SM1911M Us e r Ma nual http://www.sonbus.com/
Sha nghaiSonbest Industrial Co., Ltd Page3
(80-(-30))*(12-4)÷ (20-4)+-30
(80-(-30))*(13-4)÷ (20-4)+-30
(80-(-30))*(14-4)÷ (20-4)+-30
(80-(-30))*(15-4)÷ (20-4)+-30
(80-(-30))*(16-4)÷ (20-4)+-30
(80-(-30))*(17-4)÷ (20-4)+-30
(80-(-30))*(18-4)÷ (20-4)+-30
(80-(-30))*(19-4)÷ (20-4)+-30
(80-(-30))*(20-4)÷ (20-4)+-30
As shown in the above formula, when measuring 8mA, current current is 31.5℃。
2. humidity and current computing relationship
For example, the range is 0~100%RH, the analog output is 4~20mAcurrent signal, humidity and
current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where
A2 is humidity range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1
is the lower limit, X is the currentlyread humidity value, and C is the calculated current value. The list of
commonly used values is as follows:
As shown in the above formula, when measuring 8mA, current current is 29%RH。
Disclaimer
This document provides all information about the product, does not grant any license to intellectual
property, does not express or imply, and prohibits any other means of granting any intellectual property
rights, such as the statement of sales terms and conditions of this product, other issues. No liability is
assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use
of this product, including the suitability for the specific use of the product, the marketability or the
infringement liability for any patent, copyright or other intellectual property rights, etc. Product
specifications and product descriptions may be modified at any time without notice.