——
Cho Heating 100 ——
R7426B —— 00100
R7426C 0 0 100
Model
Conditions of
Outdoor
Temperature (I03) Frost Recovery
R7426A
R7426B
R7426C
Greater than 43°F
(6°C) or I03 not
connected
Main temperature control
Less than 43°F (6°C) Setpoint W1 temporarily
raised by Xp1 and linearly
decreased to normal value
over approximately 10 min
M17452
POWER
STEP 1 ON
STEP 2 ON
STEP 14 ON
STEP 15 ON
ON
OFF O3/O1
4 SIGNAL SEQUENCE
OF O3/O1 OUT1/OUT2
4.5 11
6.5 13 89 95.5 100%
6.5 13
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
63-2565 8
Two Position Damper Control (R7426B,C)
If parameter OMode is 4, then the R7426B,C damper output
signal O1 operates as a two-position control:
•When the On/Off input signal is On: O1 is 100 percent.
•When the On/Off input signal is Off: O1 is 0 percent.
•For the O2/O3 output sequence, see the Temperature
Sequence Control with Heating, Mixed Air Damper and
Cooling section.
NOTE: The start-up routine must be disabled.
Analog Output (R7426C only)
Three dc output control signals are provided to control
actuators for valves, dampers, or pneumatics (through E/P
transducers).
The full output range is 0 to 12 Vdc. The control range is
common to all outputs and is software configurable to either:
2 to 10 Vdc, or 0 to 10 Vdc.
NOTE: Use the parameter ORange to configure the output.
Adjustments
Control Point / Setpoint Adjustment (CPATYP)
The control or setpoint can be adjusted using an internal or
external potentiometer connected to the CPA/SPA input (see
Technical Data). The CPA/SPA type is selected by the control
parameter CPATYP (see Technical Data).
Temperature Sensor Calibration (I01CAL, I02CAL
and I03CAL)
In case of an offset resulting from long wiring lengths, the
temperature sensor inputs (I01, I02 and I03) can be adjusted
separately using parameters I01CAL, I02CAL and I03CAL.
OPERATING OVERVIEW
Display and Operation Elements
NOTES: Pressing the + or - button modifies values or scrolls
through the parameter list:
—One press: single step.
—Pressing and holding: automatically modifies
value or scrolls through list.
—After 3 seconds of pressing without release:
speed of modification/scrolling increases.
Changing Operating Modes
After power-up, the controller version is displayed (see
Fig. 9) and the controller enters standard display mode (see
Fig. 10). This mode displays selected input/output values.
NOTE: Although the R7426A,B,C have four control modes
(see Fig. 10), the R7426D controller has only Off and
On. (The On icon is the same as the Occupied icon.)
Fig. 9. Controller Version.
Parameter Selection/Adjustment
Use this mode for application configuration:
1. Press and hold the + and - buttons to display parameter
selection mode.
2. Press + until the desired parameter is displayed.
3. Press SET to enter adjustment mode.
4. Use + and - to adjust parameter to desired setting.
5. Return the controller to selection mode using either:
a. SET places the parameter value into the EEPROM.
b. SEL discards the change.
To Display Actual Values
In standard display mode, one of six actual values can be
selected and displayed (see Table 7) by pushing SEL.
Fig. 10. R7426 display.
Resetting Parameter Values to Default
To reset all parameter values to default (see Tables 9 and 10
for default values):
1. Press and hold the + and - buttons prior to and during
power up.
2. When the display starts flashingdEF, release the buttons.
NOTE: R7426D controllers also have the DefProg (C.23)
parameter. Setting DefProg to 1 resets parameter
values to default.
Time out
After approximately 10 minutes of inactivity (no buttons
pressed) the controller automatically returns to standard
display mode. Inputs not yet confirmed by the SET button are
discarded and old parameter values retained.
Table 7. Standard Displays.
M17458
R7426A:
R7426B:
R7426C:
R7426D:
1
1
WHEN POWER IS APPLIED, THE
DISPLAY FLASHES MODEL CODE:
Display Description
I01 I01
CP.1 Main Setpoint CTRP1
I02 I02
CP.2 Limit/Cascade Setpoint CTRP2
I03 I03
%rh Humidity Deviation Xwrh
O1 Output 1
O2 Output 2
O3 Output 3
M17462
FREEZE
PROTECTION OFF
CONTROL MODE
NIGHT UNOCCUPIED OCCUPIED
+
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
9 63-2565
Selecting Output Values
Output selection mode displays the output value and indicates
manual overrides. An activated manual override is indicated
by a displayed F(fixed).
NOTE: Press the SET button to enter adjustment mode.
Output Manual Overrides
Use this mode for manual override. It is especially useful
during installation and setup:
1. Press and hold the SET and SEL buttons to display
output data selection mode.
2. Press + until the desired parameter is displayed.
3. Press SET to enter adjustment mode.
4. Use + and - to adjust the output to the desired value.
5. Return the controller to selection mode using either:
a. SET changes the output.
b. SEL discards the change.
6. To disable the manual override:
a. Repeat steps 2 and 3.
b. Press and hold + and - until the device displays rEL.
NOTE: Before exiting manual override, disable all
overrides according to step 6.
7. To exit manual override, press SEL.
NOTE: If necessary, repeat step 7.
TROUBLESHOOTING
Error Messages
Improper sensor inputs will trigger an error message to flash
on the display. (See Table 8.)
Table 8. Error Messages.
aFor CPATYP 0,1, or 2, the controller uses CPA value of 0 for
control point calculations.
For CPATYP 3, the controller uses SPA value equal to W1
for setpoint calculations.
Standard
Display Description
I01 E.01 Incorrect main sensor (I01) input.
I01 ––. –No input to I01.a
I02 E.02 Incorrect limit/cascade sensor (I02) input.
I02 ––. –No input to I02.a
I03 E.03 Incorrect compensation sensor (I03) input.
I03 ––. –No input to I03.a
E.04 Incorrect humidity deviation (Xwrh) input.
–––No input to Xwrh.
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
63-2565 10
APPENDIX
Control And Configuration Parameters
The controller includes two groups of settings (I and II) for
control and configuration parameters. These settings are
automatically selected duringprogramming. See Tables 9 and
10.
NOTES:
—For more details on parameters see the
Parameter Programming section.
—Parameter Ctrltyp determines the setting:
Ctrltyp Lo selects setting I.
Ctrltyp Hi1 and Hi2 select setting II.
Table 9. Control Parameters.
aValues in brackets are for R7426D models only.
bUnless otherwise noted.
cIf tr is greater than 120 sec, resolution is 30 sec; if tr is less than 120 sec, resolution is 10 sec.
R7426 Parameter
Descriptiona
Setting I / Setting II
ResolutionaUnita,b
ABCD # Name Low
aHighaDefaulta
xxxxP.01W1 I01mainsetpoint 32[0] 130/260[100] 70/160[50] 1[0.5] °F [%]
xxxxP.02W
lim I02 limit setpoint (low or high) 40 [0] 130/260 [100] 60/200 [90] 1
xxxxP.03W
comp I03 compensation changeover point 20 110 70 1 °F
xxxxP.04Wi Winterreset -350 +350 0 2 %
xxxxP.05Su Summerreset -100[-350]+100[+350] 0 1[2]
xxxxP.06W
cas Submaster or cascade setpoint Off, 50
[Off, 0] 260 [100] 70 [Off] 1 [0.5] °F [%]
xxxxP.07R
cas Cascade reset span adjustment 0 70 [50] 20 [10]
xxxxP.08Xp1 I01Throttlingrange (main control
loop) 1 70 [50] 4 [10]
xxxxP.09Xp2 I02Throttlingrange (cascade or limit
control loop) 1 70 [50] 20 [10]
x x P.10 Xpc Cooling throttling range (sequence
control) Off, 1 70 6 1 °F
x x P.11 Xph Heating throttling range (sequence
control) 170 12
xxxxP.12tr1cReset time (main control loop) Off, 20 20 minutes Off 10 (0.5 min) sec
xxxxP.13tr2cReset time (cascade control loop)
x x P.14 MINPOS Minimum position (damper
actuators) 050 201 %
xxxxP.15O
start Mid-range shift start point (O1) -40 [-50] +40 [+50] 0 1 [0.5] °F [%]
x x x P.16 SOFFS Main setpoint offset (standby mode) 0 20 4 / 10 0.1 °F
xxxxP.17I01Cal CalibrationofsensorI01 -40[-20] +40[+20] 0 0.1 °F [%]
xxxxP.18I02Cal CalibrationofsensorI02
xxxxP.19I03Cal Calibrationoftemperaturesensor
I03
x x P.20 RetOffs Return air offset to simulate exhaust
air conditioning Off, 0 10 Off 0.1 °F
x x P.21 RuntimeO1 Actuator run time (O1) 6 180 60 1 sec
x P.22 RuntimeO3 Actuator run time (O3)
x P.23 RuntimeO2 Actuator run time (O2)
x P.27 td Derivative decay time (P+I+D
control) 160 1
x P.28 vd Derivative amplification (P+I+D
control) 05 0 0.1—