Sonniger INTELLIGENT eco User manual

INTELLIGENT Control Panel Manual v202205
INTELLIGENT controller manual
SONNIGER S.A.
ul. Śląska 35/37, 81-310 Gdynia, Poland, infolinia 801 055 155, tel. + 48 58 785 34 80, www.sonniger.com
Sąd Rejonowy Gdańsk-Północ, VIII Wydział Gospodarczy Krajowego Rejestru Sądowego,
KRS 0000966611, NIP 586 227 35 14,Regon 22154369 kapitał zakładowy: 1.655.000 PLN

INTELLIGENT Control Panel Manual v202205
1. PURPOSE
The INTELLIGENT panel is designed to control the operation of water heaters and air curtains. The controller pilots the functioning
of actuators/valves and fan speed of the heater in manual and automatic modes depending on the set room temperature. The
fan gear automatically changes to a lower one when reaching the set temperature in the room. The INTELLIGENT panel has the
possibility of using a programmed weekly temperature schedule and communicating with BMS systems in the ModBUS RTU
protocol.
The INTELLIGENT panel is compatible with the Tuya Smart mobile app, which allows the user to control and create settings via
an iOS or Android smartphone. The app's control function requires a WiFi network at the controller's location.
The possible connection of an external NTC temperature sensor, allows to extend the cable up to 20 mb.
The device does not include: the main switch of the device, fuses and power cable
One INTELLIGENT control panel can operate 2 HEATER CONDENS device.
For HEATER CONDENS CR ONE models, up to 4 units can be operated.
for HEATER CONDENS CR MAX models possibility to operate 1 unit.
for GUARD models possibility of operating up to 2 units.
1.1. SPECIFICATIONS
Power supply 230VAC/50Hz
Panel panel with buttons/ LCD display
Temperature control range +5 ÷ +40°C
RPM adjustment range 3 steps
Operating temperature range 0 ÷ +50°C
Storage temperature -10 ÷ +60°C
Temperature sensor built-in/external NTC (option)
IP 20
Mounting surface mounted
Housing ABS & Acrylic
Weekly programmer ON: 5 days+2 days, OFF.
1.2. DIMENSIONS
2. CONTROL PANEL INTELLIGENT
2.1. DESCRIPTION OF BUTTONS
1. MODE - operation mode
2. FAN - fan operation speed
3. ON/OFF - switch
4. + - increase the set temperature
5. - - decrease the set temperature

INTELLIGENT Control Panel Manual v202205
6. fan speed
7. room temperature
8. set temperature
9. cooling operation mode
10. operation mode heating
11. day of the week
12. time
13. controller lock
14. on/off in schedule
15. operation according to schedule
16. manual operation
17. schedule operation interval
18. antifreeze mode
19. ventilation mode
20. synchronization of settings with the ap-
plication
21. connection to the Internet
3. FUNCTIONS AND MODES
3.1. MODES OF OPERATION
MANUAL MODE - The fan operates at the selected speed (I, II, III) and according to the selected mode of operation:
heating, cooling and ventilation. The device works according to the set temperature
AUTOMATIC MODE - the fan speed is set automatically depending on the difference between the preset temperature
and the room temperature (it is not possible to change the fan speed manually).
3.2. METHOD OF WORK
HEATING - if the set temperature < room temperature, the valve is open and the fan runs
COOLING - if the set temperature > room temperature, the valve is open and the fan runs
VENTILATION - the fan is on and runs at a pre-set gear regardless of the temperature. TERMOSTAT ANTIFREEZ
When the temperature sensor detects a temperature drop below 5°C (the default value), it immediately opens the valve and
starts the fan, even if the controller is turned off.
4. MENU
4.1. PARAMETER SETTINGS
When the controller is off, hold down the MODE buttons for 3 seconds.
Use the MODE button to change options.
Use the +/- buttons to change the value.
Menu Preset Option Value
1 Temperature calibration -9°C ~ +9°C
2 EEPROM 0: not memorized
3 Operation mode 1: memorized
4 Sensor selection C1: Thermostatic operation mode
5 Antifreeze C2: Continuous operation mode
6 Antifreeze setting range 0: Internal sensor
7 ALARM signal 1: External NTC
8 Potential-free contact setting 0: Off
9 MODBUS functions 1: On
10 BMS speed +5°C ~ +15°C
11 BMS Protocol Settings 1~247 (01~F7)

INTELLIGENT Control Panel Manual v202205
4.2. BUTTON LOCK
To LOCK all buttons, press the + then - button and hold both for 5 seconds.
To UNLOCK all buttons press the + then - button and hold both for 5 seconds.
4.3. CLOCK SETTINGS
When the INTELLIGENT controller is off, press and hold the FAN button for 3 seconds then enter the clock settings.
The order of options is as follows: hour / minute / day of the week.
Press the FAN button to change the options.
Use the + and - buttons to change the values.
4.4. OPERATION MODE SETTINGS
Press the MODE button to select the mode: manual or automatic mode.
Press and hold the MODE button for 3 seconds to select the operation mode: heating, cooling, ventilation.
4.5. FAN SPEED SETTING
Press the FAN button briefly to select the fan speed: I, II, III, AUTO.
4.6. WEEKLY PROGRAMMER
Press and hold the FAN button for 3 seconds to start programming the programmer
Monday - Friday
First zone time setting (hour and minute) -> FAN -> First zone status setting (ON / OFF) -> FAN -> First zone temp. setting ->
FAN -> move to next zone
Sixth zone time setting (hour and minute) -> FAN-> Sixth zone status setting (ON / OFF) -> FAN-> Sixth zone temp. setting.
Saturday
First zone time setting (hour and minute) -> FAN -> First zone status setting (ON / OFF) -> FAN -> First zone temp. setting ->
FAN -> Move to next zone
Sixth zone time setting (hour and minute) -> FAN-> Sixth zone status setting (ON / OFF) -> FAN-> Sixth zone temp. setting.
Sunday
First zone time setting (hour and minute) -> FAN -> First zone status setting (ON / OFF) -> FAN -> First zone temp. setting ->
FAN -> Move to next zone
Sixth zone time setting (hour and minute) -> FAN -> Sixth zone status setting (ON / OFF) -> FAN -> Sixth zone temp. setting.
Example settings
Mon - Fri Saturday Sunday
S T S T S T
Time zone
1 06:00 ~ 08:00 ON 22°C ON 26°C ON 26°C
2 08:00 ~ 15:30 ON 24°C ON 24°C ON 24°C
3 15:30 ~ 20:30 ON 22°C ON 22°C ON 22°C
4 13:30 ~ 17:00 OFF 22°C ON 22°C ON 22°C
5 17:00 ~ 22:00 OFF 22°C ON 24°C ON 24°C
6 22:00 ~ 06:00 ON 18°C ON 24°C ON 24°C
5. BMS COMMUNICATION
Physical layer
RS485
Protocol
MODBUS-RTU
Baud rate [bps]
0-2400 / 1-9600 / 2-19200
Parity
Even
Number of data bits
8
Number of stop bits
1
IMPORTANT!
If a problem with the temperature sensor occurs, an error message will be displayed: E0.

INTELLIGENT Control Panel Manual v202205
6. SETUP
Remove the lid from the control panel.
Screw into a flat surface.
Attach the control panel to the bolted lid.
7. ELECTRICAL CONNECTION SCHEME
At the end of every wire there must be an isolated sleeve ,
Wire thickness must be attuned by designers
The dimension of the power cord must be min. 2 x 1 mm2.
Before switching the panel on, make sure the lid is tightly closed.
IMPORTANT!
Remember to unplug the control panel before the installation. The control panel shall be mounted 1,5m above
the floor in a location with good air circulation. The panel may not be mounted near to any heat sources, lighting, air
vents, widnows or doors.
IMPORTANT!
RISK OF ELECTRIC SHOCK. Before any electrical connection actions conceringt the INTELLIGENT control panel,
switch off any power suplies

INTELLIGENT Control Panel Manual v202205
8. The TUYA SMART mobile app
The Tuya Smart application allows to create and modify settings of the INTELLIGENT panel with any smartphone using an
Adroid/iOS software. The application may be downloaded via the QR Code presented below.
8.1. ADDING A CONTROL PANEL
a) Connect the control panel to voltage and the heating device, the panel must be switched off
b) Turn on TUYA Smart and follow the instruction in the app.
c) While connecting, turn on Bluetooth and WI-FI in you smartphone, and then launch TUYA Smart
d) To connect the device, hold twice the “+” buton on the panel, 5 seconds before the SA notification appears on the left
side of the screen.
e) Choose the option “Add a device”, the app should detect it, then press “Add”, and after finishing the configuration press
“Next” and “Finish”
f) In case there is no “Add” function, choose “Small Devices” and the function “Termostat (Wi-Fi)”. Nextly enter the data
required to grant access to the chosen WI-FI connection , then choose “Blikn slowly”.
g) A screen with the list of detected devices will appear. After detecting the controller, the connecting proces will proceed
automatically. When the configuration is complete, press „Next” and ”Finish”.

INTELLIGENT Control Panel Manual v202205
8.2. BASIC FUNCTIONS
8.3. CREATING A GROUP OF CONTROL PANELS
a) In Tuya Smart choose the paired control panel then select the symbol next to the controller’s name. A menu will open,
where the option „Create a group” must be picked.
b) After selecting the devices and confirming it with „Save” the group of controlles can be
customized and saved. When it is succesfully created, the group will be displayed on the top of the devices list.
ON/OFF
Mode
Fan speed
Actual mode Actual fan speed
Chosen tem-
perature
Room
tempera-
ture
Increase the chosen
temperature
Decrease the chosen
temperature
Manual work
Scheduled work
mode

INTELLIGENT Control Panel Manual v202205
8.4. SCHEDULE SETUP
a) When launching Tuya Smart, select the group of control panels for which we want to create the Schedule
b) On the parameter screen, pick the knob icon, after that press „title”. A list of time schedules to customize will appear on
the screen. After setting up the time schedule and temperatures, return to the main screen.
c) To make the device function according the the schedule, select the
„Automatic” function on the main panel
9. MODBUS PROTOCOL ADRESSES
9.1. Operation format for thermostat Read and Response:
*Command (Master to read/response status of thermostat)
Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8
Thermostat
address 0x03
Fetch Starting
address- Hi
Fetch Starting
address- Lo
Fetch Number of
Registers- Hi
Fetch Number of
Registers- Lo
CRC
-
Lo
CRC
-
Hi
*Response (thermostat sends out)

INTELLIGENT Control Panel Manual v202205
Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 ……
Thermostat
address 0x03
Numbers of
Response
Data
The First Re-
sponse Reg-
isters-Hi
The First Re-
sponse Regis-
ters- Lo
……
The N
th
Re-
sponse Reg-
isters-Hi
The N
th
Re-
sponse Reg-
isters- Lo
CRC-
Lo
CRC-
Hi
9.2. Thermostat Pre-Settings
* 1st Command(The master sends out) Thermostat Pre-Setting(Single Register)
Bit 1 Bit 2 Bit 3 Bit 4 Bit5 Bit 6 Bit 7 Bit 8
Thermostat
Address 06
Preset Starting
address -Hi
Preset
Starting
address- Lo
The 1
st
Preset
Value-Hi
The 1
st
Preset
Value-Lo CRC_Lo
CRC
-
Hi
* Response(Thermostats send out)
Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8
Thermostat Ad-
dress 06
Preset Starting ad-
dress -Hi
Preset Starting ad-
dress-Lo
Preset Va-
lue-Hi
Preset Value
-
Lo CRC-Lo
CRC
-
Hi
9.3. Thermostat Parameters Status Instruction
Byte Instruction Related Register
Address
Bit 0
On/off Flag
-
Hi is 0
0000H
Bit 1
On/off Flag
-
Lo: 0
-
Thermostat Off;1
-
Thermostat On
Bit 2
Ro
om Temperature Measurement
-
Hi:(
Hi and Lo bytes stand for measured room temperature)
0001H
Bit 3
Temperature Measurement
-
Lo: Register Data/10(0~500 stands for temperat
ure range from 0.0
~50.0 degC) (Read only)
Bit 4
Set Temperature
-
Hi (
Hi and Lo bytes stand for Setpoint)
0002H
Bit 5
Set Temperaute
-
Lo: Register Data/10(50~400 stands for temperature range from5.0 ~40.0
degC
Bit 6
00
0003H
Bit 7
Temperature Calibration
-
Lo:
-
90~90 stands for calibration range from
-
9.0 to 9.0 degC
Bit 8
00
0004H
Bit 9 Mode-Lo(Bit 1,0):00.Cooling 01 Heating 10. Ventilation
Bit 10
00
0005H
Bit 11
Sensor selection:0
-
Internal Sensor; 1
–
External Sensor
Bit 12
00
0006H
Bit 13
Status of Output
(Read only): 0
-
Low Speed 1
-
Medium Speed 2
-
High Speed 4
-
Fan off
Bit 14
00
0007H
Bit 15 Button Lock-Lo (Optional):0 buttons unlock;1 buttons locked (without LOCK function, re-
sponse is 0)
Bit 16
00
0008H
Bit 17
Anti
-
freeze function: 0
-
Disable 1
-
Enable
Bit 18
Anti
-
freeze Temperature
-
Lo: Register Data/10
(50~100 stands for temperature range from5.0
~10.0 degC 0009H
Bit 19
Anti
-
freeze Temperature
-
Hi: Hi and Lo bytes stand for Setpoint
Bit 20
00
000AH
Bit 21 Time Setting(optional):Hour 00~23 (BCD code)
Bit 22
00
000BH
Bit 23 Time Setting(optional):Minute 00~59 (BCD Code)
Bit 24
00
000CH

INTELLIGENT Control Panel Manual v202205
Bit 25 Time Setting(optional):Weekday 01~07 (BCD Code)
Bit 26
00
000DH
Bit 27
C1,C2 :0
-
C1 1
-
C2
Bit 28
00
000EH
Bit 29
Fan Speed setting: 1
-
Low Speed 2
-
Medium Speed 3
-
Hi Speed 4
-
Auto
Bit 30
00
000FH
Bit 31
Working Modes: 00 Auto Mode 01 Manual Mode 10 Temporary Manual Mode
Bit 32
00
0010H
Bit 33
Valve’s(Device) Open/Close Feedback:0
-
Disable 1
-
Enable
Bit 34
00
0011H
Bit 35
Valve’s(Device) Feedback Output: 0 Normally Close 1 Normally Open
Bit 36
00
0012H
Bit 37
Status of Output( Read only):0
-
Valve off 1
-
Valve on
Bit 38
00
0013H
Bit 39
Practical Status of Output:0 Open 1 Close 2. Unknow(If Open/Close Feedback function is
disable)
Bit 40
00
0014H
Bit 41
Feedback Alarm: 0 Enable 1 Disable
Bit 42
Modbus Version
-
Hi 0x0A~0x0F(Read only)
0015H
Bit 43
Modbus Version
-
Lo 0
x01~0x00(Read only)
Bit 44
Part No of Modbus Verison
-
Hi 0x00 (Read only)
0016H
Bit 45
Part No of Modbus Verison
-
Lo 0x10~0x99(Read only)
Table of contents
Popular Control Panel manuals by other brands

DSC
DSC PC5020 installation manual

Bosch
Bosch HPC 400 Installation instructions for contractors

Exodraft
Exodraft EW 41 quick guide

GRD Systems
GRD Systems Asteria user manual

InterPuls
InterPuls ACR Smart Instruction Manual, Operation and Maintenance original instructions

merten
merten U.motion Client Touch 7 Technical manual