Stange SE-707 User manual

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 1
Operating Manual
Program Controller
SE-707
Documentation: October 2018

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
2 Subject to technical modifications
Table of Contents
1 GENERAL........................................................................................................................................................................... 5
1.1 INFORMATION ABOUT THE OPERATING MANUAL ...................................................................................................................... 5
1.2 SYMBOL DECLARATION ...................................................................................................................................................... 5
1.3 EU-CONFORMITY ............................................................................................................................................................ 6
1.4 LIABILITY AND WARRANTY .................................................................................................................................................. 7
1.5 COPYRIGHT PROTECTION.................................................................................................................................................... 7
2 SAFETY.............................................................................................................................................................................. 8
2.1 INTENDED USE................................................................................................................................................................. 8
2.2 ELECTROMAGNETIC COMPATIBILITY (EMC) ............................................................................................................................ 8
2.3 EMC SAFEGUARDING........................................................................................................................................................ 8
2.4 GROUNDING OF INACTIVE METAL PARTS................................................................................................................................. 9
2.5 PE CONNECTION .............................................................................................................................................................. 9
2.6 UNEARTHED OPERATION .................................................................................................................................................... 9
2.7 RESPONSIBILITY OF THE OPERATOR ....................................................................................................................................... 9
2.8 OPERATING PERSONAL .....................................................................................................................................................10
2.9 MAINTENANCE...............................................................................................................................................................10
2.10 CLEANING THE FRONT PANEL ............................................................................................................................................10
2.11 REPAIRS......................................................................................................................................................................10
2.12 MANUFACTURER-ADDRESS .............................................................................................................................................11
2.13 TECHNICAL SUPPORT .....................................................................................................................................................11
2.14 DISPOSAL....................................................................................................................................................................11
3 TRANSPORT, PACKING AND STORAGE ............................................................................................................................12
3.1 TRANSPORT INSPECTION ...................................................................................................................................................12
3.2PACKING.......................................................................................................................................................................12
3.3 STORAGE ......................................................................................................................................................................12
4 TECHNICAL DATA .............................................................................................................................................................13
4.1 HARDWARE CHARACTERISTICS ............................................................................................................................................13
4.2 SOFTWARE SPECIFICATIONS ...............................................................................................................................................15
4.3 FUNCTION BASIC DATA .....................................................................................................................................................16
5 INSTALLATION OF THE INDUSTRIAL CONTROL .................................................................................................................18
5.1 GUIDELINES FOR THE INSTALLATION OF THE SE-707 ................................................................................................................18
5.2 GENERAL MOUNTING INSTRUCTIONS ....................................................................................................................................18
5.3 INSTALLATION DIMENSION.................................................................................................................................................19
5.4 INSTALLATION DEPTH .......................................................................................................................................................20
5.5 FRONT PANEL INSTALLATION ..............................................................................................................................................21
6 START-UP.........................................................................................................................................................................22
6.1 GUIDELINES FOR GROUNDING AND WIRING...........................................................................................................................22
6.2 OVERVIEW OF THE CONNECTIONS........................................................................................................................................23
6.2.1 Function of the LED's at the back of the device.....................................................................................................24
6.2.2 Turn-switch for PLC operating mode selection......................................................................................................25
6.2.3 System Watchdog ...............................................................................................................................................25
6.2.3.1 General ............................................................................................................................................................25
6.2.3.2 Mode of operation ...........................................................................................................................................25
6.2.3.3 System logger entry..........................................................................................................................................26
6.2.4 The alarm relay...................................................................................................................................................26
6.2.4.1 General ............................................................................................................................................................26
6.2.4.2 Mode of operation ...........................................................................................................................................26
6.3 MOUNTING /DISMOUNTING THE SD CARD............................................................................................................................27
6.4 CONNECTING THE POWER SUPPLY........................................................................................................................................28
6.5 PACKAGING THE CAN CABLE WITH SHIELD CONNECTION ...........................................................................................................29
6.6 CONNECTING THE PROGRAMMING INTERFACE RJ45 ................................................................................................................30

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 3
6.7 CONNECTION CAN ......................................................................................................................................................... 31
6.8 CONNECTION OF THE ALARM SOCKET................................................................................................................................... 33
6.9 CONNECTION OF THE PROFIBUS-DP-SLAVE INTERFACE (OPTION) ............................................................................................ 33
6.10 CONNECTION OF THE PROFINET IO DEVICE (SLAVE)INTERFACE (OPTION) ................................................................................ 37
6.11 CONNECTION OF A PC WITH THE SE-707........................................................................................................................... 39
6.11.1 Cabling............................................................................................................................................................. 39
6.12 SETTINGS OF THE PC FOR ETHERNET COMMUNICATION.......................................................................................................... 39
6.12.1 Separation of automation network and company/office network ...................................................................... 39
6.12.2 Length of the network line (segment length) ..................................................................................................... 40
6.12.3 Requirements ................................................................................................................................................... 40
6.12.4 Settings Windows 7/10..................................................................................................................................... 40
6.12.5 Settings of the IP-address in the device ............................................................................................................. 41
7 OPERATION..................................................................................................................................................................... 42
7.1 START-UP BEHAVIOUR ..................................................................................................................................................... 42
7.2 SHUTDOWN BEHAVIOUR .................................................................................................................................................. 42
7.3 START-UP BEHAVIOUR /STARTING ...................................................................................................................................... 43
8 OPERATING DIALOGUE OF THE CONTROL SOFTWARE..................................................................................................... 44
8.1 OPERATION .................................................................................................................................................................. 44
8.1.1 Start screen ........................................................................................................................................................ 45
8.1.2 Programmer....................................................................................................................................................... 45
8.1.3 Manual operation for set value and tracks (”Manual”)........................................................................................ 46
8.1.4 Program curve.................................................................................................................................................... 46
8.1.5 Program jump .................................................................................................................................................... 47
8.1.6 Automatic Program Start.................................................................................................................................... 47
8.1.7 Program change in actual segment..................................................................................................................... 48
8.1.8 Editing of the operating program........................................................................................................................ 48
8.1.9 Controller ........................................................................................................................................................... 49
8.1.10 Control Zone Detail View .................................................................................................................................. 49
8.1.11 PID Parameter.................................................................................................................................................. 50
8.1.12 Control zone tolerance values / limit values....................................................................................................... 51
8.1.13 Plant overview.................................................................................................................................................. 51
8.1.14 Alarms.............................................................................................................................................................. 52
8.1.15 Alarm history.................................................................................................................................................... 53
8.1.16 Process data actual values................................................................................................................................ 53
8.1.17 Process data limit values................................................................................................................................... 54
8.1.18 Process data tolerance values........................................................................................................................... 54
8.1.19 Process data formula value............................................................................................................................... 54
8.1.20 Operating-Hours Meter (Option)....................................................................................................................... 55
8.1.21 Data Logger (Option)........................................................................................................................................ 55
8.1.22 Logger Graph (Option)...................................................................................................................................... 56
8.1.23 Logger Header (Option) .................................................................................................................................... 57
8.1.24 Program start with data logger (Option) ........................................................................................................... 57
8.1.25 Configuration ................................................................................................................................................... 57
8.1.26 Login ................................................................................................................................................................ 58
8.1.27 Login Level Authorisation.................................................................................................................................. 59
8.2 PROGRAM .................................................................................................................................................................... 61
8.2.1 Program overview .............................................................................................................................................. 61
8.2.2 Creating programs.............................................................................................................................................. 61
8.2.3 Programming segments...................................................................................................................................... 62
8.2.4 Copy programs................................................................................................................................................... 62
8.2.5 Delete programs................................................................................................................................................. 63
8.2.6 Load programs to the operating mode................................................................................................................ 63
8.2.7 Sort programs .................................................................................................................................................... 63
8.2.8 Store and load program list ................................................................................................................................ 64
8.2.9 Loops ................................................................................................................................................................. 65
8.3 CONFIGURATION ............................................................................................................................................................ 66
8.3.1 Standard Settings ............................................................................................................................................... 67

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
4 Subject to technical modifications
8.3.1.1 Station Name.................................................................................................................................................................. 67
8.3.1.2 Display screen ................................................................................................................................................................ 67
8.3.1.3 Host Interface................................................................................................................................................................. 68
8.3.1.4 Siemens Modbus Connection (Option) ............................................................................................................................ 69
8.3.1.5 Programmer ................................................................................................................................................................... 69
8.3.1.6 User interface................................................................................................................................................................. 70
8.3.2 Hardware............................................................................................................................................................71
8.3.2.1 CAN Inputs/Outputs ....................................................................................................................................................... 71
8.3.2.2 Hardware Options .......................................................................................................................................................... 72
8.3.2.2.1 Profinet IO Device Interface ......................................................................................................................................... 73
8.3.2.2.2 Profibus-DP Slave interface .......................................................................................................................................... 76
8.3.2.2.3 PROFIBUS Function Description.................................................................................................................................... 78
8.3.3 Functions ............................................................................................................................................................86
8.3.3.1 Digital and analogue inputs/outputs ............................................................................................................................... 86
8.3.3.2 Actual values .................................................................................................................................................................. 87
8.3.3.3 Analogue outputs ........................................................................................................................................................... 94
8.3.3.4 Free linearization curves ................................................................................................................................................. 96
8.3.3.5 Set values....................................................................................................................................................................... 98
8.3.3.6 Control zones ............................................................................................................................................................... 101
8.3.3.7 Tolerances.................................................................................................................................................................... 122
8.3.3.8 Limit values .................................................................................................................................................................. 125
8.3.3.9 Alarm monitoring ......................................................................................................................................................... 128
8.3.3.10 Formula / constants.................................................................................................................................................... 132
8.3.3.11 PLC Statement List ...................................................................................................................................................... 134
8.3.3.12 Analogue Variables ..................................................................................................................................................... 140
8.3.3.13 Digital tracks............................................................................................................................................................... 142
8.3.3.14 Process steps.............................................................................................................................................................. 143
8.3.3.15 Analogue multiplexers ................................................................................................................................................ 144
8.3.3.16 BCD/BIN Decoders...................................................................................................................................................... 145
8.3.4 Special Functions...............................................................................................................................................148
8.3.4.1 C-Level (Option)............................................................................................................................................................ 148
8.3.4.2 Humidity Calculation..................................................................................................................................................... 152
8.3.4.3 Data Logger (Option) .................................................................................................................................................... 153
8.3.4.4 Operating-Hours Meter (Option)................................................................................................................................... 163
8.3.5 User Administration ..........................................................................................................................................164
8.3.5.1 User ............................................................................................................................................................................. 164
8.3.5.2 User Groups ................................................................................................................................................................. 165
8.3.5.3 Automatic user login..................................................................................................................................................... 167
8.3.5.4 User Profile Modbus..................................................................................................................................................... 167
8.3.6 Settings.............................................................................................................................................................168
8.3.6.1 Date / Time .................................................................................................................................................................. 168
8.3.6.2 Language dialogue........................................................................................................................................................ 169
8.3.6.3 Program Graph Pen Settings ......................................................................................................................................... 169
8.3.7 Administrate configuration................................................................................................................................170
8.3.7.1 Load configuration........................................................................................................................................................ 170
8.3.7.2 Save configuration........................................................................................................................................................ 170
8.3.7.3 Import configuration from SE-5xx or SE-4xx device ........................................................................................................ 171
8.3.7.4 Import licence file......................................................................................................................................................... 171
8.3.7.5 Reset configuration/programs (general reset) ............................................................................................................... 171
8.3.8 Update Firmware and/or license update............................................................................................................172
8.3.8.1 Requirements............................................................................................................................................................... 172
8.3.8.2 Execution of the update process ................................................................................................................................... 172
8.3.9 Hardware test ...................................................................................................................................................173
8.3.9.1 Device information ....................................................................................................................................................... 173
8.3.9.2 Software information.................................................................................................................................................... 173
8.3.9.3 Licence information...................................................................................................................................................... 174
8.3.9.4 Device health................................................................................................................................................................ 174
8.3.9.5 Digital In-/Outputs........................................................................................................................................................ 174
8.3.9.6 Save diagnosis data....................................................................................................................................................... 174
INDEX .................................................................................................................................................................................175

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 5
1 General
1.1 Information about the operating manual
This operating manual shall put the user into the position to install, put into operation, administrate and service the device
properly.
Read and understand the operating manual completely, in particular the chapter security, before the beginning of the
installation work! Comply with the operating manual, in particular the safety references as well as the regulations for the
prevention of industrial accidents, valid for the area of application, absolutely.
Always pass the device together with the operating manual to a third party.
1.2 Symbol declaration
Important safety-relevant references are characterized by symbols in this manual. Comply with the references absolutely, in
order to avoid accidents, damages to persons and physical damage.
WARNING!
This symbol marks dangers which result in impairment of health, injuries, lasting physical injury or to
death, as well as substantial property damage.
Keep the displayed references to the operational safety absolute exactly and behave in these cases
particular carefully.
WARNING! Danger by electric current!
This symbol makes attentive to dangerous situations by electric current. In case of non-observance of
the safety references the danger of heavy injuries or death exists like substantial damage to property.
The executed work may be implemented only by an instructed electrical specialist.
ATTENTION ! Consider ESD electronic protective measures!
Electrostatic unloading may destroy electronic components.
ATTENTION !
This symbol marks references, whose non-observance can result in damages, malfunctioning and/or loss
of the device.
Note
This symbol emphasizes hints and information, which are to be considered for an efficient and trouble
free operation of the device.

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
6 Subject to technical modifications
1.3 EU-Conformity
We, the company
Gutenbergstr. 3
D-51645 Gummersbach
declare under sole responsibility, that the product
Name: Program Controller
Type: SE-707
fulfils the requirements of the standard
EN 61000-6-4:2007+A1:2011 Emission
EN 61000-6-2:2005 Interference resistance
and therefore corresponds to the regulations of the EU-Directive 2014/30/EU (electromagnetic compatibility).
Gummersbach, 2018-06-25 P. Jaspert (Managing Director)
_________________________________ _________________________________
Place and Date of Issue Name, authorized Signature
The device was tested in a typical situation.
If modifications are made without our agreement this declaration loses its validity.
The device does not fall into the range of application of the low-voltage directive EEC 73/23/EEC (electrical equipment for the
use within certain voltage limits (low-voltage directive); changed by 93/68/EEC)
(This declaration follows closely to EN 45 014)

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 7
1.4 Liability and warranty
All specifications and notes in this manual were arranged with consideration of the valid regulations, the current engineering
level of development as well as our realizations and experiences of many years.
The translation of the manual was likewise provided after best knowledge. We cannot take over a liability for translation
errors however. Considerably applies the provided German version of this manual.
The actual scope of supply can deviate with special equipment, the demands of additional order options or due to newest
technical changes possibly from the explanations and graphic representations described here. Please contact the
manufacturer if you have questions.
Note!
This manual is to be perused before the beginning of all work on and with the device, in particular before the
start-up! For damage and troubles, which result from the non-observance of the manual, the manufacturer
does not take over liability.
The manual is to be put aside and directly accessible with the device for all persons, who work on or with the device. The
assignment of the manual to third party is not permitted and obligates if necessary to compensation. Further requirements
reserved.
We reserve technical changes at the device in the context of the improvement of the performance characteristics and the
advancement.
1.5 Copyright protection
The manual is to be kept in confidence. It is exclusively intended for persons employed at and with the device. The
assignment of the manual to third party is inadmissible without written agreement of the manufacturer. With requirement
please contact the manufacturer.
Note !
The content-wise specifications, texts, designs, pictures and other representations are copyrighted and are
subject to further industrial property rights. Each abusive utilization is liable to prosecution.

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
8 Subject to technical modifications
2 Safety
This section gives an overview of all important safety aspects for an optimal protection of the personnel as well as safe and
trouble free operation of the device.
Additionally the individual chapters contain concrete safety references, marked by symbols, for the prevention of direct
dangers. Beyond those pictograms, signboards and markings are present at the device, which have to be kept in constantly
readable condition.
2.1 Intended use
The industrial control exclusively serves for the control of machines and plants, which are build according to the applicable
regulations and equipped with all necessary safety installations.
The operational reliability is ensured only by the intended use of the device.
ATTENTION !
Each use of the device going beyond the intended use and/or different use is forbidden and is
considered as not intended. In particular the use of the device for the control or as replacement of
safeguarding equipment in the sense of the machine directive (98137 EG) is not permitted.
Requirements of any kind against the manufacturer and/or its authorized persons because of damage
on the basis of not intended use of the device are excluded.
For all damages on the basis of not intended use the operator is responsible alone.
Among the intended use also the correct adherence of the operating ranges as well as the installation-,
operation- and cleaning instructions.
2.2 Electromagnetic compatibility (EMC)
Before installing an EMC planning is necessary, even though devices fulfil the EMC requirements. Disturbance sources
(galvanic, inductive and capacitive coupling) as well as radiation coupling come to consideration thereby.
2.3 EMC safeguarding
The following requirements should be kept, in order to safeguard EMC:
•Inactive metal parts must have a correct and extensive grounding.
•Wires and devices have a correct shielding.
•Wiring and line run must be executed correctly.
•The electric equipment is grounded and has a uniform reference potential.
•Special applications need specific EMC measures.

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 9
2.4 Grounding of inactive metal parts
The influence of coupled interferences can be reduced, if all inactive metal parts (switch cabinet, switch cabinet door,
mounting plates, top hat rails etc.) are connected extensive and low-impedance with each other. The uniform reference
potential area results for control elements for this reason.
•In the range of bolted connections the insulating layer must be removed in case of painted eloxadized or isolated
metal parts. It has to be cared for corrosion protection of junctions.
•Connection of all free moving groundable components (cabinet doors, separate mounting plates, etc.) by using short
bonding straps to large surface areas.
•No use of aluminium parts if possible, because the oxidation of aluminium is inappropriate for grounding.
2.5 PE connection
Connect ground and PE connection (protective earth) centrally.
2.6 Unearthed operation
The relevant safety regulations and standards must receive attention in case of unearthed operation.
2.7 Responsibility of the operator
The device may be operated only in technically perfect and safe condition.
Apart from the operational safety notes in this manual are to be considered and kept the generally valid safety regulations
and regulations for the prevention of industrial accidents for the area of application of the device as well as the valid
environmental regulations.
The operator and the personnel authorized by him are responsible for the trouble free operation of the device as well as for
clear definitions over the cognizance during installation, operation, maintenance and cleaning.
The specifications of the manual must be complied completely and without restrictions!
The operator must guarantee beyond that, that
•all further instructions and safety instructions are summarized in an operating instruction in accordance with work
appliance use regulation, which result from the hazard judgement of the employments at the device.
•this manual is integrated into the plant documentation.
•maintenance and inspection intervals are to be kept.
•device, operating equipment and waste products resulting with the manufacturing are disposed environmentally
compatible and in agreement with legal regulations.

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
10 Subject to technical modifications
2.8 Operating personal
The industrial control may be served only by authorized technical personnel. The service personnel must have been
instructed particularly about arising dangers.
As technical personnel is considered, who can judge the transferred work and recognize possible dangers due to his technical
training, knowledge and experiences as well as knowledge of the relevant regulations.
ATTENTION !
This device may only be used for the applications described in the technical descriptions, and only in connection
with devices or components from other manufacturers which have been approved or recommended by STANGE.
This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and
operated and maintained as recommended.
2.9 Maintenance
Battery
The storage battery serves for the backup of the real-time clock and the remanent PLC data. With complete charge, the
storage battery has a holding time of approx. 8-10 weeks. In order to avoid data loss, it should be paid attention to the fact
that the device is switched off not longer than this time. With completely empty storage battery a time of 48 hours operation
is needed, until the storage battery has again its full capacity.
Transport
For the transport of the device is to be used excluding the original packaging.
2.10 Cleaning the front panel
The glass of the front panel is treated on the surface in order to permanently minimise light reflections and the adhesion of
finger prints.
A soft, dry cloth is adequate and provides good service for cleaning the front panel.
2.11Repairs
Repairs at SE-707 may only be made by STANGE Elektronik GmbH. In this case please contact the technical support of
STANGE Elektronik GmbH.
For making changes at the device not described in this document, no liability is accepted.

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 11
2.12Manufacturer-Address
Manufacturer:
STANGE Elektronik GmbH
Gutenbergstr. 3
51645 Gummersbach
Germany
Fon: +49 (0)2261 - 95790
Fax: +49 (0)2261 - 55212
E-Mail: info@stange-elektronik.de
Homepage: www.stange-elektronik.com
2.13Technical Support
Support:
Fon: +49 (0)2261 – 957939
Fax: +49 (0)2261 - 55212
E-mail: support@stange-elektronik.de
2.14Disposal
STANGE units can be recycled. Send back the device delivered free to STANE Elektronik GmbH for disposal. Or contact a
certified electronic waste disposal centre for environmentally acceptable recycling and disposal of your old devices.
Particularly to be considered is:
•The device contains a lithium storage battery.
•The device contains LED background lighting.
Materials:
Housing: Stainless steel
Front frame: Aluminium
Board: 1. quality
Front glass: Float glass ESG (tempered safety glass)

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
12 Subject to technical modifications
3 Transport, Packing and Storage
3.1 Transport inspection
Examine supply with receipt immediately for completeness and transport damages.
Do not accept delivery or only under reservation with outwardly recognizable transport damage. Note the damage on
transportation document/delivery note of the carrier. Start reclamation.
Reclaim hidden damages immediately after recognizing (at the latest within 8 days (date of receipt)) in writing, because
claims for damages can be made valid only within the valid complaint periods.
3.2 Packing
For the transport of the device is to be used excluding the original packaging.
3.3 Storage
Keep packages up to the assembly locked and considering of the environmental conditions for storage.

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 13
4 Technical data
4.1 Hardware characteristics
Display
Technology
TFT LCD 30.7 cm (12.1”)
Resolution
1280 x 800 pixels (WXGA)
Number of colours
16 Mil. colours
Backlight
LED
Front
ESG glass 3 mm
Operation
Type
Capacitive Touch
Dimension
W x H x D
370 x 260 x 106 mm
Weight
approx. 3,7 kg
Protection class
Front
IP 65 (NEMA 12), according to EN 60529
Back
IP 20
Environmental
condition
Climate operation
0 ... 45 °C, 10 ... 90 % relative humidity, non-condensing
Climate storage
-20 ... 60 °C, 10 ... 90 % relative humidity, non-condensing
EMC interference resistance
EN 61000-6-2
Interference radiation
EN 61000-6-3
Power supply
Voltage
24 V DC (18 … 30 V)
Voltage drops
10 ms according EN 61000-6-2
Reverse voltage protection
Yes
Fuse
Solder fuse, 2 A slow-blow
Electrical isolation
Yes
Current consumption
Typ. 500 mA at 24 VDC (for 2 min. after power-on 750 mA)
Power consumption
Typ. 20 W
Battery back-up
Battery type
Lithium battery
Data conservation
min. 8-10 weeks
Battery charge
Complete after approx. 48 hours operation
System time
Real-time clock (RTC)
Date/Time
Accuracy
50 ppm (max. 131 seconds deviation per month)
Time levelling
Manual or over network time server
Memory card
SD card
Data logger

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
14 Subject to technical modifications
Interfaces
Alarm output
Semiconductor relay output, 24V AC/DC, 300 mA,
contact type normally open contact, potential-free
Watchdog output
Semiconductor relay output, 24V AC/DC, 300 mA,
normally closed contact, potential-free
CAN
CANopen fieldbus,
9-pole SubminD connector, electrically isolated
USB 1 and 2
USB connection (female) for external storage medium (USB-
Memory-Stick)
Ethernet connector
Ethernet 10/100 Mbit/s, RJ45 female connector
Profibus-DP (optional!)
Profibus-DP Slave,
optional interface module,
9-pole SubminD connector, electrically isolated
Processor core
CPU
Freescale™ i.MX 6 ARM
Random access memory
1 GB DRAM
Memory for mains failure safe data
(PLC retain memory)
1 MB SRAM, battery backed

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 15
4.2 Software specifications
Operating system
Windows Embedded Compact 7
PLC
PLC with 3200 statements, 128 timers, programmable in STL
Functions
Controller
Up to 20 control zones (depending on stage of extension
)
Programmer
Programmer function with up to 30 set values and 64 control tracks
(depending on stage of extension)
Recipe management
Management of up to 99 recipes, Import/Export possibility over USB
Memory-Stick or STANGE ECS control system
Alarms
Alarm processing with up to 200 alarms and alarm history
(depending on stage of extension)
Data logger (optional!)
Up to 32 data channels (depending on stage of extension)
Operation and
visualization
- Ready-made graphical user interface installation possibility of
customer-specific screen pages and/or unit diagrams (depending on
stage of extension)
- Administration of 8 operating levels (user profiles)
- Online language switching with Unicode language support
(Russian, Chinese etc.) (depending on stage of extension)
Control system
ECS
SE-707 are designed for STANGE ECS control system connection
"Open" control system interface
In the system the PLC program has priority over the
visualization.
Delays in the visualization may occur
during file transfers (such
as project downloads, FTP, WEB servers), or during
communication with the development system
(e.g. PLC
debugging) as the visualization has the lower priority.
The SD™ storage media (industrial grade) used by STANGE
Elektronik are suitable for the cyclic data recording. Only use the
storage media enclosed to the device.
No formatting of the storage media (loss of the boot sector)!

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
16 Subject to technical modifications
4.3 Function basic data
Function
SE-707/Ext
SE-707/Basic
General
Instrument name
SE-707
SE-707
Instrument code
702001
702000
Instrument code MODBUS
72
72
Number of function units (Unit’s)
1
1
Operating dialog languages
4
4
Value descriptions (SV, AV etc.)
24 characters
24 characters
Dimension text
10 characters
10 characters
Number range in case of several values
-9.99999e15 ..
+9.99999e15
-9.99999e15 ..
+9.99999e15
User administration
Number of users total
32
32
Maximum number of logged in users at the same time
10
10
User profile
8
8
Login name, maximum length
15 characters
15 characters
Password, maximum length
40 characters
40 characters
User name
40 characters
40 characters
Comment field
1024 characters
1024 characters
I/O’s
Digital inputs
200
64
Digital outputs
200
64
Number of actual values
48
16
Number of average value per actual value
50
50
Number of correction point per actual value
5
5
Free linearization, pair of values
64
64
Number of analogue values
32
16
Maximum CAN node number
15
2
Several individual functions
Number of set values
30
8
Number of digital tracks
64
32
Alarms, external
200
64
Alarms, internal (but only partly used!)
40
40
Alarm history, number of entries
300
150
Alarm text length
100 characters
100 characters
Limit values
40
16
Tolerances
40
16
Formula
20
8
Formula term
31
31
Constants
40
40
Analogue variables
80
80
Number of Modbus data words
200
200
Variables string length
32 characters
32 characters
Analogue value multiplexer
10
5
BCD/BIN decoder
5
5

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 17
Controller
Number of control zones
20
8
PID sets per control zone
8
8
Controller types
2P heating, 2P cooling, 2P-PID heating,
2P-PID heating, PID heating, PID cooling,
PID / PID, PID / 2P, PID / 2P-PID, 2P-PID /
PID, 2P-PID / 2P 2P-PID / 2P-PID, 2P /
PID, 2P / 2P-PID, 2P / 2P, 3 point step
Programmer
Number of time axis
1
1
Program name length
32
32
Set values
30
8
Digital tracks
64
32
Process steps
50
50
Program segments (inclusive start segment)
201
201
Maximum segment time
999:59:59
999:59:59
Maximum program time
1 year
1 year
Loops
8
8
Loop segments
1000000
1000000
Max. number of repetitions
9999
9999
Program archive, number of programs
250
99
Program number range
1..9999
1..9999
Program graphics, number of pins set value
6
6
Program graphics, set value pages
5
2
Program graphics, number of pins digital tracks
6
6
Program graphics, digital tracks pages
11
6
PLC
PLC instructions
3200
3200
Digital input variables
800
800
Digital output variables
800
800
PLC function inputs
1146
1146
PLC function outputs
1615
1615
Flag, not zero voltage safe
256
256
Flag, zero voltage safe
256
256
Comment text length (only monolingual!)
50 characters
50 characters
Data Logger (option)
Number of data loggers
1
1
Number of log values
32
32
Number of header data
20
20
Maximum log data set number
100000
100000
Maximum alarm event number
10000
10000
File number log data directory
200
200
Number of columns log data archive
3
3
Pixel width archive display
380
380
Number of pens graphic display
16
16
Number of pen groups
5
5
Further Functions
Plant picture
Yes, option
Yes, option
Screensaver
Yes
Yes
C-level formula
2, option
1, option
Humidity calculation formula
2
1
Fieldbus interface „netJACK“, Profinet IO DEVICE
Yes, option
Yes, option
Fieldbus interface „netJACK“, Profibus-DP Slave
Yes, option
Yes, option

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
18 Subject to technical modifications
5 Installation of the industrial control
5.1 Guidelines for the installation of the SE-707
Separate the SE-707 device from heat, high voltage, and electrical noise
As a general rule for laying out the devices of your system, always separate the devices that generate high voltage and high
electrical noise from the low-voltage, logic-type devices such as the SE-707.
When configuring the layout of the SE-707 inside your panel, consider the heat-generating devices and locate the electronic-
type devices in the cooler areas of your cabinet. Operating any electronic device in a high-temperature environment will
reduce the product life.
Consider also the routing of the wiring for the devices in the panel. Avoid placing low voltage signal wires and
communications cables in the same tray with AC power wiring and high-energy, rapidly-switched DC wiring.
5.2 General mounting instructions
All SE-707 devices are mounted from the front, i.e. in a control panel. They are fastened from the rear with the supplied
fixing frame and 2 securing nuts.
All SE-707 devices can be operated up to a maximum ambient temperature of 45°C. The ambient temperature stated applies
to the area in the direct vicinity of the lower connectors, if the device is mounted vertically with unimpeded air convection
and a maximum operating height of 2000 m above sea level. The cooling slots must always be free in order to ensure the
proper cooling of the system.
The device can be mounted in an enclosure if the ambient temperature is taken into consideration. Provide a wall clearance
of at least 50 mm on all sides of the housing, so that sufficient air circulation is ensured. A minimum clearance of 75 mm
from active elements such as load current supply, transformers etc. must be ensured.
Avoid the exposure of the flat screen to direct sunlight. The radiation from the sun (UV component) reduces the lifespan of
the LCD display.
ATTENTION !
The following must be ensured in order to prevent the device from overheating during operation:
-The cooling slots must always be free in order to ensure the proper cooling of the system.
-Avoid the exposure of the flat screen to direct sunlight.
-The mounting angle must not exceed ± 35° from the vertical
If these conditions cannot be met, the mounting of an external fan is recommended.

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications 19
5.3 Installation dimension
Installation dimension SE-707:
The device requires a mounting cut-out of B x H: 354 x 238 mm +/-0,5mm
The thickness of the front panel may not exceed 7 mm.
For better sealing: Use mounting frame rearwards.
196,6
312,0
346,0
354,0
229,8
238,0

Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
20 Subject to technical modifications
5.4 Installation depth
Installation depth SE-707:
The Installation depth for the SE-707: 99.2 mm.
Length of the mounting clips: 65 mm behind the mounting plate
Table of contents
Popular Controllers manuals by other brands

nord
nord NORDAC BASE SK 1 0E Series quick start

BENDIX
BENDIX EC-15 ANTILOCK CONTROLLER ASSY installation instructions

Aerotech
Aerotech Ensemble HLe Hardware manual

Mitsubishi
Mitsubishi FX3U Series Hardware manual

nvent
nvent RAYCHEM Elexant 4010i user manual

Graco
Graco Advanjet Diaphragm-Jet HV-2000 Setup and operation