2FCP-500 Series
Table 4: Technical Data (continued)
Maximum Thickness of False Ceiling 1.25 in. (32 mm), flush mount applications only
Minimum Clearance for False Ceiling 6in. (15.2 cm)
Required Hole 5-1/16 in., tolerance -1/16 in. to +3/16 in.
(130 mm, tolerance -1 mm to +5 mm)
Minimum Distance from Lamps 1.6 ft (0.5 m)
Maximum Airflow 300 ft/min (1.5 m/s)
Operating Temperature +32 _Fto +100 _F(0_Cto+38_C)
Humidity <95%, non-condensing
Protection Class as per IEC 60529
- FCP-500-C and FCP-500-C-P IP 33
- FCP-500 and FCP-500-P IP 53
Dimensions
-Detectoronly 4.5 in. x2.2 in. (113 mm x55 mm)
- Detector with Trim Ring 5.9 in. x2.2 in. (150 mm x55 mm)
- Detector with Trim Ring and Base 5.9 in. x2.75 in. (150 mm x70 mm) with base
Compliance UL 268
2. Installation Considerations
iFor proper installation, read and understand NFPA-72, The National Fire Alarm Code be-
fore installation.
Caution:
DDo not remove the plastic film from the detector head until construction of the installation area is
finished.
DProtect the detector sensor windows from paint or contaminates. Remove the detector head during
remodelling and store it in aclean dry location.
.If you do not follow these cautions, the detector might not operate.
Detector Location and Spacing:
DBOSCH recommends spacing the sensors in compliance with NFPA-72. In low air flow applications with
smooth ceilings, space sensors with amaximum distance of 30 ft. For specific information regarding
sensor spacing, placement and special application refer to NFPA-72.
DNot suitable for outdoor use.
DDo not install in areas where the detector is pointed at
direct or indirect sunlight.
DDo not mount detector in acone of light from alamp.
DMaintain ahemispherical radius of at least 19 in.
(50 cm) around the detector (see Fig. 1.).
Insure that this area in front and to the sides of the
detector is kept clear of all obstructions (see Fig. 1.).
Further Considerations:
DOnly use end-of-line (EOL) resistors supplied or specified by the control panel manufacturer.
DSmoke detectors are not to be used with detector guards unless the combination has been evaluated and
found suitable for that purpose.
DThis detector must be installed in compliance with the control panel system installation manual.
DInstall, test and maintain this device according to this installation guide, NFPA-72, Local Codes and the
Authority Having Jurisdiction (AHJ). Failure to follow these procedures may cause the device to not
function properly. Bosch Security Systems is not responsible for any devices that are improperly
installed, tested or maintained.
Detector
19 in.(50 cm)
Ceiling
Free space
Fig. 1.
BDL-F01U000626 |A7 |2007.07 Bosch Security Systems