Colima Tor
Magnetic Level Switches
Installation and Maintenance Instructions

23.793.5275.200

3
3.793.5275.200
1. Safety information
Safe operation of these products can only be guaranteed if they are properly installed,
commissioned, used and maintained by qualied personnel (see Section 1.11) in compliance
with the operating instructions.
General installation and safety instructions for pipeline and plant construction, as well as the
proper use of tools and safety equipment must also be complied with.
1.1 Intended use
Referring to the Installation and Maintenance Instructions, name-plate and Technical Information
Sheet, check that the product is suitable for the intended use/application.
These products comply with the requirements of the European Pressure Equipment Directive
2014/68/EU (PED) falling within category 'SEP'. It should be noted that products within this category
are required by the Directive not to carry the mark.
Products intended for use in the Naval and Marine sectors are RINA, and M.M.I (Italian navy) approved.
i) The products have been specically designed for use on steam, compressed air and inert
industrial gases which are in Group 2 of the above mentioned Pressure Equipment Directive.
The products’ use on other uids may be possible but, if this is contemplated, Spirax Sarco
should be contacted to conrm the suitability of the product for the application being considered.
ii) Check material suitability, pressure and temperature and their maximum and minimum values.
If the maximum operating limits of the product are lower than those of the system in which
it is being tted, or if malfunction of the product could result in a dangerous overpressure or
overtemperature occurrence, ensure a safety device is included in the system to prevent such
over-limit situations.
iii) Determine the correct installation situation and direction of uid ow.
iv) Spirax Sarco products are not intended to withstand external stresses that may be induced
by any system to which they are tted. It is the responsibility of the installer to consider these
stresses and take adequate precautions to minimise them.
v) Remove protection covers from all connections and protective lm from all name-plates, where
appropriate, before installation on steam or other high temperature applications.
1.2 Access
Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting
to work on the product. Arrange suitable lifting gear if required.
1.3 Lighting
Ensure adequate lighting, particularly where detailed or intricate work is required.
1.4 Hazardous liquids or gases in the pipeline
Consider what is in the pipeline or what may have been in the pipeline at some previous time.
Consider: ammable materials, substances hazardous to health, extremes of temperature.
1.5 Hazardous environment around the product
Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of
temperature, hot surfaces, re hazard (e.g. during welding), excessive noise, moving machinery.
These products comply with the requirements of the European Directive 2014/34/EU (ATEX) for the
use of equipment in potentially explosive atmospheres.

43.793.5275.200
1.6 The system
Consider the eect on the complete system of the work proposed. Will any proposed action
(e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel
at risk?
Dangers might include isolation of vents or protective devices or the rendering ineective of controls
or alarms. Ensure isolation valves are turned on and o in a gradual way to avoid system shocks.
1.7 Pressure systems
Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double
isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that
the system has depressurised even when the pressure gauge indicates zero.
1.8 Temperature
Allow time for temperature to normalise after isolation to avoid danger of burns and consider whether
protective clothing (inlcuding safety glasses) is required.
1.9 Tools and consumables
Before starting work ensure that you have suitable tools and/or consumables available. Use only
genuine Spirax Sarco replacement parts.
1.10 Protective clothing
Consider whether you and/or others in the vicinity require any protective clothing to protect against
the hazards of, for example, chemicals, high/low temperature, radiation, noise, falling objects, and
dangers to eyes and face.
1.11 Permits to work
All work must be carried out or be supervised by a suitably competent person. Installation and
operating personnel should be trained in the correct use of the product according to the Installation
and Maintenance Instructions. Where a formal 'permit to work' system is in force it must be complied
with. Where there is no such system, it is recommended that a responsible person should know what
work is going on and, where necessary, arrange to have an assistant whose primary responsibility
is safety. Post 'warning notices' if necessary.
1.12 Handling
Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling,
carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised
to assess the risks taking into account the task, the individual, the load and the working environment
and use the appropriate handling method depending on the circumstances of the work being done.
1.13 Residual hazards
In normal use the external surface of the product may be very hot. If used at the maximum permitted
operating conditions the surface temperature of some products may reach temperatures of 350°C.
Many products are not self-draining. Take due care when dismantling or removing the product from
an installation (refer to 'Maintenance instructions').
1.14 Freezing
Provision must be made to protect products which are not self-draining against frost damage in
environments where they may be exposed to temperatures below freezing point.
1.15 Disposal
This product is recyclable. No ecological hazard is anticipated with the disposal of this product
providing due care is taken.

5
3.793.5275.200
1.16 Returning products
Customers and stockists are reminded that under EC Health, Safety and Environment Law, when
returning products to Spirax Sarco they must provide information on any hazards and the precautions
to be taken due to contamination residues or mechanical damage which may present a health,
safety or environmental risk. This information must be provided in writing including Health and Safety
data sheets relating to any substances identied as hazardous or potentially hazardous.

63.793.5275.200
2. General product information
2.1 Description
The Colima TOR magnetic-activated level switch is designed to control the liquid levels in most
industrial applications. The unit comprise of a rigid rod for vertical installation that is used for full
automatic management of tanks (including pressurised ones) allowing operations such as starting /
stopping of pumps, opening /closing of solenoid valves and activation of alarm systems.
One unit can be used with up to six switching points or with a potentiometer transmitter for a
continuous reading of the level.
Mounting - The Colima TOR magnetic level switch is designed for top mounting directly to the tank.
It can be installed vertically directly into the tank, or externally into a chamber connected to the tank.
Standards and certication - The Colima TOR magnetic level switch complies with the following
European Directives:
- 2014/68/EU (PED)
- 2014/34/EU (ATEX)
- Products intended for use in the Naval and Marine sectors are RINA, and M.M.I (Italian navy) LL RR.
-Gost-R approved
2.1.1 Operation
The level switch is secured to the tank by means of a ange or a thread. One or more magnetic
contacts (reed switches) or a reed switch "chain" potentiometer transmitter are placed inside a sealed
vertical tube, joined to the locking system.
Contacts
One or more oat(s), free to slide along the guide tube depending on the liquid level inside the tank,
acting magnetically on contacts placed at the operation point, switching their status from NO to NC
or vice versa.
The switching of the electrical contact is quick and reliable.
Switching points are always eld adjustable, except for TOR-CD.
Transmitter
A oat, free to slide along the guide tube depending on the liquid level inside the tank, acts magnetically
on the transmitter. The level is continuously transmitted.

7
3.793.5275.200
2.3 Design conditions
TMA Maximum
allowable temperature
Steel -110°C to +200°C
Buna N -20°C to + 80°C
Plastic
PVC -20°C to + 70°C
PP -20°C to + 105°C
PVDF -20°C to + 130°C
PMA Maximum
allowable pressure
Steel < 100 bar g
Buna N < 16 bar g
Plastic < 16 bar g
Fluid specic gravity Steel and plastic > 0.8 kg/l
Buna N / Titanium > 0.5 kg/l
Dierential xed 8 mm
Materials and sizing are dened in relation to the characteristics of the liquid and the project conditions.
Rod length
Minimum length 100 mm
Maximum length 5 000 mm
2.2 Materials
No. Part Material
1Housing Aluminium Epoxy coated / Stainless steel
2a Terminal board Melamina
2b 4 - 20 mA output converter Plastic
3/4 Flange or thread
304 / 316L / PVC / PP / PVDF
Lowest applicable nominal diameter 50 mm (2")
with nominal pressure related to design needs.
5Tube and wetted parts 316L / PVC / PP / PVDF
6Float 316L / Titanium / Monel / Hastelloy / PVC / PP / PVDF / BunaN
7a Contact SPST-SPDT or DPDT ermetically sealed, golden plated
7b Transmitter chain (not shown) SPDT ermetically sealed, golden plated, pitch 5-10-20 mm
8Chamber (not shown) A105 / 304 / 316L
2a
1
3
5
7a or 7b
6
2b
4

83.793.5275.200
Models:
TOR A
Type recommended for most industrial applications.
All wetted parts are made totally of stainless steel.
Equipped with reed switches, which allows control of up
to six switching points with a single instrument. Equipped
with a potentiometer transmitter allowing continuous
reading of liquid level.
TOR B
Type recommended for liquids with low specic weight
such as hydrocarbons and mineral oils.
Floats in BUNAN, the other wetted parts are made totally
of stainless steel. Equipped with reed switch contacts,
which allows the control of up to six switching points
with a single instrument.
Equipped with a potentiometer transmitter allowing the
continuous reading of the liquid level.
TOR CD
Compact type, recommended for applications in
hydraulic control units.
It can also be used with liquids with low specic weight
such as hydrocarbons and mineral oils.
Stainless steel or BUNA N oats, the other wetted parts
are made of stainless steel. Can be equipped with reed
switch contacts, allowing control of up to two switching
points with a single instrument.
In place of the housing, a three-pin DIN connector with
ying plug is used.

9
3.793.5275.200
TOR PC
Type indicated for corrosive liquids, such as acids
and brines, where the use of stainless steel is not
recommended. All wetted parts are made totally of
PVC-Polyvinylchloride. Equipped with reed switch
contacts, PC allows the control of up to six switching
points with a single instrument.
Equipped with a potentiometer transmitter allowing the
continuous reading of the liquid level.
TOR PP
Type indicated for corrosive liquids, such as acids
and brines, where the use of stainless steel is not
recommended. All wetted parts are made totally of
PP-Polypropylene. Equipped with reed switches, which
allows control of up to six switching points with a single
instrument. Equipped with a potentiometer transmitter
allowing continuous reading of liquid level.
TOR PF
Type indicated for corrosive liquids, such as acids
and brines, where the use of stainless steel is not
recommended.
All wetted parts are made totally of PVDF-Polyvinylidene
uoride. Equipped with reed switch contacts, which
allows control of up to six switching points with a single
instrument . Equipped with a potentiometer transmitter
allowing continuous reading of liquid level.

10 3.793.5275.200
TOR FL (Free Wires)
Model FL is designed for naval applications. Float built
in stainless steel or BUNA N; other wetted parts built in
stainless steel. Model FL can be tted only with reed
switch contacts, with a single tool allows to control up to
three xed switching points. The FL is not equipped with
housing. A sheath of heat-shrinkable material protects
the output cable. The enclosure rating is IP67.
TOR A or B in Chamber (TOR C)
TOR A and TOR B (C Version) are provided with
restraint chamber, for installations external to the tank,
according to the European Directive 2014/68/EU (PED).
The C type is designed to show local fluid level is
also available a sight glass, on request. Floats are
built in stainless steel or BUNA N, connections to the
process and chamber camera in ASTM or AISI 316.
Fittings with reed switch contacts, to control up to
three switching points with a single tool. The C type
is fitted with potentiometric transmitter, allows the
continuous reading of the liquid level.
On request, it is possible the simultaneous
presence of reed-switches and transmitter, placed
on two separate rods.
TOR M (Metric)
M Model is designed for applications on tanks that
are not provided with level gauge and which requires
manual and visual reading of the level. The level reading
is achieved using a scale tape inserted into the rod:
slowly pulling out the tape, it is possible to detect the
liquid level through the interaction of the magnet of the
oat and the magnet on the bottom of the graduated
tape. Floats are built in stainless steel or BUNA N, other
wetted parts built in stainless steel.

11
3.793.5275.200
TOR S
Type S is designed for applications in naval bilges to
control oily and saline wastewater. It is also serviceable
in hardly accessible compartments, where is necessary
to detect the presence of liquids. Fittings with reed
switch contacts, SPDT or 1 DPDT, to control a single
switching point. TOR S is not equipped with housing.
A sheath of heat-shrinkable material protects the NFO
output cable. The enclosure rating is IP68
TOR Bistable
TOR Bistable is a model designed for external mounting
on magnetic sensor level gauges. It is not provided with
oat, since the switching state of the contact is performed
by the indicator’s magnetic oat.
Compliance to the European Directive 2014/34/EU (ATEX) is full only for TOR A, TOR B and
TOR Bistable models.
For all other models, compliance (when required) is limited to the housing and therefore only
for electrical parts.

12 3.793.5275.200
3. Installation and Maintenance
Note: Before actioning any installation or maintenance work
observe the 'Safety information' in Section 1.
Refering to the Installation and Maintenance Instructions, name-plate and Technical Information
Sheet, check that the product is suitable for the intended installation.
Check: materials, pressure and temperature to ensure compatibility of the product with the required
application. If the product’s maximum operating limit is lower than the one in the system where the
Colima TOR will be mounted. Also check if the environmental temperature around the device is
between the values declared on the label (-20÷40°C).
Remove protective covers from all connections and the protective lm from the name-plate.
3.1 Assembly
The Colima TOR magnetic level switches are delivered packed.
Caution before installation disassemble the lower flange and remove the float from its
package + Conrm the presence of supplied gaskets.
3.1.1 Fit the level switch in the tank paying attention to avoid any damage to the oat.
Any damage of the oat can interfere with the correct operation of the unit.
3.1.2 Place the supplied gaskets between the anges or thread.
3.1.3 Flange mount: Place the supplied gasket between the anges. Fix the anges with bolts.
Firmly secure the xing by tightening the ange bolts.
Thread mount: Place the gasket in seat, for cylindrical thread or use PTFE tape on conical
thread. Firmly secure the xing by tightening with a wrench.
3.1.4 Ensure that there is nothing stopping the correct operation of the oat.
3.1.5 Open the unit housing and connect the wiring at the terminal board.
The housing has two cable entry points: G ½" F, Explosion-proof Gk ½" F, ½" NPT F,
M 20 x1.5, PG 13.5 (only for Waterproof and Explosion-proof versions).
Caution: Always ensure that correct earthing of the equipment is carried out. Specic points are
set inside and outside the housing.
Explosion-proof housing operating limits
Technical data Class I: simple protective-earth connection requirement
Torques of the cover = 40Nm
Employment data for potentially explosive atmospheres
Ambient temperature limits -20°C to +50°C
Marking II 1/2 GD EEx d IIC T6 Ga/Gb
EEx tb IIIC T85°C Da/Db Ia
Temperature class T6 T4
Permitted temperature variation range -20°C to +40°C -20°C to +80°C
Suitability for the area of: 0, 1, 2, GAS Group II (European Directive ATEX 1999/92/EC)
Protection degree IP66 / IP67
Warning:
1. Do not make any modication to the housing. Any alterations or modications to the product will
invalidate any warranties, explosion proof characteristics and any marking.
2. Install at the inlet of the housing a suitable xing or locking device with lling material.
The absence of these components will result in the loss of responsibility by the manufacturer.
3. These products should only be used for the purpose they were designed for. Anything outside
of the stipulated application range may be subject to unforeseen and dangerous circumstances
and full responsibility will be with the installer.
4. Any accessories used for cable entries and for closing unused apertures shall be certied
according to EN 60079-0, EN 60079-1, EN 61241-0, EN 61241-1 and be at least IP66 / IP67.

13
3.793.5275.200
3.1.6 Wiring: to connect the SPDT or DPDT contact.
8 9 10 11 12 13 14
Identication numbers wiring diagrams

14 3.793.5275.200
Contact characteristics
Reed- Switch SPDT or SPST contact
Also available DPDT (two SPDT simultaneous)
Switching capacity 60 VA 30 W
Switching current (I peak) 1 A
Switching voltage 230 V ~ / 110 V =
4.1 Maximum number of contacts per instrument
The terminal board inside the housing can connect a maximum number of 18 cables.
Each contact has the following number of wires:
3 wires in SPDT contacts
6 wires in DPDT contacts
The various possible combinations of contacts must be taken into account - Example of how many
contacts can be installed in one instrument:
6 SPDT
or
2 SPDT + 2 DPDT
or
4 SPDT + 1 DPDT etc.
Note: for housing in AISI, the maximum number of contacts is 2 SPDT or 1 DPDT.
4. Contacts
SPDT execution
Contacts in series Independant contacts
DPDT execution
(two simultaneous SPDT contacts)
Independant contacts
Flange
Thread

15
3.793.5275.200
4.2 How to adjust switching point:
1. Disconnect all of the electrical connections.
2. Remove the unit from the tank and lay it carefully on a at surface.
3. Remove the cover.
4. Disconnect the wires from the terminal board and unscrew the metallic plate located over the
terminal board, using the supplied tool. Note: taking note of the original position of the wires
in the terminal board.
5. Slowly remove the wires and berglass support. Caution be careful not to break the reed switch
contacts.
6. Unscrew the terminal board screws (1). Sliding the berglass support (2) move the reed switch
contact to the new switching point.
7. Firmly x the screws into the new position.
8. Re-insert berglass support and wires inside the tube, then connect wires to the terminal board
and block them using the specic metal plate.
9. Now move the oat position. Unscrew the ring screw (3and 4). Check new switching point
by moving the oat up to the new position making sure to leave a gap of between 5 mm and
20 mm following the oat direction (see Aand B).
10. Using a multimeter (tester), double check the new switching position by moving the oat to the
switching point.
11. Connect the wires to the terminal board.
12. Close the housing.
Fluid decrease Fluid increase
1
2
3
3
4
4

16 3.793.5275.200
5.1 Potentiometer transmitter characteristics
A potentiometer, a device comprising a printed circuit board on which a reed /resistance chain is
welded, is placed inside the oat’s vertical guide tube.
The total resistance of a known value is measured at the ends of this potentiometer.
The oat, following the liquid level trend, activates the potentiometer’s reed contact chain through
its own magnetic eld, locally closing the signal.
The total value of the resistance, is measured 100% at its maximum level and 0% at its minimum level.
The end poles of the potentiometer are connected to a converter that transforms the input value
into Ohm and the output into mA.
Reading resolution available: 5, 10, 20 mm
Resistance input 1 k ÷ 100 k Ohm. The Ohm-mA signal converters are inside the
housing. Three types of converter are available:
1 Converter for safe zone
2 Converter for inbuilt safety zone, ATEX certied.
3Converter suitable for HART®protocol, suitable
for intrisically safe, ATEX certied
Resistance input 1 k ÷ 100 k Ohm
Current output 4 ÷ 20 mA
Type 1and 2 converters can be eld set using two
trimmers [for the Z (zero) gauging and G (Gain)
gauging], without resorting to interconnecting
systems.
The type 3converter must be regulated with an
interconnection cable.
Converter for safe zone
Converter for inbuilt safety zone
Converter suitable for HART®protocol
5. Transmitter

17
3.793.5275.200
6.1 Disassembling
Before disassembly of the level switch disconnect or isolate any electricity supply or circuit and
depressurize the tank.
Warning: do not disassemble the level switch before the tank has been emptied.
6.1.1 Open housing. For E Ex-d housings wait at least ve minutes before open.
6.1.2 Disconnect electric circuit cables. Close housing.
6.1.3 When anged, unscrew connection bolts; when screwed, use adequate screwdrivers.
6.1.4 Extract level switch from the tank paying attention to avoid any damage to the oat.
Periodical inspections are necessary to guarantee complete eciency of the unit. A regular maintenance
programme starting from its initial installation is recommended. The suggested precautions are
important to obtain the best operating conditions of the level control.
The instrument does not require preventive maintenance, however it is recommended that from
time-to-time a check of the liquid uidity is actioned to avoid any suspensions or deposits that can
inuence wetted parts. Also check that the oat moves freely.
6. Disassembling

18 3.793.5275.200
The available spare parts are detailed below. No other parts are supplied as spares.
Available spares
Float 6
Contact 7a
Transmitter 7b
Converter 2a
7. Spare parts
6
7a 7b
2a
How to order spares
Always order spares by using the description
given in the column headed 'Available spares'
and state the size and serial number of the unit
which is indicated on the name-plate:
Example:
1 o Float for a Spirax Sarco Colima TOR A having
DN50 anged PN6 (AISI 304 stainless steel)
connections - Serial number 4567W.

19
3.793.5275.200
8. ATEX Conformity
Here below are listed the name-plates of compliance for the standard products covered in this
instruction; for all special versions derived from standard are supplied against a specic order, an
"ad hoc" documentation will be issue by our Documentation and Test Departement.
Flameproof (explosion-proof) enclosure for use in places at risk of explosion; the device is designed
to be employed with process liquids that have a maximum operating temperature equal to 85°C.
Electrical connections used for cable entries must have their own ATEX certication. During the
connection, make sure that the wires inside the enclosure are at a minimum distance of 3 mm from
the housing wall.
Electrical specications
220 Vac /1 Aac
220 Vcc /1Acc
24 Vcc /1Acc

3.793.5275.200 EMM Issue 9 - 2018.07
Spirax-Sarco s.r.l. - Via per Cinisello, 18 - 20834 Nova Milanese (MB) - Tel.: +39 0362 49 17.1 - Fax +39 0362 49 17 307
SERVICE
For technical support, please contact our local Sales Engineer or our Head Oce directly:
Spirax Sarco S.r.l. - Technical Assistance
Via per Cinisello, 18 - 20834 Nova Milanese (MB) - Italy
Tel.: (+39) 0362 4917 257 - (+39) 0362 4917 211 - Fax: (+39) 0362 4917 315
E-mail: [email protected]
LOSS OF GUARANTEE
Total or partial disregard of above instructions involves loss of any rights to guarantee.
This manual suits for next models
11
Table of contents
Other Spirax Sarco Switch manuals
Popular Switch manuals by other brands

ZyXEL Communications
ZyXEL Communications Dimension GS-4024 user guide

Siemens
Siemens 3KD36-0P Series operating instructions

Advanced Energy
Advanced Energy Thyro-S 1S H 1 Series manual

Vivotek
Vivotek AW-FET-100C Quick installation guide

Extreme Networks
Extreme Networks BlackDiamond 10808 installation guide

COMEPI
COMEPI SM Series use instructions